Home / Charts / ICP (Heil, Tempstar, Comfortmaker, Arcoaire) furnace codes

ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R96MSN / N96MSN Furnace Codes

Applies to: ICP (Heil, Tempstar, Comfortmaker, Arcoaire) R96MSN / N96MSN (single-stage 35-in. condensing, 4-way multipoise). Three-digit display on the furnace control (major.minor code); the LED seen through the door sight glass flashes the major code.

International Comfort Products builds furnaces sold under several brand names, including Heil, Tempstar, Comfortmaker and Arcoaire. The R96MSN service label and troubleshooting guide match the Carrier 59SC2E's. The N96MSN manual (N96MSN-03SI, Fig. 60 p. 58) prints the identical label.

CodeMeaningWhat to check
10.1L1 polarity fault (rapid flash LED): incoming 115 V polarity reversed.Line voltage polarity at each junction; on twinned units, the 24 V transformer phasing.
12.1W on at power up (normal).The blower runs 90 seconds if power comes on during a call for heat, or when R-W opens during the blower on-delay.
13.1Limit circuit lockout: limit or flame rollout open longer than 3 minutes.Auto-resets after 3 hours. See 33.1. How to fix →
14.1Ignition lockout: failed to ignite and prove flame in 4 attempts.Auto-resets after 3 hours. Manifold pressure and firing rate, gas inlet pressure swings; see 34.1. How to fix →
14.2Flame lost lockout: flame lost 3 times after the heating blower on-delay.Auto-resets after 3 hours. Manifold pressure and firing rate, gas inlet pressure swings; see 34.3. How to fix →
14.3Flame lost lockout: flame lost 7 times during one heat request.Manifold pressure and firing rate, gas inlet pressure swings; see code 34. How to fix →
21.1Gas heating lockout: 24 VAC sensed on the gas valve when it shouldn't be.Turn off power and wait 5 minutes to retry. Stuck-closed gas valve relay on the control, or a miswire or short on the gas valve wire.
22.1False flame: flame proved while the gas valve is off; inducer runs until it clears.Stuck-open or leaky gas valve.
23.1Stuck main pressure switch (closed).Obstructed pressure tube, or pressure switch stuck closed. How to fix →
23.2Stuck closed secondary pressure switch.Listed on the service label only; the troubleshooting guide's 23.1 checks are an obstructed pressure tube or a switch stuck closed. How to fix →
24.1Fuse fault.Short in the 24 V wiring, including thermostat leads; disconnect the thermostat leads to isolate it. How to fix →
25.1No program info in the micro; no heating.Program-related codes: reprogram the control with the correct program number from the rating plate (service app or super plug); replace the control if the issue remains.
25.2Corrupted program file; no heating.Reprogram the control using the service app or a super plug (sold separately).
25.3Twinned units not identical (program numbers don't match); main unit won't run.Twinned furnaces must have the same program number.
25.4Main program invalid; running on the backup program.Reprogram the control. It still operates normally.
25.5Installer settings corrupted; running on default installer settings.Reselect the installer settings or reprogram the control.
25.6Wrong program for the control; no heating.Reprogram the control so the program matches the control.
25.7Non-condensing program detected in a condensing model.Program-related codes: reprogram the control with the correct program number from the rating plate (service app or super plug); replace the control if the issue remains.
27.1Super plug program missing, not recognized or corrupted.Remove the super plug and retry; if 27 remains, try a different super plug; if it still fails, replace the control.
27.2Super plug program missing, not recognized or corrupted.Remove the super plug and retry; if 27 remains, try a different super plug; if it still fails, replace the control.
27.3Super plug program missing, not recognized or corrupted.Remove the super plug and retry; if 27 remains, try a different super plug; if it still fails, replace the control.
31.2Open secondary pressure switch (HPS): didn't close within one minute after the gas valve closed, or reopened.Excessive wind, restricted vent or wrong vent sizing, defective inducer, low inlet gas pressure (if LGPS used), inadequate combustion air, disconnected or obstructed pressure tubing, restricted or blocked condensate drainage. How to fix →
31.3Secondary pressure switch lockout: failed to close after three trials.Same checks as 31.2. If it opens during the blower on-delay, the blower runs for the selected off-delay. How to fix →
32.1Open main pressure switch (LPS): open longer than 5 minutes or reopened.The inducer shuts off for 15 minutes before retrying. See 31.2 and 31.3 for the checks. How to fix →
33.1A switch opened in the main limit circuit (limit or flame rollout).Blower runs 4 minutes or until the switch remakes; over 3 minutes it becomes 13.1. Flame rollout and BVSS need a manual reset. Dirty filter or restricted ducts, loose blower wheel, defective switch or connections, defective blower motor, improper gas input. How to fix →
34.1Ignition proving failure: flame not sensed during trial for ignition; tries four times before 14.1.Low inlet gas pressure, control ground continuity, manual shut-off valve, green/yellow wire connected from the furnace to the burner box screw, flame sensor not grounded or touching the casing. In component test, the igniter should glow orange/white within the 15-second warm-up; flame current should be 4.0-6.0 µA nominal (clean the sensor with fine steel wool if under 0.5 µA during trial). How to fix →
34.2Flame lost after ignition, before the heating blower on-delay.Same checks as 34.1. How to fix →
34.3Flame lost after ignition, after the heating blower on-delay.Same checks as 34.1. How to fix →
45.1Control failure: flame circuit fault, memory mismatch or sequence error.Cycle power; if 45 repeats, replace the control.
45.2Control failure: gas valve relay won't close.Cycle power; if 45 repeats, replace the control.
45.3Control failure: EEPROM memory issue.Cycle power; if 45 repeats, replace the control.
46.1Momentary loss of power.Heating stops and restarts once the power fluctuation is resolved.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: ICP R96MSN Installation, Start-up, Operating and Service and Maintenance Instructions R96MSN-03SI (7/26), Fig. 60 service label p. 56, Troubleshooting Guide pp. 74-75. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.

Related

Other brands