York TG9S Furnace Codes
Johnson Controls also sells furnaces under the Coleman and Luxaire names. Codes match only when the control board is the same, so check the label inside the blower door.
| Code | Meaning | What to check |
|---|---|---|
| Slow green | Normal operation, no thermostat calls. | |
| Slow amber | Normal operation with call for heat. | |
| LED off | LED does not flash at all. | Check power to the board and the 3-amp fuse on the board. If power and fuse are good, the control board may need to be replaced. How to fix → |
| Steady on, any color | Control failure. | Turn power off and back on. If the code returns, replace the control board; it is not field-repairable. |
| Continuous amber flash | Flame sense current is below 1.5 microamps. | Clean the flame sensor and check gas flow. Current should be above 1.5 microamps at the flame current test pad (normal is about 3.7 microamps DC; lockout point 0.1). How to fix → |
| 1 red | Flame sensed when there was not a call for heat. | The control runs the inducer and supply blower. Leaking or slow-closing gas valve. How to fix → |
| 2 red | Pressure switch closed when it should be open. | The control checks the switch is open at the start of each heat cycle. Faulty pressure switch or miswiring. How to fix → |
| 3 red | Pressure switch contacts open when they should be closed. | Faulty inducer, blocked vent pipe, broken pressure switch hose, disconnected switch or inducer wires, faulty pressure switch. How to fix → |
| 4 red | Main limit switch open. | The control runs the blower and inducer while the limit is open. Dirty filter, undersized ducts, wrong blower speed, incorrect firing rate, loose limit wiring or faulty blower motor. Five limit trips in one call for heat also gives 4 red and a one-hour soft lockout; open longer than five minutes becomes 11 red. How to fix → |
| 5 red | Rollout switch open. | Manual reset. Check combustion air, inducer operation, heat exchanger failure or a burner problem. Hard lockout: cycle power after the problem is corrected. How to fix → |
| 6 red | Pressure switch opened four times during the call for heat. | Faulty inducer, blocked vent pipe or faulty pressure switch. Locks out for one hour, then restarts. How to fix → |
| 7 red | Flame not established during three trials for ignition. | Gas valve switch ON, low or no gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface igniter, loose wires or a burner problem. Locks out for one hour, then restarts. How to fix → |
| 8 red | Flame lost five times (four recycles) during the heating cycle. | Low gas pressure, dirty or faulty flame sensor or faulty gas valve. Locks out for one hour, then restarts. How to fix → |
| 9 red | Reversed line voltage polarity, grounding problem, or incorrect 24 V phasing. | Check polarity at the furnace and branch circuit, furnace ground, and that the flame probe isn't shorted to the chassis. Phasing: measure 120 V line to the 24 V R terminal; you should read line minus secondary voltage. If you read line plus secondary, reverse the transformer secondary connections. On twinned furnaces it can mean a twinning error. |
| 10 red | Gas valve energized with no call for heat. | Main blower and inducer run and no ignition sequence starts while this lasts. Check the gas valve and its wiring. |
| 11 red | Main limit open for more than five minutes. | Usually a failed blower motor or blower wheel. Hard lockout: cycle power after the problem is corrected. How to fix → |
| 4 amber | Y signal from the thermostat without a G signal. | The furnace still heats and cools normally; the code flags a wiring problem. Make sure the G wire from the thermostat is connected. How to fix → |
How to read the codes
- Slow flash: two seconds on, two off. Counted codes: 1/3 second on and 1/3 off, repeated the number of times equal to the code, with a two-second pause between codes. Continuous flashes have no pause.
- To read stored codes: end any call for heat, cooling or continuous fan, then push the LAST ERROR button. The LED flashes up to five stored codes, newest first, with a two-second pause between them, then returns to a slow green flash. Two green flashes means no codes are stored.
- To clear stored codes, hold LAST ERROR for more than five seconds; the LED flashes three green when memory is cleared. Codes survive a power loss.
- Soft lockout resets itself after one hour. Hard lockout needs power turned off and back on.
Source: York TG9S Installation Manual, 1083287-UIM-L-1219, Furnace Control Diagnostics p. 38 and Diagnostic Fault Code Storage and Retrieval p. 39. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Rheem / Ruud R98V (98% modulating communicating, upflow)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage)
- Carrier 59TP6C two-stage condensing with InteliSense (Performance series)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T (95% single-stage condensing, constant-torque blower; model numbers (-)951T)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise)
- Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58SB0A / 58SB1A (single-stage, non-condensing)