Bryant 619RE Console and Cassette Error Codes

Applies to: Bryant 619RE Console and Cassette (floor console 619REQ009FBMA, 619REQ012FBMA; cassette 619REQ009CBMA, 619REQ012CBMA, 619REQ018CBMA). Operation and Timer lamps on the indoor unit's display panel.

Bryant ductless systems come from Carrier. The floor console (619R*F) and cassette (619R*C) service manuals print the same indoor error table and the same diagnosis pages, so one chart covers both. Other Bryant ductless lines have their own manuals.

CodeMeaningWhat to check
E0Indoor unit EEPROM error.The main chip gets no feedback from the EEPROM chip. Bryant lists installation mistake or a faulty PCB (indoor PCB for E0).
E1Communication malfunction between indoor and outdoor units.No feedback from the outdoor unit for 110 seconds, four times in a row. Power off and restart after 2 minutes. Measure Vs between S and L2 at the outdoor unit (red probe on S): it should fluctuate. Check the outdoor and indoor wiring, then the indoor and outdoor main PCBs. Bryant's remark: the reactor should read about zero ohms. How to fix →
E3Indoor fan speed out of control.The indoor fan stayed too slow (300 RPM) for a set time. Causes: wiring, fan assembly (blocked fan), fan motor, PCB. Restart after 2 minutes first.
E4Indoor room temperature sensor T1 open or shorted.Sampling voltage under 0.06 V or over 4.94 V. Check the sensor-to-PCB connection, then measure the sensor against Table 8. How to fix →
E5Evaporator coil temperature sensor T2 open or shorted.Sampling voltage under 0.06 V or over 4.94 V. Check the connection, then measure the sensor against Table 8. How to fix →
ECRefrigerant leakage detection.In the first 5 minutes after the compressor starts, the board compares the coil temperature T2 with its value at start-up (Tcool); three failures and the unit turns off. The printed trip value is garbled in the manual, so it isn't repeated here. Causes: T2 sensor, indoor PCB, or a system problem such as a leak or blockage. Restart after 2 minutes, check for cool air, check T2, then look for the leak or blockage and recharge. How to fix →
EEWater-level alarm malfunction.The sampling voltage isn't 5 V. Restart after 3 minutes; if it's still there, make sure the water-level switch is seated, then check the switch, the water pump and the indoor PCB. How to fix →
F0Current overload protection.Listed in Bryant's table; the manual has no diagnosis page for it.
F1Outdoor ambient temperature sensor T4 open or shorted.Sampling voltage under 0.06 V or over 4.94 V. Check the connection, then measure against Table 8. How to fix →
F2Condenser coil temperature sensor T3 open or shorted.Sampling voltage under 0.06 V or over 4.94 V. Check the connection, then measure against Table 8. How to fix →
F3Compressor discharge temperature sensor T5 open or shorted.Sampling voltage under 0.06 V or over 4.94 V. Check the connection, then measure against Table 9 (T5). How to fix →
F4Outdoor unit EEPROM error.The main chip gets no feedback from the EEPROM chip. Bryant lists installation mistake or a faulty PCB (outdoor PCB for F4).
F5Outdoor fan speed out of control.Listed in Bryant's table; the manual has no diagnosis page for it.
F6T2B sensor error.Listed in Bryant's table; no diagnosis page. How to fix →
F7Lifting-panel communication error.Listed in Bryant's table (both manuals print it); no diagnosis page.
F8Lifting-panel malfunction.Listed in Bryant's table; no diagnosis page.
F9Lifting-panel is not closed.Listed in Bryant's table; no diagnosis page.
P0IPM malfunction (or IGBT over-strong current protection).The IPM's signal to the compressor drive chip is abnormal. Check the wiring between the main PCB and compressor, then the IPM (replace the IPM board or main PCB). Causes also include the outdoor fan assembly and the compressor. How to fix →
P1Over voltage or too low voltage protection.Check the power supply, then the connections and wires. Bryant's remark: DC voltage between P and N should be about 310 V; otherwise replace the IPM board. How to fix →
P2High temperature protection of the compressor top.The sampling voltage isn't 5 V. Check indoor and outdoor airflow (clear the inlets, outlets and coils), restart after 3 minutes, then check the overload protector (OLP) connection and resistance; replace the OLP or the outdoor control PCB. How to fix →
P3Outdoor low temperature protection.Listed in Bryant's table; no diagnosis page.
P4Inverter compressor drive error.The drive detection circuit (communication, voltage and compressor speed signals) found a fault. Check the wiring between the main PCB and compressor, then the IPM; causes also include the outdoor fan assembly, compressor and outdoor PCB. How to fix →
P5Mode conflict.Listed in Bryant's table; no diagnosis page.
P6Compressor low-pressure protection.Listed in Bryant's table; no diagnosis page. How to fix →
P7Outdoor IGBT temperature sensor error.Listed in Bryant's table; no diagnosis page. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing boards or sensors. Inverter boards hold a dangerous charge after power-off; wait and verify DC bus voltage is gone before touching them. Refrigerant work requires EPA 608 certification.

Source: Bryant 619R*F Floor Console Ductless Service Manual SM619RF-01, Table 6 p. 15 and diagnosis pp. 14-29; same table and pages in the 619R*C Cassette Service Manual SM619RC-01 (Table 7 p. 16). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.