Lennox Signature SLP99DFV Furnace Codes

Applies to: Lennox Signature SLP99DFV (Dave Lennox Signature downflow, variable capacity, variable speed, communicating: SLP99DF070XV36B, SLP99DF090XV36C, SLP99DF090XV48C, SLP99DF090XV60C, SLP99DF110XV60C). Seven-segment diagnostic LED and push button on the variable capacity integrated control.

CodeMeaningWhat to check
E105Device communication problem: no other devices on the bus.Check for miswiring and loose connections, and for a high voltage noise source near the system (a welder, etc.). How to fix →
E110Low line voltage (below the nameplate rating).Check line voltage.
E113High line voltage (above the nameplate rating).Check line voltage.
E114Line voltage frequency out of range.No 60 Hz power: check voltage and frequency.
E115Low 24 V (the control restarts if it recovers).24 V range is 18 to 30 V. Check voltage.
E120Unresponsive device.Usually the outdoor unit is slow to answer the indoor unit's polling. Cycle power and check wiring. How to fix →
E124Communicating thermostat signal missing for more than 3 minutes.Check connections and cycle power at the thermostat. How to fix →
E125Control failed self-check or hardware (flame sense circuit faults, pin shorts, etc.); control not communicating.Cycle power on the control. Replace it if the problem prevents service and persists.
E126Failed internal communication between the control's microcontrollers.Cycle power on the control. Replace it if the problem prevents service and persists.
E180Outdoor air sensor failure (no error if disconnected; shown only if shorted or out of range).Lennox gives no action in this table. Check the sensor and its wiring.
E200Hard lockout: rollout circuit open or previously open.Correct the cause of the rollout trip or replace the rollout switch, then test furnace operation. How to fix →
E201Indoor blower communication failure: can't communicate with the blower motor.Includes power outage. Check power and wiring to the motor. How to fix →
E202Indoor blower motor mismatch: motor horsepower doesn't match unit capacity.Wrong furnace size code selected. Check the unit size codes on the configuration guide or in the installation instructions.
E203Furnace size not programmed (invalid unit code).No furnace size code selected. Check the unit size codes on the configuration guide or in the installation instructions.
E204Gas valve miswired.Check operation of the gas valve.
E205Gas valve control relay contact shorted.Check operation of the gas valve.
E207Hot surface igniter sensed open.Measure igniter resistance; replace if open or out of spec. How to fix →
E223Low pressure switch failed open.Check the switch's closing pressure (inches w.c.) on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E224Low pressure switch failed closed.Check the low pressure switch for closed contacts, measure operating pressure, inspect the vent and inducer. How to fix →
E225High pressure switch failed open.Check the switch's closing pressure (inches w.c.) on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E226High pressure switch failed closed.Check the high pressure switch for closed contacts, measure operating pressure, inspect the vent and inducer. How to fix →
E227Low pressure switch open during trial for ignition or run mode.Check the switch's closing pressure (inches w.c.) on the heat call, measure operating pressure, and inspect the vent and combustion air inducer for correct operation and restriction. How to fix →
E228Pressure switch calibration failed.Retries after 300 seconds; the error counter clears when it leaves lockout. Check the vent system and pressure switch wiring. How to fix →
E240Low flame current, run mode.Check flame microamps (Table 18 above), clean or replace the sensor, and measure neutral to ground for a good unit ground. How to fix →
E241Flame sensed out of sequence; flame still present.Shut off the gas and check the gas valve for a leak.
E250Limit switch circuit open.Find why the limit trips: overfiring or low airflow. How to fix →
E252Discharge air temperature too high (gas heat only).Check temperature rise, airflow and input rate. How to fix →
E270Soft lockout: too many retries, no flame current sensed.Check gas flow, that the igniter lights the burner, and flame sensor current. How to fix →
E271Soft lockout: too many retries; last retry failed when the pressure switch opened.Same as E223. How to fix →
E272Soft lockout: too many recycles; last recycle due to the pressure switch opening.Same as E223 and E225. How to fix →
E273Soft lockout: too many recycles; last recycle due to flame failure.Same as E240. How to fix →
E274Soft lockout: too many recycles; last recycle failed on the limit, or the limit stayed open over 3 minutes.Same as E250. How to fix →
E275Soft lockout: flame sensed out of sequence (code 241); flame signal now gone.Same as E241.
E276Soft lockout: too many calibration retries.Same as E228. How to fix →
E290Igniter circuit fault: failed igniter or triggering circuitry.Same as E207. How to fix →
E291Restricted airflow: cfm below what minimum firing rate needs.Check for a dirty filter, airflow restriction and blower performance. How to fix →
E292Indoor blower motor can't start (seized bearings, stuck wheel, etc.).Replace the motor or wheel if the assembly doesn't run or meet performance.
E294Combustion air inducer amp draw too high.Check inducer bearings, wiring and amps; replace if it doesn't run or meet performance. How to fix →
E295Indoor blower motor temperature too high (tripped on its internal protector).Check motor bearings and amps; replace if needed.
E310Discharge air sensor failure (no error if disconnected; shown only if shorted or out of range).Discharge air temperature sensor reading out of range; the code is activated during Field Test mode.
E311Heat rate reduced to match indoor blower airflow.The blower is in cutback for restricted airflow. Replace the filter if needed or repair/add ductwork. How to fix →
E312Restricted airflow in cooling or continuous fan: below the cfm setting.The blower is in cutback to protect the motor outside its design range (0 to 0.8 in. w.c. total external static). Check the filter and ductwork. How to fix →
E313Indoor and outdoor unit capacity mismatch.Wrong capacity code. Check configuration. Warning only; clears when commissioning is exited.
E331Global network connection: communication link problem.Lennox lists this as for future use.
E347No 24 V output on Y1 to C with a non-communicating outdoor unit.The Y1 relay or stage 1 failed (pilot relay contacts didn't close or the coil didn't energize).
E348No 24 V output on Y2 to C with a non-communicating outdoor unit.The Y2 relay or stage 2 failed (pilot relay contacts didn't close or the coil didn't energize).
E349No 24 V between R and O with a non-communicating outdoor unit (dual fuel module needed for a heat pump).Non-communicating mode only. The R to O link on the furnace control has been cut, which can cause a brown out and a low voltage alert. Restore the link by hard-wiring R to O on the terminal strip.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Lennox SLP99DFV Unit Information, Service Literature 100002 (04/2024), unit size codes p. 19, Table 14 LED status and diagnostic codes pp. 20-23, Table 18 flame signal p. 29. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.