Home / Charts / Lennox furnace codes

Lennox G60DF / G60DFV Furnace Codes

Applies to: Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901). Two LEDs on the SureLight control, DS1 and DS2, read together.

Lennox's SureLight service literature also covers boards 100869 (G60UH) and 100870 (G60UHV), which use X + Y flash codes instead; those are the second table on the Lennox document.

CodeMeaningWhat to check
Both slow flash togetherNormal power-on; also shown in cooling and continuous fan.
Both fast flash togetherNormal operation: heating demand at the thermostat.
DS1 slow flash, DS2 onPrimary, secondary or rollout limit open. Limits must close within 3 minutes or the unit goes into a 1-hour Watchguard.Airflow first: filter, blower, closed registers, dirty coil. How to fix →
DS1 off, DS2 slow flashLow pressure switch open, blocked inlet or exhaust vent, or low pressure switch closed before the inducer started. How to fix →
DS1 off, DS2 fast flashHigh pressure switch open, blocked inlet or exhaust vent, or high pressure switch closed before the inducer started. How to fix →
Alternating slow flashWatchguard: burners failed to ignite, limit open over 3 minutes, flame lost 5 times in one heating cycle, or pressure switch opened 5 times in one heating cycle. How to fix →
DS1 slow flash, DS2 offFlame sensed with the gas valve not energized.Gas valve leaking through or a shorted flame sense circuit. How to fix →
Both on, or one on and one offCircuit board failure or miswired control.Check 24 V and 115 V at the board before replacing it.
DS1 fast flash, DS2 slow flashMain power polarity reversed.Swap line and neutral.
DS1 slow flash, DS2 fast flashLow flame signal (below 0.2 microamps).Clean or replace the flame sense rod; check ground. How to fix →
Alternating fast flash (during ignitor warm-up)Improper main ground, broken ignitor or open ignitor circuit, or line voltage below 75 V. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Lennox SureLight Ignition System, Two Stage and Two Stage Variable Speed, Service Literature Corp. 0222-L7 (revised 11-2006), Table 5. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.