Home / Charts / ICP (Heil, Tempstar, Comfortmaker, Arcoaire) furnace codes

ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N95ESN / R92ESN Furnace Codes

Applies to: ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N95ESN / R92ESN (single-stage 35-in. condensing, 4-way multipoise; also PG95ESA). LED on the furnace control, two-digit status codes.

International Comfort Products builds furnaces sold under several brand names, including Heil, Tempstar, Comfortmaker and Arcoaire. The N95ESN service label prints the same codes and checks as the Carrier 59SC5B label, and so does the R92ESN label (R92ESN-04SI, Fig. 68 p. 64). Payne's PG95ESA manual (IM-PG95ESAA-05, Fig. 67 p. 68) prints the same service label text.

CodeMeaningWhat to check
11No previous code.Stored codes are erased automatically after 72 hours.
12Blower on after power up (115 VAC or 24 VAC).Blower runs 90 seconds if power comes on during a call for heat (R-W closed) or R-W opens during the blower on-delay.
13Limit circuit lockout: a limit or flame rollout switch open longer than 3 minutes.Auto-resets after three hours. See 33. How to fix →
14Ignition lockout.Auto-resets after three hours. See 34. How to fix →
21Gas heating lockout (does NOT auto reset).Miswired gas valve, or a defective control (valve relay).
22Abnormal flame-proving signal: flame proved while the gas valve is off; inducer runs until it clears.Leaky or stuck-open gas valve.
23Pressure switch did not open.Obstructed pressure tubing, or pressure switch stuck closed. How to fix →
24Secondary voltage fuse is open.Short circuit in the 24 VAC wiring. How to fix →
31HPS pressure switch did not close or reopened.If the HPS stays open one minute after the gas valve closes (after three successive trials), the control locks out for 3 hours. Excessive wind, restricted vent or wrong vent sizing, defective inducer or low inducer voltage (115 VAC), low inlet gas pressure (if LGPS used), defective pressure switch, inadequate combustion air, disconnected or obstructed pressure tubing, restricted or blocked condensate drainage. How to fix →
32LPS pressure switch did not close or reopened.If the LPS is open longer than five minutes, the inducer shuts off for 15 minutes before retrying. See 31. How to fix →
33Limit circuit fault: a limit or flame rollout switch is open.Blower runs 4 minutes or until the switch remakes; over 3 minutes it becomes 13. The flame rollout switch needs a manual reset. Dirty filter or restricted ducts, vent sizing or restriction, loose blower wheel, excessive wind, defective blower motor, defective switch or connections, inadequate combustion air (rollout switch open). How to fix →
34Ignition proving failure: control tries three more times before lockout 14.Oxide on the flame sensor (clean with fine steel wool); flame current 0.5 µA DC minimum, 4.0-6.0 nominal; manual valve, control ground continuity, gas valve defective or off, low inlet gas pressure, poor carryover or rough ignition, defective hot surface igniter, flame sensor grounded, green/yellow wire not connected to furnace sheet metal. How to fix →
45Control circuitry lockout: gas valve relay stuck open, flame sense circuit failure or software check error.Auto-resets after one hour. Reset power to clear it; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: ICP N95ESN Installation, Start-up, Operating and Service and Maintenance Instructions N95ESN-05SI, Fig. 68 Service Label Information p. 69 (read at 400 dpi); pressure switch names p. 61. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.

Related

Other brands