Lennox Signature SLP99UHVK Furnace Codes
The SLP99UHVK installation instructions (508587-03, pp. 46-49) print the same table word for word.
| Code | Meaning | What to check |
|---|---|---|
| E105 | Device communication problem: no other devices on the bus. | Check for miswiring and loose connections, and for a high voltage noise source near the system (a welder, etc.). How to fix → |
| E110 | Low line voltage (below the nameplate rating). | Check line voltage. |
| E111 | Line voltage polarity reversed. | Reverse the line voltage wiring. Resumes 5 seconds after recovery. |
| E112 | Earth ground not detected; system shuts down. | Provide a proper earth ground. Resumes 5 seconds after recovery. |
| E113 | High line voltage (above the nameplate rating). | Check line voltage. |
| E114 | Line voltage frequency out of range. | No 60 Hz power: check voltage and frequency. |
| E115 | Low 24 V (the control restarts if it recovers). | 24 V range is 18 to 30 V. Check voltage. |
| E117 | Poor ground detected (warning only). | Provide proper grounding for the unit. Clears 30 seconds after recovery. |
| E118 | Reset limit exceeded (hard lockout). | The unit went into soft lockout and was manually reset six times within 15 minutes. Cycle power to clear it after fixing the fault. |
| E120 | Unresponsive device. | Usually the outdoor unit is slow to answer the indoor unit's polling. Cycle power and check wiring. How to fix → |
| E124 | Communicating thermostat signal missing for more than 3 minutes. | Check connections and cycle power at the thermostat. How to fix → |
| E125 | Control failed self-check or hardware (flame sense circuit faults, pin shorts, etc.); control not communicating. | Cycle power on the control. Replace it if the problem prevents service and persists. |
| E126 | Failed internal communication between the control's microcontrollers. | Cycle power on the control. Replace it if the problem prevents service and persists. |
| E150 | Refrigerant leak detected. | May mean a leak at or in the indoor coil that must be repaired, and the charge verified. Can't be cleared while the sensor still reports a leak. |
| E151 | Refrigerant leak detector sensor #1 fault. | The sensor reports a problem that stops it working; it may need replacing. Clears when it no longer reports a fault. |
| E152 | Refrigerant leak detector sensor #2 fault. | The sensor reports a problem that stops it working; it may need replacing. Clears when it no longer reports a fault. |
| E154 | Refrigerant leak detector sensor #1 communication lost, or invalid sensor DIP switch setting (disable/enable). | Check the harness and connector between the sensor and the furnace control for damage or poor connection, and the sensor for damage or an obstructed harness plug. Clears when communication returns; the blower latches on for at least 5 minutes. Retest with the Low GWP test button. May also mean the Low GWP DIP switches are set wrong. |
| E155 | Refrigerant leak detector sensor #2 communication lost. | Check the harness and connector between sensor #2 and the furnace control, and the sensor and its plug. Clears when communication returns; the blower latches on for at least 5 minutes. Retest with the Low GWP test button. |
| E160 | Refrigerant leak detector sensor #1 is the wrong type. | Replace it with a Lennox-approved sensor. Clears when a suitable sensor is detected; the blower latches on for at least 5 minutes. Retest with the Low GWP test button. |
| E161 | Refrigerant leak detector sensor #2 is the wrong type. | Replace it with a Lennox-approved sensor. Clears when a suitable sensor is detected; the blower latches on for at least 5 minutes. Retest with the Low GWP test button. |
| E163 | Furnace control board failure. | May need a new indoor control board. Clears when the control operates normally. |
| E164 | Low GWP test. | Started with the Low GWP test button. Normal operation resumes and the code clears after 1 minute. |
| E180 | Outdoor air sensor failure (no error if disconnected; shown only if shorted or out of range). | Lennox gives no action in this table. Check the sensor and its wiring. |
| E200 | Hard lockout: rollout circuit open or previously open. | Correct the cause of the rollout trip or replace the rollout switch, then test furnace operation. How to fix → |
| E201 | Indoor blower communication failure: can't communicate with the blower motor. | Includes power outage. Check power and wiring to the motor. How to fix → |
| E202 | Indoor blower motor mismatch: motor horsepower doesn't match unit capacity. | Wrong furnace size code selected. Check the unit size codes on the configuration guide or in the installation instructions. |
| E203 | Furnace size not programmed (invalid unit code). | No furnace size code selected. Check the unit size codes on the configuration guide or in the installation instructions. |
| E204 | Gas valve miswired. | Check operation of the gas valve. |
| E205 | Gas valve control relay contact shorted. | Check operation of the gas valve. |
| E207 | Hot surface igniter sensed open. | Measure igniter resistance; replace if open or out of spec. How to fix → |
| E223 | Low pressure switch failed open. | Check the switch's closing pressure (inches w.c.) on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix → |
| E224 | Low pressure switch failed closed. | Check the low pressure switch for closed contacts, measure operating pressure, inspect the vent and inducer. How to fix → |
| E225 | High pressure switch failed open. | Check the switch's closing pressure (inches w.c.) on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix → |
| E226 | High pressure switch failed closed. | Check the high pressure switch for closed contacts, measure operating pressure, inspect the vent and inducer. How to fix → |
| E227 | Low pressure switch open during trial for ignition or run mode. | Check the switch's closing pressure (inches w.c.) on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix → |
| E228 | Pressure switch calibration failed. | Retries after 300 seconds; the error counter clears when it leaves lockout. Check the vent system and pressure switch wiring. How to fix → |
| E240 | Low flame current, run mode. | Check flame microamps (Table 22 above), clean or replace the sensor, and measure neutral to ground for a good unit ground. How to fix → |
| E241 | Flame sensed out of sequence; flame still present. | Shut off the gas and check the gas valve for a leak. |
| E250 | Limit switch circuit open. | Find why the limit trips: overfiring or low airflow. How to fix → |
| E252 | Discharge air temperature too high (gas heat only). | Check temperature rise, airflow and input rate. How to fix → |
| E270 | Soft lockout: too many retries, no flame current sensed. | Check gas flow, that the igniter lights the burner, and flame sensor current. How to fix → |
| E271 | Soft lockout: too many retries; last retry failed when the pressure switch opened. | Same as E223. How to fix → |
| E272 | Soft lockout: too many recycles; last recycle due to the pressure switch opening. | Same as E223 and E225. How to fix → |
| E273 | Soft lockout: too many recycles; last recycle due to flame failure. | Same as E240. How to fix → |
| E274 | Soft lockout: too many recycles; last recycle failed on the limit, or the limit stayed open over 3 minutes. | Same as E250. How to fix → |
| E275 | Soft lockout: flame sensed out of sequence (code 241); flame signal now gone. | Same as E241. |
| E276 | Soft lockout: too many calibration retries. | Same as E228. How to fix → |
| E290 | Igniter circuit fault: failed igniter or triggering circuitry. | Same as E207. How to fix → |
| E291 | Restricted airflow: cfm below what minimum firing rate needs. | Check for a dirty filter, airflow restriction and blower performance. How to fix → |
| E292 | Indoor blower motor can't start (seized bearings, stuck wheel, etc.). | Replace the motor or wheel if the assembly doesn't run or meet performance. |
| E294 | Combustion air inducer amp draw too high. | Check inducer bearings, wiring and amps; replace if it doesn't run or meet performance. How to fix → |
| E295 | Indoor blower motor temperature too high (tripped on its internal protector). | Check motor bearings and amps; replace if needed. |
| E310 | Discharge air sensor failure (no error if disconnected; shown only if shorted or out of range). | Discharge air temperature sensor reading out of range; the code is activated during Field Test mode. |
| E311 | Heat rate reduced to match indoor blower airflow. | The blower is in cutback for restricted airflow. Replace the filter if needed or repair/add ductwork. How to fix → |
| E312 | Restricted airflow in cooling or continuous fan: below the cfm setting. | The blower is in cutback to protect the motor outside its design range (0 to 0.8 in. w.c. total external static). Check the filter and ductwork. How to fix → |
| E313 | Indoor and outdoor unit capacity mismatch. | Wrong capacity code. Check configuration. Warning only; clears when commissioning is exited. |
| E331 | Global network connection: communication link problem. | Lennox lists this as for future use. |
| E345 | O relay failure. | Replace the integrated control. |
| E347 | No 24 V output on Y1 to C with a non-communicating outdoor unit. | The Y1 relay or stage 1 failed (pilot relay contacts didn't close or the coil didn't energize). |
| E348 | No 24 V output on Y2 to C with a non-communicating outdoor unit. | The Y2 relay or stage 2 failed (pilot relay contacts didn't close or the coil didn't energize). |
| E370 | Interlock switch sensed open for 2 minutes. | The control saw 24 VAC missing for 2 minutes and stops all services until the interlock closes. Clears when 24 VAC is on the DS terminal for at least 10 seconds, or on a power reset. |
| E390 | Low GWP relay stuck. | A problem with the Low GWP relay in the furnace control; may need a new indoor control board. Clears when the relay works normally. |
How to read the codes
- Hold the push button: a new menu item shows every 5 seconds; release on the one you want. P means the furnace size is programmed. E enters error code recall (b exits; c clears the error history, press again while it flashes). A dash enters Field Test mode (solid C starts pressure switch calibration; a blinking dash exits).
- Status displays: a blinking decimal point means idle; A blower cfm; C cooling stage then cfm; d dehumidification; h variable capacity heat, % of input rate then cfm; H heat stage then cfm; dF defrost; U discharge air temperature.
- Two horizontal bars: soft disable. The thermostat found a device on the bus it doesn't recognize. Check wiring between all devices, cycle power to the control showing the code, rerun thermostat setup, then Setup > System Devices > Thermostat > Edit > Reset (and ResetAll).
- Flame signal: Lennox's Table 22 for this furnace: normal 2.6 µA or greater, low 2.5 or less, drop-out 1.1.
- E150-E164 and E390 are the A2L refrigerant detection (Low GWP) codes; the Low GWP test button on the control runs the test.
Source: Lennox SLP99UHVK With R454B Unit Information, Service Literature 100181, LED Segment Status p. 18, Integrated Control Diagnostic Codes pp. 19-22, Table 22 flame signal p. 34; same table in installation instructions 508587-03 (05/2026) pp. 46-49. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R96MSN / N96MSN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R95MSU (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N95ESN / R92ESN (single-stage 35-in. condensing, 4-way multipoise; also PG95ESA)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N92ESN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96P / 96MDP (96% two-stage condensing, PSC blower; model numbers (-)96P and (-)(-)96MDP, e.g. R96PA0702317MSA)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Rheem / Ruud R98V (98% modulating communicating, upflow)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox EL296UHV / SL280UHV control 107045 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, two-stage, variable-speed, communicating; EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C)
- Lennox EL296UHV / SL280UHV control 103130 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, earlier units: EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C, SL280UH060NV36A, SL280UH080NV48B, SL280UH080NV60C, SL280UH100NV60C)
- Lennox Elite EL297UHVK(X) / EL297DFVK (two-stage, variable-speed, communicating; upflow/horizontal EL297UH045XV36BK, EL297UH070XV36BK, EL297UH090XV36CK, EL297UH090XV48CK, EL297UH090XV60CK, EL297UH110XV48CK, EL297UH110XV60CK, EL297UH135XV60DK; downflow EL297DF045XV36BK, EL297DF070XV48BK, EL297DF090XV60CK, EL297DF110XV60CK; also Merit SL280UHVK and SL280UHNVK: SL280UH070XV36AK, SL280UH090XV48BK, SL280UH090XV60CK, SL280UH110XV60CK, SL280UH070V36AK, SL280UH090V36BK, SL280UH090V48BK, SL280UH090V60CK, SL280UH110V60CK, SL280UH135V60DK, SL280UH060NV36AK, SL280UH080NV48BK, SL280UH080NV60CK, SL280UH100NV60CK)
- Lennox Signature SLP99DFV (Dave Lennox Signature downflow, variable capacity, variable speed, communicating: SLP99DF070XV36B, SLP99DF090XV36C, SLP99DF090XV48C, SLP99DF090XV60C, SLP99DF110XV60C)
- Lennox Elite EL296UHE (96% two-stage, constant torque: EL296UH045XE36B, EL296UH070XE36B, EL296UH090XE48C, EL296UH110XE60C, EL296UH135XE60D; also Elite EL280DFE downflow: EL280DF070E36A, EL280DF090E48B)
- Lennox Elite EL297UHEK (two-stage, constant torque, non-communicating: EL297UH045XE36BK, EL297UH070XE36BK, EL297UH090XE48CK, EL297UH110XE60CK, EL297UH135XE60DK; same control and codes: Elite EL280UHEK and EL280DFEK (80%): EL280UH045E36AK, EL280UH070E36AK, EL280UH070XE36AK, EL280UH090E36BK, EL280UH090E48BK, EL280UH090XE48BK, EL280UH110E48CK, EL280UH110E60CK, EL280UH110XE60CK, EL280DF070E36AK, EL280DF090E48BK)
- Lennox Merit ML196UHEK / Elite EL196UHEK (80% single-stage, constant torque: ML196UH030XE36BK, ML196UH045XE36BK, ML196UH070XE36BK, ML196UH070XE48BK, ML196UH090XE36CK, ML196UH090XE48CK, ML196UH090XE60CK, ML196UH110XE60CK, ML196UH135XE60DK, EL196UH030XE36BK, EL196UH045XE36BK, EL196UH070XE36BK, EL196UH090XE48CK, EL196UH110XE60CK; same control and codes: Elite EL180UHNEK, Merit ML180UHEK, ML193DFEK, Elite EL195UHNEK: EL180UH040NE36AK, EL180UH060NE36AK, EL180UH080NE48BK, EL180UH100NE60CK, ML180UH045E36AK, ML180UH045XE36AK, ML180UH070E36AK, ML180UH070E36BK, ML180UH070XE36BK, ML180UH090E48BK, ML180UH090XE48BK, ML180UH090E60CK, ML180UH110E60CK, ML180UH110XE60CK, ML180UH135E60DK, ML193DF045XE36BK, ML193DF070XE36BK, ML193DF090XE48CK, EL195UH040NE36BK, EL195UH060NE36BK, EL195UH080NE48CK, EL195UH100NE60CK; variable-speed Merit ML180UHVK: ML180UH030V36AK, ML180UH045V36AK, ML180UH070V36AK, ML180UH070V36BK, ML180UH070V48BK, ML180UH090V48BK, ML180UH110V60CK, ML180UH135V60DK)
- Lennox Merit ML196UHE / ML196DFE / ML193UHE (single-stage, red LED controls 103217-03 and 107163-01: ML196UH030XE36B, ML196UH045XE36B, ML196UH070XE36B, ML196UH070XE48B, ML196UH090XE36C, ML196UH090XE48C, ML196UH090XE60C, ML196UH110XE60C, ML196UH135XE60D, ML196DF045XE36B, ML196DF070XE48B, ML196DF090XE48C, ML196DF110XE60C, ML193UH030XE36B, ML193UH045XE36B, ML193UH070XE36B, ML193UH090XE36C, ML193UH090XE48C, ML193UH110XE48C, ML193UH110XE60C; also ML180UHE and ML180DFE: ML180UH045E36A, ML180UH045XE36A, ML180UH070E36A, ML180UH070XE36A, ML180UH070E36B, ML180UH070XE36B, ML180UH090E48B, ML180UH090XE48B, ML180UH090E60C, ML180UH110E60C, ML180UH110XE60C, ML180UH135E60D, ML180DF045E36A, ML180DF070E36A, ML180DF070E36B, ML180DF090E48B, ML180DF110E60C; ML180UHV: ML180UH030V36A, ML180UH045V36A, ML180UH070V36A, ML180UH070V36B, ML180UH070V48B, ML180UH090V48B, ML180UH110V60C; Elite EL195UH (2011): EL195UH045P24B, EL195UH045P36B, EL195UH070P36B, EL195UH070P48B, EL195UH090P36C, EL195UH090P48C, EL195UH090P60C, EL195UH110P48C, EL195UH110P60C, EL195UH135P60D)
- Lennox Merit ML296UHVK / ML296DFVK / ML297UHVK (two-stage, variable-speed; upflow/horizontal ML296UH045XV36BK, ML296UH070XV36BK, ML296UH090XV48CK, ML296UH110XV60CK; downflow ML296DF045XV36BK, ML296DF070XV48BK, ML296DF090XV60CK; ML297UH045XV36BK, ML297UH070XV36BK, ML297UH090XV36CK, ML297UH090XV60CK, ML297UH110XV60CK, ML297UH135XV60DK)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage; also Daikin DM96SN, DM92SN, DC96SN: DM96SN0403AN, DM96SN0603BN, DM96SN0803BN, DM96SN0804CN, DM96SN0805CN, DM96SN1005CN, DM96SN1205DN, DM92SN0403AN, DM92SN0603BN, DM92SN0803BN, DM92SN0804CN, DM92SN0805CN, DM92SN1004CN, DM92SN1005CN, DM92SN1205DN, DC96SN0403BN, DC96SN0603BN, DC96SN0804CN, DC96SN1005CN, DC96SN1205DN)
- Payne PG96VTAB (two-stage condensing, variable-speed, non-communicating, 4-way multipoise)
- Payne PG9YAA / PG9YAB (95% single-stage condensing, direct or non-direct vent)
- Carrier 59TP6C (two-stage condensing with InteliSense, Performance series; also 926TC)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMEC96 / GCEC96 (two-stage, multi-speed ECM: GMEC96, GCEC96, Amana AMEC96, ACEC96)
- Goodman / Amana / Daikin GMSS92 / GMSS96 / GCSS9 (single-stage, 92% and 96%: GMSS92, GMSS96, GCSS92, GCSS96, Amana AMSS92, AMSS96, ACSS92, ACSS96, Daikin VMSS9, VCSS9)
- Goodman / Amana / Daikin GMES92 / GMES96 / GCES96 (single-stage, 92% and 96%: GMES92, GMES96, GCES96, Amana AMES92, AMES96, ACES96, Daikin VMES96, VCES96)
- Goodman / Amana GM9C96 / GC9C96 (two-stage, nine-speed ECM: GM9C96, GC9C96, Amana AM9C96, AC9C96)
- Goodman / Amana GMH8 / GDH8 / GME95 (modified two-stage: 80% GMH8, GDH8, Amana AMH8, ADSH8; 95% GME95, Amana AMEH96)
- Goodman / Amana / Daikin GMS8 / GDS8 (80% single-stage: GMS8, GDS8, Amana AMS8, ADSS8, Daikin VMS8, VDS8)
- Goodman / Amana GMES96 U Ultra-Low NOx (single-stage 96%, U models: GMES96, Amana AMES96)
- Goodman / Amana GM9S96 U Ultra-Low NOx (single-stage 96%, U models: GM9S96, Amana AM9S96; Daikin DM96SN U: DM96SN0403BU, DM96SN0603BU, DM96SN0805CU)
- Goodman / Amana GMVS80 U Ultra-Low NOx (80% single-stage, variable-speed communicating: GMVS80, Amana AMVS80)
- Goodman / Amana GKS9 / AKSS92 (92% single-stage upflow: GKS9, Amana AKSS92)
- Goodman / Amana GMVM97 / GCVM97 ComfortBridge (97% modulating, BA revision and later: GMVM97, GCVM97, Amana AMVM97, ACVM97)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVC96 / GCVC96 BB ComfortBridge (96%, BB revision: GMVC96, GCVC96, Amana AMVC96, ACVC96)
- Goodman / Amana / Daikin AMVC96 / DM96VC / DM80VC ComfortNet (two-character codes: AMVC96, ACVC96, GMVC96, GCVC96 before the BA revision; DM96VC0403BN, DM96VC0603BN, DM96VC0803BN, DM96VC0804CN, DM96VC1005CN, DM96VC1005DN, DM96VC1205DN, DC96VC0403BN, DC96VC0603BN, DC96VC0803BN, DC96VC0804CN, DC96VC1005CN, DC96VC1205DN, DM80VC0603B, DM80VC0604B, DM80VC0805C, DM80VC1005C, DD80VC0603B, DD80VC0805C, DD80VC1005C)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U; also Daikin DM96SC U: DM96SC0603BU, DM96SC0805CU)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96; also Daikin DM97MC/DC97MC: DM97MC0603BNA, DM97MC0803BNA, DM97MC0804CNA, DM97MC1005CNA, DM97MC1205DNA, DC97MC0603BNA, DC97MC0803BNA, DC97MC0804CNA, DC97MC1005CNA)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T / R95T / R92T (90%+ single-stage condensing, constant-torque blower; model numbers (-)951T, (-)95T, (-)(-)95MSX, (-)92T, (-)(-)92MSX, e.g. R95TC0701317MSA, R92TC0701317MSA)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise; also 313AAV, 313JAV)
- Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E)
- York TG9S (95.5% AFUE single-stage PSC, multi-position)
- York TM9T (96% AFUE two-stage PSC, multi-position)
- York TM9X (95.5% AFUE single-stage ECM, multi-position: TM9X040A10MP11, TM9X060B12MP11, TM9X080B12MP11, TM9X080C16MP11, TM9X100C16MP11, TM9X100C20MP11, TM9X120D20MP11)
- York TM9M (97% AFUE modulating PSC, multi-position)
- York YP9C / TP9C / CP9C / LP9C (up to 98% AFUE modulating ECM, multi-position)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58TN0A / 58TN1A (80% two-stage, variable-speed, 4-way multipoise; also 880TA, 881TA)
- Carrier 58TN0B / 58TN1B (80% two-stage, variable-speed, 4-way multipoise)
- Carrier 58TP0A / 58TP1A (80% two-stage, variable-speed ECM, 4-way multipoise; also PG80VTLA)
- Carrier 58TP0B / 58TP1B InteliSense (80% two-stage, variable 25-speed ECM, 4-way multipoise)
- Carrier 59SC5A (single-stage condensing, 4-way multipoise; also 912SB, 912SC, 922SA, 925SA, PG92SAS, PG92SCS, PG95SAS)
- Bryant 925TA (two-stage condensing, 4-way multipoise; also PG95XAT)
- Bryant 926SA (single-stage condensing, multi-speed ECM, multipoise)
- Bryant 926SB (single-stage condensing, 25-speed ECM, InteliSense)
- Carrier 59SC5B / 59SC2D (single-stage 35-in. condensing, 4-way multipoise; also 912SD, 915SB)
- Carrier 59MN7A / 59MN7B (modulating condensing, 4-way multipoise; also 987MA, 987MB)
- Carrier 59MN7C modulating condensing (59MN7C060C17, 59MN7C060C21, 59MN7C080C17, 59MN7C080C21, 59MN7C100C21, 59MN7C120C24; also 987MC)
- Carrier 59TP6B / 59TP6A / 59TN6A two-stage (condensing, two-digit codes; also 926TA, 926TB, 986TB, PG96VAT, PG96VTAA)
- Carrier 59TN6B two-stage condensing (variable-speed: 59TN6B060C17, 59TN6B080C17, 59TN6B080C21, 59TN6B100C21, 59TN6B120C24; also 986TC)
- Carrier 59TN6C two-stage condensing (variable-speed, 35 in. tall: 59TN6C040C14, 59TN6C060C17, 59TN6C080C17, 59TN6C080C21, 59TN6C100C21, 59TN6C120C24)
- Carrier 59TN7A two-stage condensing (variable-speed, 35 in. tall: 59TN7A060C17, 59TN7A080C17, 59TN7A080C21, 59TN7A100C21, 59TN7A120C24)
- Carrier 59SU5A (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- Carrier 59SU5B single-stage Ultra Low NOx (condensing, 35 in. tall: 59SU5B040M17, 59SU5B060M17, 59SU5B080M21, 59SU5B100M21; also PG95MSUA)
- Carrier 59TP7A two-stage InteliSense (condensing, variable-speed, non-communicating: 59TP7A060V17, 59TP7A080V17, 59TP7A080V21, 59TP7A100V21, 59TP7A120V24)
- Carrier 59SC2E / 59SC6A (single-stage 35-in. condensing, 4-way multipoise; also 912SE, PG96MSAA)
- Carrier 58CU0A (80% communicating, Ultra Low NOx, 4-way multipoise)
- Carrier 58SU0A (80% single-stage, ECM blower, Ultra Low NOx, 4-way multipoise; also 830SA)
- Carrier 58SU0B (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display)
- Carrier 58SB0B / 58SB1B / 58SC0B / 58SC1B (80% single-stage, multi-speed ECM, 4-way multipoise; also PG80MSA, PG80MSLA)
- Bryant 820SA / 821SA (80% single-stage, 4-way multipoise)
- Carrier 58SB0A / 58SB1A / 58SC0A / 58SC1A (single-stage, non-condensing; 58SC is the multi-speed ECM version; also 800SA, 801SA, PG80ESAA, PG80ESLA)