Goodman / Amana GMEC96 / GCEC96 Furnace Codes

Applies to: Goodman / Amana GMEC96 / GCEC96 (two-stage, multi-speed ECM: GMEC96, GCEC96, Amana AMEC96, ACEC96). Green, amber and red LEDs on the integrated control, with a LAST ERROR button.

CodeMeaningWhat to check
Solid greenStandby: waiting for a call.Normal.
Rapid greenCall for fan only (24 V on G).Normal.
1 greenNormal operation, low stage cooling call (Ylo and G).Normal.
2 greenNormal operation, high or single stage cooling call (Y and G).Normal.
1 amberNormal operation, low stage heat call (W1).Normal.
2 amberNormal operation, high or single stage heat call (W2).Normal.
3 amberW2 call present without W1; furnace doesn't run.Thermostat or thermostat wiring. How to fix →
4 amberYlo or Y call present without G; furnace doesn't run.Thermostat or thermostat wiring. How to fix →
Rapid amberLow flame sense current.Dirty or coated flame rod (Goodman says clean it with steel wool), poor flame, improper gas pressure, poor flame sense wire or connections. How to fix →
1 redFlame sensed when no flame should be present.Gas valve stuck open, improper wiring to the gas valve, shorted flame rod or wire. Confirm gas safety before working on it.
2 redPressure switch stuck closed / inducer error (inducer may be running).Faulty pressure switch, shorted pressure switch wires, or the board's inducer relay stuck closed. How to fix →
3 redFirst stage (low fire) pressure switch stuck open / inducer error.Faulty pressure switch, switch tubing or wiring, failed inducer relay on the board, vent pipe restriction or too many elbows or too much length. How to fix →
3 double redSecond stage pressure switch stuck open / inducer error.Pressure switch function and tubing; make sure the inducer runs and pulls enough vacuum to close the switch. How to fix →
4 redOpen limit circuit: main limit, aux limit or rollout switch.Temperature rise, duct static, gas pressure, burner alignment, orifice plate position, wiring to all limits. How to fix →
5 redLimit and rollout circuit open for 15 minutes, open control board fuse, or open rollout switch.Control board fuse, temperature rise, duct static, gas pressure, burner alignment, orifice plate position, wiring to all limits. How to fix →
6 redPressure switch cycling lockout: the switch opened 5 times in one heating cycle.Excessive venting restriction, leaking pressure switch tubing. How to fix →
7 redLockout: too many retries because flame wasn't proven during trial for ignition.Gas pressure, gas valve, front cover pressure switch, flame rod. How to fix →
8 redLockout: too many recycles because flame was lost after being proven.Gas pressure, gas valve, front cover pressure switch, flame rod. How to fix →
9 redImproper grounding or reversed polarity.Hot and neutral reversed at the furnace. The hot wire (door switch and L1 on the board) should read 115 V to ground and to neutral; neutral should read 0 V to ground.
10 redGas valve current detected with no call for heat.Make sure the gas valve isn't getting voltage from an electrical short. If the valve wiring is correct, replace the control board.
11 redLimit switch open for more than 5 minutes (blower failure); inducer running.Reset main power and check indoor blower operation. How to fix →
12 redControl board igniter relay not energizing the igniter.Replace the control board. How to fix →
Solid redControl board internal fault (internal, gas valve, micro and frequency check).Replace the control board.
Rapid redTwinning error.Correct the twinning wiring.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Goodman/Amana GMEC96/GCEC96 & AMEC96/ACEC96 Service and Troubleshooting manual RS6612013 Rev. 10 (2020), Troubleshooting Chart pp. 58-59, LED code table, fault recall and lockout reset p. 60. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.