Goodman / Amana / Daikin GMSS92 / GMSS96 / GCSS9 Furnace Codes
| Code | Meaning | What to check |
|---|---|---|
| None | No signal: furnace doesn't run. | No 115 V or 24 V at the control (disconnect off, door switch open, 24 V wires loose), blown fuse or breaker, or an internal control fault. Check the 3 A fuse and look for shorts in the 115 V and 24 V circuits before replacing it. How to fix → |
| Steady on | Normal operation. | None. |
| 1 flash | Lockout after too many ignition retries (3 total). | Failure to establish flame (no gas, front cover pressure switch stuck open, bad igniter or igniter alignment, wrong orifices, coated or oxidized flame sensor) or loss of flame after it was established (interrupted gas, lazy flames from wrong gas pressure, flue or combustion air restriction, front cover pressure switch opening, weak inducer). Check gas, the front cover pressure switch, the igniter, the flame signal, flue piping and inducer performance. How to fix → |
| 2 flashes | Pressure switch circuit closed while the inducer isn't running. | Inducer pressure switch contacts sticking, or a short in the pressure switch circuit. Replace the switch or repair the short. How to fix → |
| 3 flashes | Pressure switch circuit not closed with the inducer running; inducer runs continuously. | Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe, blocked drain system or a weak inducer; wrong pressure switch setpoint or bad contacts; loose wiring. How to fix → |
| 4 flashes | Primary or auxiliary limit circuit open; circulator blower runs continuously. | Faulty limit switch; not enough air over the heat exchanger (blocked filters, restrictive ductwork, wrong blower speed, failed blower); loose wiring. How to fix → |
| 5 flashes | Flame sensed with no call for heat; inducer and circulator blower run continuously. | Short to ground in the flame sense circuit: fix the short at the flame sensor or its wiring. |
| 6 flashes | Rollout limit open or control board fuse open; circulator blower runs continuously. | Flame rollout, misaligned burners, blocked flue or inlet pipe, failed inducer, loose wiring, faulty rollout limit, a short in the thermostat wiring, or the control board fuse. How to fix → |
| 7 flashes | Low flame sense microamp signal (furnace still runs). | Coated or oxidized flame sensor, sensor out of position in the flame, or lazy flame from wrong gas pressure or combustion air. Clean the sensor, check its alignment, inlet piping and gas pressure against the rating plate. How to fix → |
| C (continuous rapid flash) | 115 V or 24 V polarity reversed. | 115 V polarity reversed at the furnace or control, the orange and gray wires to the transformer reversed, or a poor unit ground. Check the wiring diagram and the ground. |
How to read the codes
- Count the flashes. Steady on is normal operation; no light at all means no 115 V or 24 V at the control, a blown 3 A fuse, or a failed control.
- The flash code stops if power to the control is interrupted through the disconnect or the door switch, so read it before opening the blower door.
- After a lockout (1 flash) the control tries again on its own after one hour.
- Goodman's service manual says to turn the power off before repairs and to replace the control fuse only with a 3 A automotive fuse.
Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.
Source: Goodman/Amana/Daikin GMSS9/GCSS9/AMSS9/ACSS9/VMSS9/VCSS9 Service Instructions RS6612012 Rev. 8 (2017), Troubleshooting pp. 44-45. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R96MSN / N96MSN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R95MSU (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N95ESN / R92ESN (single-stage 35-in. condensing, 4-way multipoise; also PG95ESA)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N92ESN (single-stage 35-in. condensing, 4-way multipoise)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96P / 96MDP (96% two-stage condensing, PSC blower; model numbers (-)96P and (-)(-)96MDP, e.g. R96PA0702317MSA)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Rheem / Ruud R98V (98% modulating communicating, upflow)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox EL296UHV / SL280UHV control 107045 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, two-stage, variable-speed, communicating; EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C)
- Lennox EL296UHV / SL280UHV control 103130 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, earlier units: EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C, SL280UH060NV36A, SL280UH080NV48B, SL280UH080NV60C, SL280UH100NV60C)
- Lennox Elite EL297UHVK(X) / EL297DFVK (two-stage, variable-speed, communicating; upflow/horizontal EL297UH045XV36BK, EL297UH070XV36BK, EL297UH090XV36CK, EL297UH090XV48CK, EL297UH090XV60CK, EL297UH110XV48CK, EL297UH110XV60CK, EL297UH135XV60DK; downflow EL297DF045XV36BK, EL297DF070XV48BK, EL297DF090XV60CK, EL297DF110XV60CK; also Merit SL280UHVK and SL280UHNVK: SL280UH070XV36AK, SL280UH090XV48BK, SL280UH090XV60CK, SL280UH110XV60CK, SL280UH070V36AK, SL280UH090V36BK, SL280UH090V48BK, SL280UH090V60CK, SL280UH110V60CK, SL280UH135V60DK, SL280UH060NV36AK, SL280UH080NV48BK, SL280UH080NV60CK, SL280UH100NV60CK)
- Lennox Signature SLP99UHVK (Dave Lennox Signature, variable capacity, variable speed, communicating: SLP99UH070V36BK, SLP99UH070XV36BK, SLP99UH090V36CK, SLP99UH090XV36CK, SLP99UH090V48CK, SLP99UH090XV48CK, SLP99UH090V60CK, SLP99UH090XV60CK, SLP99UH110V60CK, SLP99UH110XV60CK, SLP99UH135V60DK, SLP99UH135XV60DK)
- Lennox Signature SLP99DFV (Dave Lennox Signature downflow, variable capacity, variable speed, communicating: SLP99DF070XV36B, SLP99DF090XV36C, SLP99DF090XV48C, SLP99DF090XV60C, SLP99DF110XV60C)
- Lennox Elite EL296UHE (96% two-stage, constant torque: EL296UH045XE36B, EL296UH070XE36B, EL296UH090XE48C, EL296UH110XE60C, EL296UH135XE60D; also Elite EL280DFE downflow: EL280DF070E36A, EL280DF090E48B)
- Lennox Elite EL297UHEK (two-stage, constant torque, non-communicating: EL297UH045XE36BK, EL297UH070XE36BK, EL297UH090XE48CK, EL297UH110XE60CK, EL297UH135XE60DK; same control and codes: Elite EL280UHEK and EL280DFEK (80%): EL280UH045E36AK, EL280UH070E36AK, EL280UH070XE36AK, EL280UH090E36BK, EL280UH090E48BK, EL280UH090XE48BK, EL280UH110E48CK, EL280UH110E60CK, EL280UH110XE60CK, EL280DF070E36AK, EL280DF090E48BK)
- Lennox Merit ML196UHEK / Elite EL196UHEK (80% single-stage, constant torque: ML196UH030XE36BK, ML196UH045XE36BK, ML196UH070XE36BK, ML196UH070XE48BK, ML196UH090XE36CK, ML196UH090XE48CK, ML196UH090XE60CK, ML196UH110XE60CK, ML196UH135XE60DK, EL196UH030XE36BK, EL196UH045XE36BK, EL196UH070XE36BK, EL196UH090XE48CK, EL196UH110XE60CK; same control and codes: Elite EL180UHNEK, Merit ML180UHEK, ML193DFEK, Elite EL195UHNEK: EL180UH040NE36AK, EL180UH060NE36AK, EL180UH080NE48BK, EL180UH100NE60CK, ML180UH045E36AK, ML180UH045XE36AK, ML180UH070E36AK, ML180UH070E36BK, ML180UH070XE36BK, ML180UH090E48BK, ML180UH090XE48BK, ML180UH090E60CK, ML180UH110E60CK, ML180UH110XE60CK, ML180UH135E60DK, ML193DF045XE36BK, ML193DF070XE36BK, ML193DF090XE48CK, EL195UH040NE36BK, EL195UH060NE36BK, EL195UH080NE48CK, EL195UH100NE60CK; variable-speed Merit ML180UHVK: ML180UH030V36AK, ML180UH045V36AK, ML180UH070V36AK, ML180UH070V36BK, ML180UH070V48BK, ML180UH090V48BK, ML180UH110V60CK, ML180UH135V60DK)
- Lennox Merit ML196UHE / ML196DFE / ML193UHE (single-stage, red LED controls 103217-03 and 107163-01: ML196UH030XE36B, ML196UH045XE36B, ML196UH070XE36B, ML196UH070XE48B, ML196UH090XE36C, ML196UH090XE48C, ML196UH090XE60C, ML196UH110XE60C, ML196UH135XE60D, ML196DF045XE36B, ML196DF070XE48B, ML196DF090XE48C, ML196DF110XE60C, ML193UH030XE36B, ML193UH045XE36B, ML193UH070XE36B, ML193UH090XE36C, ML193UH090XE48C, ML193UH110XE48C, ML193UH110XE60C; also ML180UHE and ML180DFE: ML180UH045E36A, ML180UH045XE36A, ML180UH070E36A, ML180UH070XE36A, ML180UH070E36B, ML180UH070XE36B, ML180UH090E48B, ML180UH090XE48B, ML180UH090E60C, ML180UH110E60C, ML180UH110XE60C, ML180UH135E60D, ML180DF045E36A, ML180DF070E36A, ML180DF070E36B, ML180DF090E48B, ML180DF110E60C; ML180UHV: ML180UH030V36A, ML180UH045V36A, ML180UH070V36A, ML180UH070V36B, ML180UH070V48B, ML180UH090V48B, ML180UH110V60C; Elite EL195UH (2011): EL195UH045P24B, EL195UH045P36B, EL195UH070P36B, EL195UH070P48B, EL195UH090P36C, EL195UH090P48C, EL195UH090P60C, EL195UH110P48C, EL195UH110P60C, EL195UH135P60D)
- Lennox Merit ML296UHVK / ML296DFVK / ML297UHVK (two-stage, variable-speed; upflow/horizontal ML296UH045XV36BK, ML296UH070XV36BK, ML296UH090XV48CK, ML296UH110XV60CK; downflow ML296DF045XV36BK, ML296DF070XV48BK, ML296DF090XV60CK; ML297UH045XV36BK, ML297UH070XV36BK, ML297UH090XV36CK, ML297UH090XV60CK, ML297UH110XV60CK, ML297UH135XV60DK)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage; also Daikin DM96SN, DM92SN, DC96SN: DM96SN0403AN, DM96SN0603BN, DM96SN0803BN, DM96SN0804CN, DM96SN0805CN, DM96SN1005CN, DM96SN1205DN, DM92SN0403AN, DM92SN0603BN, DM92SN0803BN, DM92SN0804CN, DM92SN0805CN, DM92SN1004CN, DM92SN1005CN, DM92SN1205DN, DC96SN0403BN, DC96SN0603BN, DC96SN0804CN, DC96SN1005CN, DC96SN1205DN)
- Payne PG96VTAB (two-stage condensing, variable-speed, non-communicating, 4-way multipoise)
- Payne PG9YAA / PG9YAB (95% single-stage condensing, direct or non-direct vent)
- Carrier 59TP6C (two-stage condensing with InteliSense, Performance series; also 926TC)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMEC96 / GCEC96 (two-stage, multi-speed ECM: GMEC96, GCEC96, Amana AMEC96, ACEC96)
- Goodman / Amana / Daikin GMES92 / GMES96 / GCES96 (single-stage, 92% and 96%: GMES92, GMES96, GCES96, Amana AMES92, AMES96, ACES96, Daikin VMES96, VCES96)
- Goodman / Amana GM9C96 / GC9C96 (two-stage, nine-speed ECM: GM9C96, GC9C96, Amana AM9C96, AC9C96)
- Goodman / Amana GMH8 / GDH8 / GME95 (modified two-stage: 80% GMH8, GDH8, Amana AMH8, ADSH8; 95% GME95, Amana AMEH96)
- Goodman / Amana / Daikin GMS8 / GDS8 (80% single-stage: GMS8, GDS8, Amana AMS8, ADSS8, Daikin VMS8, VDS8)
- Goodman / Amana GMES96 U Ultra-Low NOx (single-stage 96%, U models: GMES96, Amana AMES96)
- Goodman / Amana GM9S96 U Ultra-Low NOx (single-stage 96%, U models: GM9S96, Amana AM9S96; Daikin DM96SN U: DM96SN0403BU, DM96SN0603BU, DM96SN0805CU)
- Goodman / Amana GMVS80 U Ultra-Low NOx (80% single-stage, variable-speed communicating: GMVS80, Amana AMVS80)
- Goodman / Amana GKS9 / AKSS92 (92% single-stage upflow: GKS9, Amana AKSS92)
- Goodman / Amana GMVM97 / GCVM97 ComfortBridge (97% modulating, BA revision and later: GMVM97, GCVM97, Amana AMVM97, ACVM97)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVC96 / GCVC96 BB ComfortBridge (96%, BB revision: GMVC96, GCVC96, Amana AMVC96, ACVC96)
- Goodman / Amana / Daikin AMVC96 / DM96VC / DM80VC ComfortNet (two-character codes: AMVC96, ACVC96, GMVC96, GCVC96 before the BA revision; DM96VC0403BN, DM96VC0603BN, DM96VC0803BN, DM96VC0804CN, DM96VC1005CN, DM96VC1005DN, DM96VC1205DN, DC96VC0403BN, DC96VC0603BN, DC96VC0803BN, DC96VC0804CN, DC96VC1005CN, DC96VC1205DN, DM80VC0603B, DM80VC0604B, DM80VC0805C, DM80VC1005C, DD80VC0603B, DD80VC0805C, DD80VC1005C)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U; also Daikin DM96SC U: DM96SC0603BU, DM96SC0805CU)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96; also Daikin DM97MC/DC97MC: DM97MC0603BNA, DM97MC0803BNA, DM97MC0804CNA, DM97MC1005CNA, DM97MC1205DNA, DC97MC0603BNA, DC97MC0803BNA, DC97MC0804CNA, DC97MC1005CNA)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T / R95T / R92T (90%+ single-stage condensing, constant-torque blower; model numbers (-)951T, (-)95T, (-)(-)95MSX, (-)92T, (-)(-)92MSX, e.g. R95TC0701317MSA, R92TC0701317MSA)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise; also 313AAV, 313JAV)
- Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E)
- York TG9S (95.5% AFUE single-stage PSC, multi-position)
- York TM9T (96% AFUE two-stage PSC, multi-position)
- York TM9X (95.5% AFUE single-stage ECM, multi-position: TM9X040A10MP11, TM9X060B12MP11, TM9X080B12MP11, TM9X080C16MP11, TM9X100C16MP11, TM9X100C20MP11, TM9X120D20MP11)
- York TM9M (97% AFUE modulating PSC, multi-position)
- York YP9C / TP9C / CP9C / LP9C (up to 98% AFUE modulating ECM, multi-position)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58TN0A / 58TN1A (80% two-stage, variable-speed, 4-way multipoise; also 880TA, 881TA)
- Carrier 58TN0B / 58TN1B (80% two-stage, variable-speed, 4-way multipoise)
- Carrier 58TP0A / 58TP1A (80% two-stage, variable-speed ECM, 4-way multipoise; also PG80VTLA)
- Carrier 58TP0B / 58TP1B InteliSense (80% two-stage, variable 25-speed ECM, 4-way multipoise)
- Carrier 59SC5A (single-stage condensing, 4-way multipoise; also 912SB, 912SC, 922SA, 925SA, PG92SAS, PG92SCS, PG95SAS)
- Bryant 925TA (two-stage condensing, 4-way multipoise; also PG95XAT)
- Bryant 926SA (single-stage condensing, multi-speed ECM, multipoise)
- Bryant 926SB (single-stage condensing, 25-speed ECM, InteliSense)
- Carrier 59SC5B / 59SC2D (single-stage 35-in. condensing, 4-way multipoise; also 912SD, 915SB)
- Carrier 59MN7A / 59MN7B (modulating condensing, 4-way multipoise; also 987MA, 987MB)
- Carrier 59MN7C modulating condensing (59MN7C060C17, 59MN7C060C21, 59MN7C080C17, 59MN7C080C21, 59MN7C100C21, 59MN7C120C24; also 987MC)
- Carrier 59TP6B / 59TP6A / 59TN6A two-stage (condensing, two-digit codes; also 926TA, 926TB, 986TB, PG96VAT, PG96VTAA)
- Carrier 59TN6B two-stage condensing (variable-speed: 59TN6B060C17, 59TN6B080C17, 59TN6B080C21, 59TN6B100C21, 59TN6B120C24; also 986TC)
- Carrier 59TN6C two-stage condensing (variable-speed, 35 in. tall: 59TN6C040C14, 59TN6C060C17, 59TN6C080C17, 59TN6C080C21, 59TN6C100C21, 59TN6C120C24)
- Carrier 59TN7A two-stage condensing (variable-speed, 35 in. tall: 59TN7A060C17, 59TN7A080C17, 59TN7A080C21, 59TN7A100C21, 59TN7A120C24)
- Carrier 59SU5A (single-stage Ultra Low NOx condensing, upflow/horizontal, 35 in. tall)
- Carrier 59SU5B single-stage Ultra Low NOx (condensing, 35 in. tall: 59SU5B040M17, 59SU5B060M17, 59SU5B080M21, 59SU5B100M21; also PG95MSUA)
- Carrier 59TP7A two-stage InteliSense (condensing, variable-speed, non-communicating: 59TP7A060V17, 59TP7A080V17, 59TP7A080V21, 59TP7A100V21, 59TP7A120V24)
- Carrier 59SC2E / 59SC6A (single-stage 35-in. condensing, 4-way multipoise; also 912SE, PG96MSAA)
- Carrier 58CU0A (80% communicating, Ultra Low NOx, 4-way multipoise)
- Carrier 58SU0A (80% single-stage, ECM blower, Ultra Low NOx, 4-way multipoise; also 830SA)
- Carrier 58SU0B (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display)
- Carrier 58SB0B / 58SB1B / 58SC0B / 58SC1B (80% single-stage, multi-speed ECM, 4-way multipoise; also PG80MSA, PG80MSLA)
- Bryant 820SA / 821SA (80% single-stage, 4-way multipoise)
- Carrier 58SB0A / 58SB1A / 58SC0A / 58SC1A (single-stage, non-condensing; 58SC is the multi-speed ECM version; also 800SA, 801SA, PG80ESAA, PG80ESLA)