Lennox Merit ML180UH Furnace Codes

Applies to: Lennox Merit ML180UH (80% single-stage). Single LED on the integrated control, counted in flashes.

CodeMeaningWhat to check
OffNo power to the control, or control hardware fault detected. (Off is also shown during normal operation.)Confirm 115 VAC and 24 VAC at the control and the door switch.
1 flashFlame present with gas valve de-energized.Gas valve leaking through or a shorted flame sense circuit. How to fix →
2 flashesPressure switch closed with combustion air inducer de-energized.Stuck or jumpered pressure switch. How to fix →
3 flashesPressure switch open with combustion air inducer energized.Blocked vent or intake, cracked or plugged hose, weak inducer, wet switch. How to fix →
4 flashesPrimary limit switch open.Airflow: filter, blower, closed registers, dirty coil, high temperature rise. How to fix →
5 flashesRollout switch open.Flame rolling out: blocked heat exchanger or flue. Find the cause before resetting. How to fix →
6 flashesPressure switch cycle lockout.Pressure switch opening repeatedly during the cycle. How to fix →
7 flashesLockout, burners fail to light.Gas supply, igniter, gas valve, flame sensor. How to fix →
8 flashesLockout, burners lost flame too many times.Flame sensor, gas pressure, grounding, flame carryover. How to fix →
9 flashesLine voltage polarity incorrect.Hot and neutral reversed, or poor ground. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Lennox ML180UH Installation Instructions, 507323-01 (07/2018), Integrated Control Diagnostic Codes. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.