Home / Charts / Trane / American Standard furnace codes

Trane / American Standard S8B1 / S8X1 / S8X2 Furnace Codes

Applies to: Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage). Seven-segment display on the integrated furnace control (IFC).

Covers the single-stage S8B1 and S8X1 and the two-stage S8X2. American Standard sells matching models; check the label on the unit.

CodeMeaningWhat to check
E01Loss of the IRQ or other internal failures (internal IFC error).Replace the integrated furnace control if it repeats.
E2.1Retry exceeded: flame never sensed. One-hour lockout after 3 times.Gas supply, igniter, gas valve, flame sensor. How to fix →
E2.2Recycles exceeded: flame sensed then lost. One-hour lockout after 10 times.Flame sensor, ground, gas pressure, pressure switch dropping out. How to fix →
E2.31st-stage gas valve not energized when it should be, exceeded after 10 times.Gas valve wiring and the circuit through the limits and pressure switch. How to fix →
E3.1Shorted pressure switch, 1st stage.Switch stuck closed or a wiring short. How to fix →
E3.2Open pressure switch, 1st stage.Vent blockage, hoses, inducer, switch. How to fix →
E3.3Shorted pressure switch, 2nd stage (S8X2 only).Switch stuck closed or a wiring short. How to fix →
E3.4Open pressure switch, 2nd stage (S8X2 only).Vent blockage, hoses, inducer, switch. How to fix →
E04Open limit (main thermal, rollout switch, or reverse airflow switch).Airflow first; a tripped rollout needs a vent and heat exchanger check before resetting. How to fix →
E05Flame detected, should not be present.Gas valve leaking through or a shorted flame sense circuit. How to fix →
E6.1Voltage reversed polarity.Hot and neutral reversed.
E6.2Bad grounding.Furnace and burner ground.
E6.3Igniter relay fails, or igniter open.Check the igniter before the control. How to fix →
E7.11st-stage gas valve (MVL) is energized when it should be off.Gas valve wiring; control.
E08Flame current is low, but still strong enough to allow operation.Clean the flame sensor; check ground and gas pressure. How to fix →
E11Gas valve circuit: 1st-stage valve not energized when it should be, 1st-stage relay stuck closed, or (S8X2) a 2nd-stage valve or relay fault.Gas valve wiring and the control's valve relays.
E12Open fuse.Short in the 24 V wiring. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Trane Installer's Guide, S8B1 / S8X1 / S8X2 gas furnaces, 18-CE16D1-1C-EN (2021), Integrated Furnace Control Display Codes, p. 58. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.