Carrier 58SB0B / 58SB1B / 58SC0B / 58SC1B Furnace Codes

Applies to: Carrier 58SB0B / 58SB1B / 58SC0B / 58SC1B (80% single-stage, multi-speed ECM, 4-way multipoise; also PG80MSA, PG80MSLA). Three-digit display on the furnace control (major.minor code); the LED seen through the door sight glass flashes the major code.

The 58SC0B/58SC1B instructions (58SC0B-01SI, Fig. 45 p. 30) print the same service label (348061-201 Rev. A) and the same troubleshooting guide, so both are covered here. The older 58SB0A / 58SB1A / 58SC0A / 58SC1A use two-digit codes and have their own chart. Payne's PG80MSA/PG80MSLA instructions (IM-PG80MSAA-02, Fig. 45 p. 30) print the same service label, part number 348061-201 Rev. A.

CodeMeaningWhat to check
10.1L1 polarity fault (rapid flash LED): 115 V polarity is reversed.Correct the 115 V wiring polarity at each junction. If units are twinned, check low-voltage (24 V) transformer phasing.
12.1W on at power up (normal operation).The blower runs for 90 seconds if power comes on during a call for heat (R-W closed), or when R-W opens during the blower on-delay.
13.1Limit lockout: a switch in the main limit circuit was open longer than 3 minutes.The limit, draft safeguard, flame rollout or blocked vent switch (if used) was open more than 3 minutes. The control auto-resets after 3 hours. See 33.1. How to fix →
14.1Ignition lockout after 4 consecutive ignition tries.Auto-resets after 3 hours. Check manifold pressure and firing rate, inlet gas pressure fluctuations, then see code 34. How to fix →
14.2Flame lost 3 times after 70 seconds of heating.Auto-resets after 3 hours. Check manifold pressure and firing rate, inlet gas pressure fluctuations, then see 34.3. How to fix →
14.3Lockout: 7 loss-of-flame events during one heat request.Check manifold pressure and firing rate, inlet gas pressure fluctuations, then see 34.2 and 34.3. How to fix →
21.1Gas heating lockout: 24 VAC sensed on the gas valve when it shouldn't be.Turn off power and wait 5 minutes to retry. Check for a stuck-closed gas valve relay on the control, or a miswire or short on the gas valve wire.
22.1False flame: flame is proved while the gas valve is de-energized.The inducer runs until the fault clears. Check for a stuck-open or leaky gas valve.
23.1Main pressure switch stuck closed.Check for an obstructed pressure tube or a pressure switch stuck closed. How to fix →
24.1Fuse fault.Look for a short circuit in the 24 V wiring, including thermostat leads. Disconnect the thermostat leads to isolate the short. How to fix →
25.1No program information in the control; no heating operation.Reprogram the control with the correct program number from the rating plate. Replace the control if the issue remains.
25.2Corrupted program file; no heating operation.Reprogram the control using the service app or a super plug (supplied separately). Replace the control if the issue remains.
25.3Twinned units are not identical: program numbers don't match.Twinned furnaces must be identical (same program number). The main unit will not operate heating until they match.
25.4Main program invalid; using the backup program.The control still operates normally. Reprogram the control to correct the issue.
25.5Installer settings corrupted.The control runs on default installer settings. Try reselecting the installer settings, or reprogram the control.
25.6Wrong program for this control; no heating operation.Reprogram the control so the program matches the control used. Replace the control if the issue remains.
27.1Program in the super plug is missing, not recognized or corrupted.Remove the super plug and retry. If 27 still shows, try a different super plug. If it still fails, replace the control.
27.2Program in the super plug is missing, not recognized or corrupted.Remove the super plug and retry. If 27 still shows, try a different super plug. If it still fails, replace the control.
27.3Program in the super plug is missing, not recognized or corrupted.Remove the super plug and retry. If 27 still shows, try a different super plug. If it still fails, replace the control.
31.1Main pressure switch open.If it is open longer than 5 minutes, the inducer shuts off for 15 minutes before retrying; if it opens during the blower on-delay, the blower runs for the selected off-delay. Check vent sizing, low inducer voltage (115 V), low inlet gas pressure (if an LGPS is used), combustion air supply, disconnected or obstructed pressure tubing, inducer motor, pressure switch, excessive wind and a restricted vent. How to fix →
33.1A switch in the main limit circuit has opened.The limit, draft safeguard, flame rollout or blocked vent shutoff switch (if used; part of the chimney adapter kit) is open. The blower runs 4 minutes or until the switch closes, whichever is longer. Open more than 3 minutes changes to lockout 13.1. The flame rollout switch and blocked vent shutoff switch need a manual reset. Check for a dirty filter or restricted ducts, a loose blower wheel, the switch or its connections, the blower motor or capacitor, combustion air (rollout open), a restricted vent, vent sizing and excessive wind. How to fix →
34.1Ignition proving failure: no flame sensed during four consecutive ignition trials.The gas valve is de-energized and the control tries four times before 14.1. Check inlet gas pressure, control ground continuity and the manual shut-off valve. The green/yellow wire must be connected to the furnace burner box screw, and the flame sensor must not be grounded or touching the casing. Carrier's guide: run the component test with the R lead removed to check the igniter (115 V between pin 1 and NEUTRAL-L2 for the 15 seconds), then check for 24 V at the gas valve on a call for heat. Flame current below 0.5 DC microamps: clean the sensor with fine steel wool (4.0-6.0 microamps nominal). How to fix →
34.2Flame lost after successful ignition, before the heating blower on-delay ended.Same checks as 34.1. Also check for inadequate flame carryover or rough ignition, low inlet gas pressure, firing rate, and a blocked or incorrect carry-over gap (.045 in. nominal). How to fix →
34.3Flame lost after successful ignition, after the heating blower on-delay.Same checks as 34.1. If flame current is near 4.0-6.0 microamps and the burners won't stay on, check connections and retry, then replace the control. How to fix →
45.1Control failure: flame circuit fault, memory mismatch or sequence error.Cycle power. If code 45 repeats, replace the control.
45.2Control failure: gas valve relay will not close.Cycle power. If code 45 repeats, replace the control.
45.3Control failure: EEPROM memory issue.Cycle power. If code 45 repeats, replace the control.
46.1Momentary loss of power.Heating stops and restarts once the power fluctuation is resolved.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 58SB0B/58SB1B Installation, Start-Up, Operating and Service and Maintenance Instructions 58SB0B-01SI, Fig. 45 Service Label (348061-201 Rev. A) p. 31 and Fig. 51 Troubleshooting Guide pp. 42-44 (read at 400 and 230 dpi). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.