Goodman / Amana / Daikin GMSS92 / GMSS96 / GCSS9 Furnace Codes

Applies to: Goodman / Amana / Daikin GMSS92 / GMSS96 / GCSS9 (single-stage, 92% and 96%: GMSS92, GMSS96, GCSS92, GCSS96, Amana AMSS92, AMSS96, ACSS92, ACSS96, Daikin VMSS9, VCSS9). Single red diagnostic LED on the integrated control module.

CodeMeaningWhat to check
NoneNo signal: furnace doesn't run.No 115 V or 24 V at the control (disconnect off, door switch open, 24 V wires loose), blown fuse or breaker, or an internal control fault. Check the 3 A fuse and look for shorts in the 115 V and 24 V circuits before replacing it. How to fix →
Steady onNormal operation.None.
1 flashLockout after too many ignition retries (3 total).Failure to establish flame (no gas, front cover pressure switch stuck open, bad igniter or igniter alignment, wrong orifices, coated or oxidized flame sensor) or loss of flame after it was established (interrupted gas, lazy flames from wrong gas pressure, flue or combustion air restriction, front cover pressure switch opening, weak inducer). Check gas, the front cover pressure switch, the igniter, the flame signal, flue piping and inducer performance. How to fix →
2 flashesPressure switch circuit closed while the inducer isn't running.Inducer pressure switch contacts sticking, or a short in the pressure switch circuit. Replace the switch or repair the short. How to fix →
3 flashesPressure switch circuit not closed with the inducer running; inducer runs continuously.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe, blocked drain system or a weak inducer; wrong pressure switch setpoint or bad contacts; loose wiring. How to fix →
4 flashesPrimary or auxiliary limit circuit open; circulator blower runs continuously.Faulty limit switch; not enough air over the heat exchanger (blocked filters, restrictive ductwork, wrong blower speed, failed blower); loose wiring. How to fix →
5 flashesFlame sensed with no call for heat; inducer and circulator blower run continuously.Short to ground in the flame sense circuit: fix the short at the flame sensor or its wiring.
6 flashesRollout limit open or control board fuse open; circulator blower runs continuously.Flame rollout, misaligned burners, blocked flue or inlet pipe, failed inducer, loose wiring, faulty rollout limit, a short in the thermostat wiring, or the control board fuse. How to fix →
7 flashesLow flame sense microamp signal (furnace still runs).Coated or oxidized flame sensor, sensor out of position in the flame, or lazy flame from wrong gas pressure or combustion air. Clean the sensor, check its alignment, inlet piping and gas pressure against the rating plate. How to fix →
C (continuous rapid flash)115 V or 24 V polarity reversed.115 V polarity reversed at the furnace or control, the orange and gray wires to the transformer reversed, or a poor unit ground. Check the wiring diagram and the ground.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman/Amana/Daikin GMSS9/GCSS9/AMSS9/ACSS9/VMSS9/VCSS9 Service Instructions RS6612012 Rev. 8 (2017), Troubleshooting pp. 44-45. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.