Thermostat Wiring Diagrams
HVAC Cheat Sheet · hvaccheatsheet.com/charts/thermostat-wiring-diagrams
A typical furnace + AC uses five wires: R (24V power), C (common), G (fan), Y (cooling) and W (heat), each landing on the matching letter at the furnace board, with Y and C continuing to the outdoor unit. A heat pump adds O/B (reversing valve) and AUX/W2 (electric backup heat). Match terminal letters, not wire colors.
Prints all three diagrams and the terminal key.
Some heat pumps also run a wire from the outdoor defrost board to the air handler's heat strips (often labeled W or X) to temper air during defrost. Check the unit's diagram.
Terminal key
| Terminal | What it does |
|---|---|
| R (Rh, Rc) | 24 VAC hot from the transformer. Rh/Rc split heating and cooling power on systems with two transformers; a jumper joins them on single-transformer systems. |
| C | 24 VAC common, the return side of the transformer. Powers Wi-Fi and smart thermostats continuously. |
| G | Indoor blower fan. |
| Y (Y1) | Cooling: energizes the outdoor contactor (and the compressor on a heat pump in both modes). Y2 = second stage. |
| W (W1) | Heat: furnace or boiler call. W2 = second stage heat. |
| O/B | Heat pump reversing valve. O energizes in cooling (most brands); B energizes in heating (Rheem/Ruud and some others). Set the thermostat to match. |
| AUX / W2 / E | Heat pump auxiliary electric heat. E is emergency heat (aux without the compressor); many installs land AUX and E on the same air handler terminal. |
Wire colors shown are common convention only. Installers don't always follow them.
Related
- Thermostat wiring terminals and colors explained
- How to test a contactor
- Heat pump blowing cold air in heat mode (often an O/B setting problem)