Goodman / Amana GR9S80-U / GR9S96-U Ultra-Low NOx Furnace Codes

Applies to: Goodman / Amana GR9S80-U / GR9S96-U Ultra-Low NOx (R-32 era single-stage; also AR9S80-U, AR9S96-U, DR80SN-U, DR96SN-U: DR80SN0403AU, DR80SN0603AU, DR80SN0604BU, DR80SN0804BU, DR80SN0805CU, DR96SN0403BU, DR96SN0603BU, DR96SN0805CU). Three-character seven-segment display on the integrated control.

Covers the Ultra-Low NOx Goodman GR9S80 and GR9S96 and Amana AR9S80 and AR9S96 U models (RS6621302 Rev. 2, pp. 30-34, and RS6612302 Rev. 2, pp. 33-37). Daikin's DR80SN*U (RSD6621302 Rev. 2, pp. 30-34) and DR96SN*U (RSD6612302 Rev. 2, pp. 32-36) service instructions list the same codes and fault descriptions. The standard (non-U) models have their own chart, as does the older R-410A GM9S96 U.

CodeMeaningWhat to check
IdLIdle: normal operation.
nonENo display: no 120 VAC to the furnace or no 24 V to the integrated control.Breaker, manual disconnect and door switch; 120 VAC on the transformer primary and 24 V on the secondary; 24 V wires to the 12-pin harness. Replace the control only after the wiring checks out.
EbLCirculator blower motor drawing very little current after the heat-on delay (hard lockout).Loose blower motor connections; the motor's 120 V L1 wire must be on the CIRC-H terminal of the control; blower voltage, amps and speed setting; replace the motor if needed.
EbUCirculator blower motor drawing too much current during inducer pre-purge (hard lockout).Blower motor power wiring reversed on the control; loose or miswired connections.
Ed0No shared data.Populate the shared data set with the BTPIM01 plug-in module.
Ed8Invalid call: check the ODS setting.Set ODS and TON airflow to match the outdoor unit, with the system set to IdL first.
EE0Lockout after too many ignition retries (3 total): failure to establish flame, or loss of flame after it was established.Gas supply and pressure; front cover pressure switch and drainage; igniter and its alignment; restricted orifices; flame sensor (clean with steel wool); flue blockage, length and elbows; combustion air; inducer performance. How to fix →
EE1Pressure switch circuit closed at the start of the heating cycle.Sticking switch contacts or a short in the switch wiring. How to fix →
EE2Pressure switch circuit open; the inducer runs with no further operation.Pressure switch hose blocked, pinched or misconnected; blocked flue or inlet pipe; blocked drain system; weak inducer; wrong switch set point or bad contacts; loose wiring. How to fix →
EE3Primary limit circuit open; the circulator blower runs with no furnace operation.Blocked filters or restrictive ductwork; blower speed and motor; loose wiring in the limit circuit. Check the temperature rise against the specification sheet. How to fix →
EE4Flame sensed with no call for heat; inducer and circulator run continuously.Short to ground in the flame sense circuit, a lingering burner flame, or a slow-closing gas valve. How to fix →
EE5Open fuse.Replace the fuse (3-amp automotive type) and find the short in the low-voltage wiring, or the back of the control touching the mounting panel because standoffs are missing. How to fix →
EE6Low flame sense microamp signal (furnace still runs).Clean a coated or oxidized flame sensor with steel wool; check its position in the flame; check the inlet air piping for blockage, length, elbows and termination; compare gas pressure with the rating plate. How to fix →
EE7Problem with the igniter circuit.Wiring from the control to the igniter; a shorted igniter; the furnace ground; the igniter output from the control (igniter relay fault). How to fix →
E10Grounding fault.Poor neutral connection: verify the neutral wire to the furnace and continuity to the ground source.
E11Open burner box limit switch circuit.Gas pressure too high, misaligned burners, or a restricted heat exchanger or vent. How to fix →
E12Redundant relay open alarm.Replace the integrated control; don't replace other parts based on this code.
E13Redundant relay stuck closed alarm.Replace the integrated control. If E13 stays after the new control, replace the system wire harness.
EbFInducer communication alarm.Loose wiring between the control and the inducer: check the red, black and white harness and its connections at both ends.
E1bAnalog pressure sensor reference error: the 5 VDC reference is out of range (5.0 ±0.2 VDC for 5 seconds).Red, black and white harness and connections to the inducer and control; replace the pressure sensor. How to fix →
E1CAnalog pressure sensor null error: sensor voltage out of range with the inducer off.Red, black and white harness and connections; pressure hoses to the pressure sensor and pressure switch. How to fix →
E1dAnalog pressure sensor span error: sensor out of range when the pressure switch is closed, or the switch opens and closes outside the expected sensor range.Harness and connections; pressure hoses to the sensor and switch; replace the pressure switch if the error continues. How to fix →
E1EAnalog pressure sensor pressure error: inducer RPM has reached its limit, or a blocked flue pipe.Harness and connections; flue piping for blockage, length, elbows and termination; replace the pressure sensor if necessary. How to fix →
E1FAnalog pressure sensor input error: wrong pressure sensor installed.Harness and connections; replace the pressure sensor with the correct part. How to fix →
EEA120 VAC polarity reversed.Correct the polarity per the wiring diagram and verify the furnace ground.
EEbThe control is not energizing the gas valve when it should.Check the gas valve circuit wiring; if it is good, replace the integrated control. Goodman says not to replace the gas valve for this code.
EECGas valve energized when it should be off.Cycle 120 VAC. If EEC stays, it is a wiring problem outside the control: inspect the system wiring and replace the system harness; if EEC still stays, replace the control.
EEdAuxiliary limit switch open (blower compartment).120 V power shut off during a heat cycle; not enough air over the heat exchanger (blocked filters, restrictive ducts, blower speed or failed blower motor); loose wiring in the limit circuit. How to fix →
EEEThe control has detected an internal fault.Power off for at least 3 minutes and back on; inspect the 120 V and 24 V wiring and the ground. Replace the control; don't replace other parts based on this code.
EEHTwinning error.Both furnaces must be on the same 120 VAC from the breaker panel. Disconnect the twinning wire and power both: a control that still shows EEH alone is the one to replace. Reconnect, check the twinning wire, then give G to the main furnace and confirm the twinned blower follows at the same speed.
EAFLost communication with the R-32 sensor; the furnace is in mitigation mode (fan only).The furnace may not be paired with an R-32 cooling unit: see the manual's R-32 information section. Otherwise check the sensor wire and connection, and replace the sensor if needed.
EALThe R-32 sensor has detected a refrigerant leak; mitigation mode (fan only).Look for a leak at the indoor coil. Heating resumes once no leak is detected and the 5-minute delay is over.
EASThe R-32 sensor has detected a fault; mitigation mode (fan only).Check the R-32 sensor and replace it if necessary.
EArThe control has detected a problem with its internal A2L relay and is running mitigation mode.Disconnect any wire on the control's ALARM terminal and cycle power. If the code clears, repair the ALARM wiring; if not, replace the control.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman Service and Troubleshooting, 96% Single Stage Ultra-Low NOx Gas Furnaces GR9S96-U / AR9S96-U, RS6612302 Rev. 2, Troubleshooting pp. 33-37 (read from page images). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.