Home / Charts / ICP (Heil, Tempstar, Comfortmaker, Arcoaire) furnace codes

ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU Furnace Codes

Applies to: ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU (80% single-stage, ECM blower, Ultra Low NOx, minor series 2 and 3). STATUS LED on the furnace control.

International Comfort Products builds furnaces sold under several brand names, including Heil, Tempstar, Comfortmaker and Arcoaire. This chart is from the N80ESU manual. Unlike the N8MSN and N9MSE, this ultra low NOx furnace uses a pressure transducer and an inducer RPM signal instead of a pressure switch, so codes 2, 3 and 4+2 mean different things. Go by the service label on the furnace you're working on.

CodeMeaningWhat to check
2Pressure above 0.15 in. w.c. at start-up.The transducer reads pressure before the inducer runs. Check for obstruction in the pressure tubing or transducer vent holes, a defective transducer, and the transducer wiring. How to fix →
3Pressure transducer input does not sense target pressure, or pressure is out of range.Check: excessive wind, vent sizing, restricted vent, defective inducer motor, inadequate combustion air supply, defective pressure transducer, low inlet gas pressure (if an LGPS is used), low inducer voltage (115 VAC), disconnected or obstructed pressure tubing. How to fix →
5Abnormal flame-proving signal.Flame is proved while the gas valve is de-energized. The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve.
6Ignition proving failure.The control tries ignition four times before locking out. If the flame signal is lost during the blower on-delay, the blower comes on for the selected off-delay. Check: oxide on the flame sensor (clean with fine steel wool); flame current (0.5 microamps DC minimum, 4.0-6.0 nominal); manual valve shut off; low inlet gas pressure; control ground continuity; gas valve defective or turned off; flame sensor grounded or touching the casing; poor flame carryover or rough ignition; green/yellow wire must be connected to the furnace sheet metal. How to fix →
7Limit circuit lockout.A limit, draft safeguard, burner thermal switch or blocked vent switch (if used) is open. The control auto-resets after three hours. Check: loose blower wheel, restricted vent, vent sizing, excess wind, dirty filter or restricted ducts, a defective switch or connections, inadequate combustion air (burner thermal switch open). How to fix →
8Gas heating lockout.The control will NOT auto-reset. Check for a miswired gas valve, a defective control (valve relay), or 24 VAC at the gas valve when it shouldn't be there.
10Polarity.Line voltage (115 VAC) polarity reversed.
1+2Blower on after power up.The blower runs for 90 seconds if power comes on (115 VAC or 24 VAC) during a call for heat (R-W closed), or if R-W opens during the blower on-delay.
2+5Invalid model selection or setup error.The model plug is missing or incorrect. If the code flashes 4 times on power-up, the control is defaulting to the model selection stored in memory.
4+2Inducer motor fault.The control didn't see RPM pulses from the inducer within 20 seconds after a heat request, the inducer is outside its valid range, or the RPM signal was lost for 5 seconds while running. Check: vent sizing, restricted combustion air supply, a failed inducer motor, improper or loose motor wiring or a bad connection. How to fix →
6+1Ignition lockout.The control auto-resets after three hours. See code 6. How to fix →
OFFLED off: secondary voltage fuse open.Check for a short circuit in the secondary (24 VAC) wiring. Also check 115 VAC at L1 and L2 and 24 VAC at SEC-1 and SEC-2. How to fix →
ON / SOLIDLED on solid: control circuitry lockout.Auto-resets after one hour. Caused by a stuck-open gas valve relay, a flame sense circuit failure or a software check error. Reset power to clear it; replace the control if the code repeats.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a limit, rollout or pressure switch to keep a furnace running. Gas and line-voltage work is for trained technicians.

Source: ICP N80ESU Installation, Start-up, Operating and Service and Maintenance Instructions, 441 01 1501 04 (edition 04/21), Service Guide, p. 33. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.