How to Test a Furnace Hot Surface Igniter (and Why They Keep Failing)

The hot surface igniter (HSI) is one of the most replaced parts on a gas furnace, and one of the easiest to diagnose.

Safety: Igniters get hot enough to burn instantly and carry line voltage during warm-up. Keep hands clear while testing, and turn power off before unplugging it.

Watch the sequence first

On a call for heat, a typical furnace runs the inducer, proves the pressure switch, then powers the igniter for a warm-up period before opening the gas valve. Watch through the sight glass or with the burner door open, as the manufacturer allows:

What you see Points to
Inducer runs, igniter never glows Igniter, its wiring or plug, or no voltage from the board
Igniter glows dim orange instead of bright Low voltage at the igniter, or a weak igniter
Igniter glows, gas valve never opens Gas valve or its circuit, or the board; see ignition lockout
Igniter glows, gas lights, shuts off in seconds Flame sensing, not the igniter; see flame sensor readings
Inducer runs, nothing else Pressure switch; see pressure switch troubleshooting

Step by step

  1. Read the board's LED code before cycling power.
  2. Call for heat and wait for the igniter's warm-up period.
  3. Measure voltage at the igniter plug during warm-up. It should match the manufacturer's spec. No voltage means a board or wiring problem.
  4. Voltage present, no glow: turn power off, unplug the igniter and measure its resistance. An open reading confirms it's failed. A reading far outside the manufacturer's range points to a failing igniter.
  5. Inspect it with a light: hairline cracks, white or chalky spots, and broken mounting are all reasons to replace it.
  6. Check the connector for burned or loose pins.

Silicon carbide vs. silicon nitride

Silicon carbide Silicon nitride
Look Gray-black, often a flat or zig-zag element Usually a smaller, darker, rounded or flat element
Durability Fragile; cracks if bumped or touched Much tougher
Warm-up Typically longer Typically faster
Replacement Universal or OEM Usually OEM or a matched universal; board timing and voltage must match

The board controls voltage and warm-up time for the igniter it was designed for. A universal igniter must list your furnace model or be rated for the same voltage and type.

Why igniters keep failing

  • Touching the element. Skin oils create hot spots that crack it.
  • High line voltage. Measure supply voltage; consistently high voltage shortens igniter life.
  • Wrong igniter for the board's voltage and timing.
  • Short cycling from a high limit or pressure switch problem: every extra ignition attempt wears the igniter.
  • Misalignment: an igniter sitting in the flame or too close to the burner overheats.
  • Dust and drywall dust after construction.

Replacing an igniter

  1. Turn off power and gas.
  2. Remove the burner door and unplug the igniter.
  3. Remove the mounting screw and slide it out without touching the element.
  4. Install the new one in the same position, with the same gap to the burner as the original.
  5. Restore power and gas and watch several full ignition cycles.

Common mistakes

  • Replacing the igniter when the board isn't sending voltage.
  • Replacing the igniter when the flame sensor is the problem. If it lights, the igniter worked.
  • Handling the element with bare fingers.
  • Using the wrong type for the board.
  • Not finding why the old one failed early.

FAQ

How long should a furnace igniter last?

It varies. Silicon nitride igniters generally last much longer than silicon carbide. Voltage, handling and how often the furnace cycles all affect life.

Can a bad igniter cause a lockout?

Yes. After several failed ignition attempts, the board locks out. See furnace ignition lockout.

Should I carry spare igniters?

Most service techs carry a universal igniter kit plus common OEM silicon nitride igniters for the brands they see most.

Sources

Related guides

Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.