ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80ESU / R80ESU Furnace Codes
International Comfort Products builds furnaces sold under several brand names, including Heil, Tempstar, Comfortmaker and Arcoaire. This chart is from the N80ESU manual. Unlike the N8MSN and N9MSE, this ultra low NOx furnace uses a pressure transducer and an inducer RPM signal instead of a pressure switch, so codes 2, 3 and 4+2 mean different things. Go by the service label on the furnace you're working on.
| Code | Meaning | What to check |
|---|---|---|
| 2 | Pressure above 0.15 in. w.c. at start-up. | The transducer reads pressure before the inducer runs. Check for obstruction in the pressure tubing or transducer vent holes, a defective transducer, and the transducer wiring. How to fix → |
| 3 | Pressure transducer input does not sense target pressure, or pressure is out of range. | Check: excessive wind, vent sizing, restricted vent, defective inducer motor, inadequate combustion air supply, defective pressure transducer, low inlet gas pressure (if an LGPS is used), low inducer voltage (115 VAC), disconnected or obstructed pressure tubing. How to fix → |
| 5 | Abnormal flame-proving signal. | Flame is proved while the gas valve is de-energized. The inducer runs until the fault clears. Check for a leaky or stuck-open gas valve. |
| 6 | Ignition proving failure. | The control tries ignition four times before locking out. If the flame signal is lost during the blower on-delay, the blower comes on for the selected off-delay. Check: oxide on the flame sensor (clean with fine steel wool); flame current (0.5 microamps DC minimum, 4.0-6.0 nominal); manual valve shut off; low inlet gas pressure; control ground continuity; gas valve defective or turned off; flame sensor grounded or touching the casing; poor flame carryover or rough ignition; green/yellow wire must be connected to the furnace sheet metal. How to fix → |
| 7 | Limit circuit lockout. | A limit, draft safeguard, burner thermal switch or blocked vent switch (if used) is open. The control auto-resets after three hours. Check: loose blower wheel, restricted vent, vent sizing, excess wind, dirty filter or restricted ducts, a defective switch or connections, inadequate combustion air (burner thermal switch open). How to fix → |
| 8 | Gas heating lockout. | The control will NOT auto-reset. Check for a miswired gas valve, a defective control (valve relay), or 24 VAC at the gas valve when it shouldn't be there. |
| 10 | Polarity. | Line voltage (115 VAC) polarity reversed. |
| 1+2 | Blower on after power up. | The blower runs for 90 seconds if power comes on (115 VAC or 24 VAC) during a call for heat (R-W closed), or if R-W opens during the blower on-delay. |
| 2+5 | Invalid model selection or setup error. | The model plug is missing or incorrect. If the code flashes 4 times on power-up, the control is defaulting to the model selection stored in memory. |
| 4+2 | Inducer motor fault. | The control didn't see RPM pulses from the inducer within 20 seconds after a heat request, the inducer is outside its valid range, or the RPM signal was lost for 5 seconds while running. Check: vent sizing, restricted combustion air supply, a failed inducer motor, improper or loose motor wiring or a bad connection. How to fix → |
| 6+1 | Ignition lockout. | The control auto-resets after three hours. See code 6. How to fix → |
| OFF | LED off: secondary voltage fuse open. | Check for a short circuit in the secondary (24 VAC) wiring. Also check 115 VAC at L1 and L2 and 24 VAC at SEC-1 and SEC-2. How to fix → |
| ON / SOLID | LED on solid: control circuitry lockout. | Auto-resets after one hour. Caused by a stuck-open gas valve relay, a flame sense circuit failure or a software check error. Reset power to clear it; replace the control if the code repeats. |
How to read the codes
- Each code is one or two digits. The first number is the count of short flashes; the number after the plus sign is the count of long flashes. For example, 6+1 is six short flashes then one long.
- Heartbeat: the control has 24 VAC. That's normal. LED continuously off: check for 115 VAC at L1 and L2 and 24 VAC at SEC-1 and SEC-2.
- To recall the last stored code, briefly (2-3 seconds) remove and reconnect one main limit wire. After the stored code, the component test runs.
- Stored codes erase automatically after 72 hours.
- Component test without a code recall: shut off the thermostat (or disconnect R) and briefly short TEST/TWIN to C. The LED flashes the most recent code 4 times, then the inducer runs for the whole test while the hot surface igniter, fan speed, heat speed and cool speed each come on for 10-15 seconds. The gas valve and humidifier stay off. At the end, a heartbeat means the blower tested OK (look at the inducer and igniter yourself); 2+5 is a setup error; 4+2 means the inducer failed the test.
- The label's text for 6+1 says "refer to status code #34" and code 6 mentions "lockout #14". Those look like leftovers from older code numbers; on this furnace the lockout after failed ignition is 6+1.
Source: ICP N80ESU Installation, Start-up, Operating and Service and Maintenance Instructions, 441 01 1501 04 (edition 04/21), Service Guide, p. 33. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.
Related
- How to read furnace LED flash codes
- Furnace pressure switch troubleshooting
- Flame sensor microamps and cleaning
Other brands
- Lennox Merit ML180UH (80% single-stage)
- Carrier 58CVA / 58CVX (80% variable-speed two-stage)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N9MSE (90% single-stage condensing, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N8MSN / N8MSL (80% single-stage, PSC blower)
- ICP (Heil, Tempstar, Comfortmaker, Arcoaire) N80MSU (80% single-stage, ECM blower, Ultra Low NOx, 3-digit display, minor series 3)
- Rheem / Ruud R96V / 96MDV (96% two-stage communicating)
- Rheem / Ruud R97V (97% modulating communicating, downflow/horizontal)
- Rheem / Ruud R98V (98% modulating communicating, upflow)
- Goodman / Amana GR9S80 / GD9S80 (80% single-stage)
- Trane / American Standard S9X1 / S9X2 / S9B1 (96% condensing)
- Lennox SL280UHV (80% two-stage variable speed)
- Goodman / Amana / Daikin GM9S96 / GC9S96 / GM9S92 (96% and 92% condensing, single-stage)
- Carrier 59TP6C two-stage condensing with InteliSense (Performance series)
- Lennox G60DF / G60DFV (older two-stage SureLight boards 18M3401, 46M9901, 18M9901, 49M5901)
- Lennox G60UH / G60UHV (SureLight boards 100869 and 100870)
- Rheem / Ruud R801T Ultra Low NOx (14 ng/J) single-stage upflow/horizontal, constant-torque blower
- Rheem / Ruud 802V / 80MDV (80% two-stage communicating, ECM blower; model numbers (-)802V and (-)(-)80MDV)
- Trane / American Standard S8B1 / S8X1 / S8X2 (80% single-stage and two-stage)
- Trane / American Standard A801X060AM3S (80% single-stage, 2024 installation manual)
- Trane / American Standard A801X (80% single-stage: A801X040AM3SD, A801X040BM2SD, A801X060BM4SD, A801X080BM4SD, A801X080CM5SD, A801X100CM5SD, A801X120DM5SD)
- Goodman / Amana GMVC96 / GCVC96 (96% two-stage variable-speed, *MVC96*BA and *CVC96*BA)
- Goodman / Amana GMVS96 / AMVS96 U-revision (96% variable-speed with analog pressure sensor, model numbers GMVS96*U and AMVS96*U)
- Goodman / Amana GMVM96 / GCVM96 / AMVM96 / ACVM96 (96% modulating, model numbers *MVM96 and *CVM96)
- Rheem / Ruud R801T / 80MSX (80% single-stage, constant-torque blower; model numbers (-)801T and (-)(-)80MSX)
- Rheem / Ruud 802P / 80MDP (80% two-stage, model numbers (-)802P and (-)(-)80MDP)
- Rheem / Ruud 802T / 80MDT (80% two-stage with constant-torque blower, model numbers (-)802T and (-)(-)80MDT)
- Rheem / Ruud 801S / 801P / 80MSS / 80MSP (80% single-stage, model numbers (-)801S, (-)801P, (-)(-)80MSS and (-)(-)80MSP)
- Rheem / Ruud W801T (Rheem Select 80% downflow single-stage)
- Rheem / Ruud R951T (95% single-stage condensing, constant-torque blower; model numbers (-)951T)
- Rheem / Ruud 801V Ultra Low NOx (80% communicating, constant CFM blower, upflow/horizontal)
- Carrier 58STA / 58STX (80% single-stage, 4-way multipoise)
- Carrier 58CTA / 58CTX (80% two-stage, 4-way multipoise, Series 140/E)
- York TG9S (95.5% AFUE single-stage PSC, multi-position)
- York TM9V (96% AFUE two-stage variable-speed ECM, multi-position)
- York UTEC Board (single- and two-stage furnaces from August 2009; SAP 539617, 542760, 542767, 542766; Source 1 S1-33102956000, S1-03102951001, S1-33102954000, S1-33102955000)
- York White-Rodgers Board (the generation before the 2009 UTEC boards; 265901, S1-33109167000 / 265902, S1-33109168000 / 265903, S1-33109169000 / 265904)
- York TI Board (older furnaces; 031-01972-000 TI 6DT-1, 031-01973-000 TI 6DT-2, 031-09117-000 TI 6MD-1, 031-09118-000 TI 6MI-1)
- Carrier 58SB0A / 58SB1A (single-stage, non-condensing)
Did you find your code?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
HVAC Cheat Sheet · Free PT charts, code lookups and calculators for techs at hvaccheatsheet.com