Carrier 59TP6C two-stage condensing with InteliSense Furnace Codes

Applies to: Carrier 59TP6C two-stage condensing with InteliSense (Performance series). Three-digit display on the control (major.minor, e.g. 13.1), plus the Status Code LED through the blower door.

Older 59TP6A and 59TP6B boards show two-digit flash codes only; use their own service labels.

CodeMeaningWhat to check
10.1L1 polarity fault (LED flashes rapidly).Swap hot and neutral at the furnace; verify ground.
12.1W (heat call) on at power-up.Thermostat and W wiring.
13.1Limit lockout: a switch in the main limit circuit open longer than 3 minutes.Filter, ductwork, blower speed and motor, limit wiring. How to fix →
14.1Ignition lockout after 4 consecutive ignition tries.Gas supply, igniter, flame sensor, ground. How to fix →
14.2Flame lost 3 times after 70 seconds of heating. How to fix →
14.3Lockout: 7 loss-of-flame events during one heat request. How to fix →
14.4Lockout: 7 low pressure switch (LPS) open events during one heat request. How to fix →
15.1Lockout: no blower RPM detected.Blower motor, its power and harness.
19.1InteliSense communications loss.
21.124 V AC sensed on the gas valve when it shouldn't be.Control board; shut the gas off if the valve stays open.
22.1False flame (flame sensed when it shouldn't be).Flame sense circuit shorts; slow-closing gas valve.
23.4Low pressure switch (LPS) stuck closed. How to fix →
23.5High pressure switch (HPS) stuck closed. How to fix →
24.1Fuse fault.Find the short in the 24 V wiring before replacing the 3 A fuse. How to fix →
25.1No program in the control. No heating operation.Reprogram with the program number on the rating plate; replace the control if it persists.
25.2Corrupted program file. No heating operation.Reprogram with the service app or a super plug.
25.3Twinned units not identical (program numbers don't match). Main unit will not heat.Twinned furnaces must be the same model and program.
25.4Main program invalid; running on the backup program. Still operates normally.Reprogram the control.
25.5Installer settings corrupted; running on default settings.Re-enter installer settings or reprogram.
25.6Wrong program for this control. No heating operation.Reprogram so the program matches the control.
27.1–27.3Program in the super plug missing, not recognized or corrupted.Remove the super plug and retry, then try another super plug; replace the control if it still fails.
31.6Open secondary (high) pressure switch (HPS). How to fix →
31.7HPS failed to close within 75 seconds going from low to high heat. High heat locked out for the next cycle. How to fix →
32.2Open main (low) pressure switch (LPS). How to fix →
33.1A switch opened in the main limit circuit. How to fix →
33.2Lockout of high heat for the current cycle. How to fix →
34.1Ignition fault during four consecutive ignition trials. How to fix →
34.5Low heat flame lost before the blower on-delay. How to fix →
34.6Low heat flame lost after the blower on-delay. How to fix →
34.7High heat flame lost before the blower on-delay. How to fix →
34.8High heat flame lost after the blower on-delay. How to fix →
41.1No blower RPM at start-up.Blower motor, its power and harness.
41.2No RPM while the blower motor should be running.Blower motor, its power and harness.
43.1High pressure switch closed before the low pressure switch. How to fix →
45.1Internal control error.Cycle power; if 45 repeats, replace the control.
45.2Gas valve relay (GVR) not closing.Cycle power; if 45 repeats, replace the control.
45.3Micro EEPROM error.Cycle power; if 45 repeats, replace the control.
45.4Micro loss of communication.Cycle power; if 45 repeats, replace the control.
46.1Momentary loss of power.
52.1Supply air temperature sensor (SAT) open.
52.2Supply air temperature sensor (SAT) shorted.
53.1Return air temperature sensor (RAT) open.
53.2Return air temperature sensor (RAT) shorted.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 59TP6C Installation, Start-up, Operating and Service Instructions (59TP6C-03SI), Fig. 60 Service Label status code table and Table 21. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.