Friedrich Floating Air R-454B Error Codes

Applies to: Friedrich Floating Air R-454B (single zone; systems FPHW091C, FPHW121C; indoor FAHSW09A1C, FAHSW12A1C, FAHFW09A1C, FAHFW09A3D, FAHFW12A3D, FAHFW18A3D, FAHFW24A3D; outdoor FPHSR09A1C, FPHSR12A1C, FPHSR09A3D, FPHSR12A3D, FPHSR18A3D, FPHSR24A3D). Number shown on the indoor unit's display.

Friedrich is a Rheem company; Rheem sells matching Floating Air units under its own name. The Floating Air Pro has its own chart (same numbers, without 56 and 57).

CodeMeaningWhat to check
EACommunication between the display board and control board interrupted.Loose connection between display and control board; indoor control board; display board wiring.
0Normal.
1Outdoor coil temperature sensor failure.Sensor connector loose; outdoor coil sensor; indoor control board. How to fix →
2Compressor exhaust (discharge) temperature sensor failure.Sensor connector loose; discharge sensor; outdoor control board. How to fix →
5IPM module protection.IPM board; outdoor fan broken, failed or blocked; dirty condenser. How to fix →
6AC voltage higher or lower protection.Supply voltage; the unit's internal supply voltage. How to fix →
7Communication failure between the indoor and outdoor unit.Communication cable loose, miswired or failed; filter board to terminal and to outdoor board connections; indoor control board, PFC board, power board, outdoor control board. How to fix →
8Current overload protection.Fan motor running abnormally; dirty condenser or evaporator; blocked air inlet or outlet.
9Maximum current protection.Outdoor control board or drive board short circuited; other components shorted. How to fix →
10Communication trouble between the outdoor unit and the driver.Loose connection wires; outdoor board or drive board. How to fix →
11Outdoor EEPROM fault.EEPROM chip loose, inserted incorrectly or failed.
12Outdoor ambient temperature too low or too high protection.Outdoor temperature outside the operating range; not a part failure.
13Compressor exhaust (discharge) temperature too high protection.Discharge temperature sensor; low refrigerant charge. How to fix →
14Outdoor ambient temperature sensor failure.Sensor connector loose; ambient sensor; outdoor control board. How to fix →
15Compressor shell temperature too high protection.Friedrich lists the compressor exhaust temperature sensor connector and a low refrigerant charge. How to fix →
16Anti-freeze protection in cooling, or overload protection in heating.Indoor coil sensor connector or sensor; indoor control board; refrigerant system problem. How to fix →
17PFC protection.PFC; outdoor drive board. How to fix →
18DC compressor start failure.Outdoor drive board; compressor. How to fix →
19Compressor drive failure.Outdoor drive board; compressor; outdoor control board. How to fix →
20Outdoor fan motor locked rotor protection.Fan motor connection loose; something blocking the fan; fan motor; outdoor control board. How to fix →
21Outdoor coil anti-overload protection in cooling.Overcharge; outdoor fan motor failed or fan broken; dirty condenser; indoor or outdoor airflow problem.
22Compressor preheating.Normal in cold weather.
23Refrigerant leak in the product.Leak at the indoor unit, outdoor unit or connecting pipe. How to fix →
24Outdoor board chip failure.Wrong drive board or wrong compressor installed. How to fix →
26Overheated outdoor radiator (heat sink).Radiator sensor; sensor detection circuit on the control board. How to fix →
27Protection against too high system pressure.Pressure switch; pressure detection on the control board; system pressure actually over the limit.
33Indoor room temperature sensor failure.Sensor loose or failed; indoor control board. How to fix →
34Indoor coil temperature sensor failure.Sensor loose or failed; indoor control board. How to fix →
36Communication failure between the indoor and outdoor unit.Communication cable connector loose or cable failed; filter board connections; indoor control board, PFC board, power board, outdoor control board. How to fix →
38Indoor EEPROM failure.EEPROM chip loose; indoor control board.
39Indoor fan motor runs abnormally.Something blocking the fan; motor cord disconnected or loose; fan motor; indoor control board.
41Indoor grounding protection.Indoor control board.
56Refrigerant leak detected by the refrigerant sensor. The indoor fan is forced to its highest speed, the outdoor unit stops, and the controls only respond to the clearing steps.Find and repair the leak (indoor unit or connecting pipe). Then clear it with the remote: press MODE once (1 beep), press the up/down swing button three times (3 beeps), press MODE once more (1 beep). Four beeps confirm it; otherwise repeat. After clearing, the indoor fan runs at maximum for 5 minutes, then the unit resumes the set mode. How to fix →
57Communication trouble between the refrigerant sensor and the indoor control board.Sensor-to-board connection loose; sensor wiring; indoor control board.
77Wi-Fi connection enabled.Cycle power off and on.

How to read the codes

Codes point to a circuit, not a part. Test before replacing boards or sensors. Inverter boards hold a dangerous charge after power-off; wait and verify DC bus voltage is gone before touching them. Refrigerant work requires EPA 608 certification.

Source: Friedrich Floating Air Single Zone R-454B Service Manual 96112001_00 (files.rheem.com), Indoor Unit Diagnostic Codes pp. 71-73. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.