Carrier 59MN7A / 59MN7B Furnace Codes

Applies to: Carrier 59MN7A / 59MN7B (modulating condensing, 4-way multipoise; also 987MA, 987MB). LED on the furnace control, two-digit status codes.

The 59MN7B instructions (59MN7B-02SI, Fig. 71 p. 73) print the same service label text as the 59MN7A. The newer 59MN7C uses three-digit codes and has its own chart. Bryant's manuals print the identical service label: Bryant 987MA (II987MA-12, p. 72) and 987MB (II987MB-02, p. 73).

CodeMeaningWhat to check
11No previous code.Stored codes are erased automatically after 72 hours or when cleared (see above). After the component test, 11 means the inducer and blower tested OK; check the hot surface igniter visually.
12Blower on after power up (115 VAC or 24 VAC).The blower runs 90 seconds if the unit is powered up during a call for heat (R-W/W1 closed) or R-W/W1 opens during the blower on-delay.
13Limit circuit lockout: a limit or flame rollout switch open longer than 3 minutes, or 10 successive limit trips during maximum heat.Auto-resets after 3 hours. See 33. How to fix →
14Ignition lockout.Auto-resets after 3 hours. See 34. How to fix →
15Blower motor lockout: the blower failed to reach 250 RPM or to communicate within 30 seconds of being turned on, in two successive heating cycles.Auto-resets after 3 hours. See 41.
21Gas heating lockout (does NOT auto reset).Mis-wired gas valve, or a defective control (valve relay).
22Abnormal flame-proving signal: flame is proved while the gas valve is de-energized.The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve.
23Pressure switch did not open.Obstructed pressure tubing, or a pressure switch stuck closed. How to fix →
24Secondary voltage fuse is open.Short circuit in the 24 VAC wiring. How to fix →
25Model selection or setup error: model plug (PL4) missing or wrong, or setup switch SW1-1 or SW1-6 set wrong.If the code flashes only 4 times at power-up, the control is using the model selection stored in memory. Check for a thermostat call with SW1-1 ON or with SW1-6 ON, SW1-1 and SW1-6 both ON, or two different furnace models twinned. If it flashes continuously, check the model plug number and resistance values on the rating plate.
31Medium pressure switch, high pressure switch or PSR relay did not close or reopened.The medium or high pressure switch failed to close on a call for intermediate or maximum heat, or opened during the heat cycle. The PSR relay may be defective. See 32. How to fix →
32Low pressure switch did not close or reopened.It failed to close on a call for heat or opened during minimum heat; if it opens within 5 minutes after ignition, the next heating cycle is limited to maximum heat. Check vent sizing, a plugged condensate drain, low inlet gas pressure (if an LGPS is used), pressure switch wiring, a restricted vent, disconnected or obstructed pressure tubing, excessive wind, water in the vent piping (possible sagging pipe), and failed or out-of-calibration pressure switches. How to fix →
33Limit circuit fault: a limit or flame rollout switch is open, or the furnace is in maximum heat after 2 successive low or medium range limit trips.The blower runs 4 minutes or until the switch closes, whichever is longer; open more than 3 minutes changes to lockout 13. The flame rollout switch needs a manual reset. Check for an improper limit switch or missing limit gasket, the switch or its connections, gas input adjustment and a loose blower wheel. How to fix →
34Ignition proving fault: the control tries three more times before lockout 14.If the flame signal is lost during the blower on-delay, the blower runs for the selected off-delay. Check for oxide on the flame sensor (clean with fine steel wool), flame current (0.5 microamps DC minimum, 4.0-6.0 nominal), the manual shut-off valve, control ground continuity, a defective or OFF gas valve, low inlet gas pressure, poor flame carryover or rough ignition, a defective hot surface igniter, and a grounded flame sensor. The green/yellow wire must be connected to the furnace sheet metal. How to fix →
35Gas valve fault: the modulating gas valve failed to communicate.Check the connection to the furnace control and the gas valve.
41Blower motor fault: the blower failed to reach 250 RPM or to communicate in time (30 seconds after being turned on, or 10 seconds during steady operation).After the component test: check the blower, wiring and furnace control.
42Inducer motor fault: inducer didn't start within 20 seconds of a call for heat, its RPM is out of range, or its RPM signal was lost for 5 seconds.Check vent sizing, a restricted combustion air supply, a failed inducer motor and the motor wiring.
43Low or medium pressure switch open while the medium or high pressure switch is closed.Check for a plugged condensate drain, switches closing out of order (HPS before LPS, HPS before MPS, MPS before LPS), low inlet gas pressure (if an LGPS is used), pressure switch wiring, water in the vent piping (possible sagging pipe), a stuck-open low or medium pressure switch, and disconnected or obstructed pressure tubing. How to fix →
45Control circuitry lockout: gas valve relay stuck open, flame sense circuit failure or software check error.Auto-resets after 1 hour. Reset power to clear the lockout; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: Carrier 59MN7A Installation, Start-up, Operating and Service and Maintenance Instructions 59MN7A-10SI, Fig. 62 Service Label Information p. 73 (read at 400 dpi). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.