Home / Charts / Lennox furnace codes

Lennox EL296UHV / SL280UHV control 103130 Furnace Codes

Applies to: Lennox EL296UHV / SL280UHV control 103130 (Elite EL296UHV(X), EL296DFV(X) and SL280UHV/SL280UHNV/SL280DFV, earlier units: EL296UH045V36B, EL296UH045XV36B, EL296UH070V36B, EL296UH070XV36B, EL296UH090V36C, EL296UH090XV36C, EL296UH090XV48C, EL296UH090V60C, EL296UH090XV60C, EL296UH110V48C, EL296UH110XV48C, EL296UH110V60C, EL296UH110XV60C, EL296UH135V60D, EL296UH135XV60D, EL296DF045XV36B, EL296DF070V48B, EL296DF070XV48B, EL296DF090V60C, EL296DF090XV60C, EL296DF110V60C, EL296DF110XV60C, SL280UH070V36A, SL280UH070XV36A, SL280UH090V36B, SL280UH090V48B, SL280UH090XV48B, SL280UH090V60C, SL280UH090XV60C, SL280UH110V60C, SL280UH110XV60C, SL280UH135V60D, SL280DF070V36A, SL280DF090V48B, SL280DF090V60C, SL280DF110V60C, SL280UH060NV36A, SL280UH080NV48B, SL280UH080NV60C, SL280UH100NV60C). Seven-segment diagnostic LED and push button on the SureLight ignition control 103130 (two-stage, variable-speed, communicating).

Lennox's service literature for the EL296UHV(X) and EL296DFV(X) (1125, 1126) and the SL280UHV/SL280UHNV and SL280DFV (1116, 1117) lists two controls with the same tables. The SL280UHNV service literature (1601, revised 04/2024, Table 5 pp. 16-21) prints this same 103130 code list without naming the control. This chart is the older 103130; later units have the 107045, which drops the LSOM compressor codes (E400-E409) and a few others; see that chart. The model number doesn't tell you which control is fitted: check the part number on the control's label.

CodeMeaningWhat to check
E105Device communication problem: no other devices on the RSBus.Usually electrical noise. Keep high voltage separated from the RSBus wiring; check for miswired or loose connections between the thermostat, indoor and outdoor units; look for a high voltage noise source near the system. Clears when communication returns. How to fix →
E110Low line voltage (below the nameplate rating).Check and correct line voltage. Clears 5 seconds after recovery.
E111Listed as low line voltage; Lennox's action is to reverse the line power wiring (polarity).Reverse the line power wiring. Resumes 5 seconds after recovery.
E112Ground not detected; system shuts down.Provide a proper earth ground. Resumes 5 seconds after recovery.
E113High line voltage (above the nameplate rating).Provide voltage within range. Resumes 5 seconds after recovery.
E114Line voltage frequency out of range.No 60 Hz power: check voltage and line frequency. Resumes 5 seconds after recovery.
E115Low 24 V (the control restarts if it recovers).24 V range is 18 to 30 V. Check and correct; look for power-robbing equipment on the system; a larger VA transformer may be needed. Clears after recovery.
E116High 24 V.24 V range is 18 to 30 V. Check and correct; check for proper line voltage (120 V, 240 V, etc.) to the equipment. Clears when the control senses proper voltage.
E117Poor ground detected (warning only).Provide proper grounding for the unit. Clears 30 seconds after recovery.
E120Unresponsive device (communicating only).Usually the outdoor unit is slow to answer the indoor unit's polling. Cycle power and check all wiring connections. Clears when the device responds. How to fix →
E124Communicating thermostat signal missing for more than 3 minutes.Check the four wiring connections and ohm the wires; cycle power at the thermostat. All services stop until the thermostat's heartbeat message returns. How to fix →
E125Control failed self-check or hardware (flame sense circuit faults, pin shorts, etc.); control not communicating.Cycle power. Replace the control if the problem persists and prevents service. Critical alert; clears 300 seconds after recovery.
E126Control internal communication problem.Hardware problem on the control. Cycle power; replace the control if the problem prevents service and persists. Clears 300 seconds after recovery.
E131Corrupted control parameters (communicating only).Reconfigure the system: exit commissioning and run Set Factory Default. Replace the control if heating or cooling isn't available. The control still runs on default settings.
E180Outdoor air temperature sensor failure (shown only if shorted or out of range).Compare sensor resistance with the temperature/resistance chart in the installation instructions; replace the sensor pack if needed. If no sensor should be installed, redo configuration and make sure it shows not installed on the indoor unit About screen. Clears 30 seconds after recovery.
E200Hard lockout: rollout circuit open or previously open.Correct the cause of the rollout trip, or replace the rollout switch. Test operation. Clears after recovery. How to fix →
E201Indoor blower communication failure: can't communicate with the blower motor.Includes power outage. Possible causes: motor not powered, loose wiring. The problem can be on the control or the motor side. Clears after recovery. How to fix →
E202Indoor blower motor mismatch: motor horsepower doesn't match unit capacity.Wrong unit size code selected. Check the Unit Size Codes on the configuration guide or in the instructions. Clears after the correct match is detected following a reset (remove the thermostat while applying power and reprogramming).
E203Unit size code not programmed (invalid code).No unit size code selected. Program it from the Unit Size Codes on the configuration guide or in the instructions. Critical alert; clears after a valid code is read following a reset.
E204Gas valve miswired.Check gas valve operation and wiring. Clears when repaired.
E205Gas valve control relay contact shorted.Check wiring on the control and gas valve. If the wiring is correct, replace the control.
E206Gas valve second-stage relay failure.The furnace runs on first stage for the rest of the heat call. If it still can't run second stage, replace the control.
E207Hot surface igniter sensed open.Measure igniter resistance; replace if open or outside the range in the installation instructions. How to fix →
E223Low pressure switch failed open.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix →
E224Low pressure switch failed closed.Check whether the low pressure switch is stuck closed on the heat call for longer than 150 seconds. Measure operating pressure; inspect the vent and inducer. How to fix →
E225High pressure switch failed open.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix →
E226High pressure switch failed closed.Check the high pressure switch closing on the heat call, measure operating pressure, inspect the vent and inducer. How to fix →
E227Low pressure switch open during trial for ignition or run mode.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix →
E228Combustion air inducer calibration failure.The control couldn't calibrate the pressure switch. Check the vent system and pressure switch wiring. How to fix →
E229Ignition on high fire.The control switched to high-fire ignition because the low-fire pressure switch didn't close in time. No action needed.
E240Low flame current, run mode.Check flame microamps with the control diagnostics (see the flame table above); clean or replace the sensor; measure neutral to ground for a good unit ground. Clears after the heat call completes. How to fix →
E241Flame sensed out of sequence; flame still present.Shut off the gas. Check the gas valve for a leak and replace it if needed. Clears when the fault recovers.
E250Limit switch circuit open.Check firing rate, blockage in the heater and airflow. If the limit doesn't close within 3 minutes, the unit goes into a 1-hour soft lockout. How to fix →
E252Discharge air temperature too high (gas heat only).Check temperature rise, airflow and input rate. Clears when the heat call ends. How to fix →
E270Soft lockout: too many retries, no flame current sensed.Check gas flow, that the igniter lights the burner, and flame sensor current. Clears when a heat call finishes successfully. How to fix →
E271Soft lockout: too many retries; last retry failed when the pressure switch opened.Check pressure (inches w.c.) of the switch closing on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. Resumes after the fault clears. How to fix →
E272Soft lockout: too many recycles; last recycle due to the pressure switch opening.Check whether the low pressure switch is stuck closed, check the high pressure switch closing, measure operating pressure, inspect the vent and inducer. How to fix →
E273Soft lockout: too many recycles; last recycle due to flame failure.Check flame microamps, clean or replace the sensor, measure neutral to ground for a good unit ground. How to fix →
E274Soft lockout: too many recycles; last recycle failed on the limit circuit, or the limit stayed open over 3 minutes.1-hour soft lockout. Check firing rate and airflow; check for blockage. How to fix →
E275Soft lockout: flame sensed out of sequence; flame signal now gone.Shut off the gas and check the gas valve for a leak. 1-hour soft lockout; clears when flame is proven stable.
E276Watchguard calibration failure.The control couldn't calibrate the pressure switch. Check the vent system and pressure switch wiring. 1-hour soft lockout; clears when calibration finishes. How to fix →
E290Igniter circuit fault: failed igniter or triggering circuitry.Measure hot surface igniter resistance; replace if open or out of spec. 1-hour soft lockout. How to fix →
E291Heat airflow restricted below the minimum.Check for a dirty filter and airflow restriction; check blower performance. 1-hour soft lockout; clears when a heat call finishes successfully. How to fix →
E292Indoor blower motor can't start (obstructed wheel, seized bearings).Replace the motor or wheel if the assembly doesn't run or meet performance. 1-hour soft lockout; clears after the blower starts.
E294Combustion air inducer over current.Check inducer bearings, wiring and amps; replace it if it doesn't run or meet performance. Clears when inducer current is in range after the next ignition following the soft lockout or a reset. How to fix →
E295Indoor blower motor temperature too high (tripped on its internal protector).Check motor bearings and amps; replace if needed. Clears after the blower demand is satisfied.
E310Discharge air temperature sensor failure (shown only if shorted or out of range).Compare sensor resistance with the chart in the installation instructions; replace if needed. Clears 30 seconds after recovery (communicating) or after the heat call (non-communicating).
E311Heat rate reduced to match indoor blower airflow (warning only).The blower is in cutback for restricted airflow and the firing rate drops every 60 seconds to match; 2-stage controls drop to first stage. Check the filter and duct system. How to fix →
E312Restricted airflow in cooling or continuous fan: below the cfm setting (warning only).The blower is in cutback to protect the motor outside its design range (0 to 0.8 in. w.c. total external static). Check the filter and duct system. Clears after the current call is satisfied. How to fix →
E313Indoor and outdoor unit capacity mismatch (communicating only).Wrong indoor/outdoor capacity code. Check configuration. Warning only: the system runs but may not meet efficiency and capacity. Clears when commissioning is complete.
E331Global network connection: communication link problem.Lennox lists this as for future use.
E334Relay Y1 stuck on the integrated control.Replace the integrated control. (The installation instructions list this as E344.)
E347No 24 V output on Y1 with a non-communicating outdoor unit.Operation stopped: the Y1 relay or stage 1 failed (pilot relay contacts didn't close or the coil didn't energize). Critical alert; clears after reset when Y1 input is sensed.
E348No 24 V output on Y2 with a non-communicating outdoor unit.The Y2 relay or stage 2 failed (pilot relay contacts didn't close or the coil didn't energize). Critical alert; clears after reset (Lennox's text says when Y1 input is sensed).
E349No 24 V between R and O with a non-communicating outdoor unit (dual fuel module needed for a heat pump).The R to O configuration link must be restored: replace the link or hard-wire it. Non-communicating mode only. Critical alert.
E370Interlock switch (DS terminal) sensed open for 2 minutes.The control saw 24 VAC missing for 2 minutes and stops all services until the interlock closes. Clears when 24 VAC is present on DS for at least 10 seconds, or on a power reset.
E400LSOM: compressor internal overload tripped.Y1 demand is present but the compressor isn't running. Check power to the outdoor unit. Clears after current is sensed in both RUN and START sensors for at least 2 seconds, after service is removed, or on a power reset.
E401LSOM: compressor long run cycle or low system pressure.The compressor ran more than 18 hours on one thermostat demand; also monitors low pressure switch trips. Critical alert. Clears after 30 consecutive normal run cycles or a power reset.
E402LSOM: outdoor unit system pressure trip.Discharge or suction pressure out of limits, or compressor overloaded. Clears after 4 consecutive normal compressor run cycles.
E403LSOM: compressor short-cycling (running less than 4 minutes); outdoor unit pressure trip.The compressor runs less than 3 minutes to satisfy a demand. Clears after 4 consecutive normal run cycles or a power reset.
E404LSOM: compressor rotor locked; short-cycling (running less than 4 minutes).Locked rotor from a shorted run capacitor, seized bearings, excessive liquid refrigerant, etc. Clears after 4 consecutive normal run cycles or a power reset.
E405LSOM: compressor open circuit.Compressor circuit open (power disconnected, open fuse, etc.). Clears after 1 normal compressor run cycle.
E406LSOM: compressor open start circuit.Not enough current through the START current transformer. Clears after current is sensed in the START sensor, or a power reset.
E407LSOM: compressor open run circuit.Not enough current through the RUN current transformer. Clears after current is sensed in the RUN sensor, 1 normal run cycle, or a power reset.
E408LSOM: compressor contactor welded.The compressor runs continuously. Clears after 1 normal compressor run cycle or a power reset.
E409LSOM: compressor low voltage.Secondary voltage is below 18 VAC; after 10 minutes operation stops. Clears when voltage is above 20 VAC for 2 seconds, or on a power reset.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Lennox EL296UHV(X) Unit Information, Service Literature 1125 (revised 08/2022), Ignition Control 103130 Diagnostic Modes and Codes (Tables 4-5) pp. 32-38, flame signal table; same table in EL296DFV(X) Service Literature 1126 pp. 14-20. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.

Related

Other brands