Home / Charts / ACiQ mini-split codes

ACiQ Single-zone wall mount, R-454B Error Codes

Applies to: ACiQ Single-zone wall mount, R-454B (ACiQ-xxWS / -xxW-BL with -xxZS / -xxZPL outdoor). Code shown on the indoor unit display.

Older ACiQ (R-410A) units may show shorter codes. Refrigerant sensor codes (EHC/FHA) only appear on models with a leak sensor.

CodeMeaningWhat to check
EH 00Indoor EEPROM malfunction.Indoor control board.
EH 0AIndoor EEPROM parameter error.Indoor control board.
EL 01Indoor/outdoor communication error.Interconnect wiring, terminal screws, power at the outdoor unit. How to fix →
EH 02Zero-crossing signal detection error.Supply power and indoor board.
EH 03Indoor fan speed out of control.Indoor fan motor, blower wheel binding, connector.
EH 31Indoor DC fan motor voltage too low (units with a DC fan driver board).
EH 32Indoor DC fan motor voltage too high (units with a DC fan driver board).
EH 0bIndoor main board and display board communication error.Display board cable and connectors.
EH 60Indoor room temperature sensor (T1) error.Measure the sensor; check the connector. How to fix →
EH 61Evaporator coil temperature sensor (T2) open or shorted.Measure the sensor; check the connector. How to fix →
PH 0cIndoor humidity sensor malfunction.
EC 07Outdoor fan speed out of control.Outdoor fan motor, obstruction, connector.
EC 51Outdoor EEPROM parameter error.Outdoor control board.
EC 52Outdoor coil temperature sensor (T3) error.Measure the sensor; check the connector. How to fix →
EC 53Outdoor ambient temperature sensor (T4) error.Measure the sensor; check the connector. How to fix →
EC 54Compressor discharge temperature sensor (TP) error.Measure the sensor; check the connector. How to fix →
EC 55Outdoor IPM module temperature sensor (TH) error. How to fix →
EC 56Evaporator coil outlet sensor (T2B) open or shorted (multi-zone). How to fix →
EL 0CSystem low on refrigerant.Leak search, starting at the flare connections. How to fix →
EH C1Refrigerant sensor detects a leak.Ventilate, leak search; follow the A2L leak procedure.
EH C2Refrigerant sensor out of range and a leak is detected.
EH C3Refrigerant sensor out of range.
EC C1Another indoor unit's refrigerant sensor detected a leak (multi-zone).
FH A2Communication error between the indoor unit and the refrigerant sensor.Sensor cable and connector.
FH A3Refrigerant sensor internal error.
FH A4Refrigerant sensor permanent error.
FH A5Refrigerant sensor self-check failed.
FH A6Refrigerant sensor low voltage error.
FH CCRefrigerant sensor error.
FH 0PWireless module self-test failure.
FL 09Indoor and outdoor units mismatched.Confirm the indoor and outdoor model numbers are an approved match.
PC 00Outdoor IPM module protection.Inverter board and compressor. How to fix →
PC 02Compressor top (or IPM) temperature protection.Outdoor airflow, dirty coil, charge. How to fix →
PC 03Pressure protection (low or high pressure).Charge, airflow, closed service valve, restriction.
PC 06Compressor discharge temperature protection.Low charge or restriction is the usual cause. How to fix →
PC 08Outdoor current protection.
PC 0ACondenser high temperature protection.Dirty outdoor coil, blocked airflow, outdoor fan.
PC 0FPFC module protection.
PC 0LOutdoor low temperature protection (outdoor temperature below the operating range).
PC 10Outdoor low AC voltage protection.Supply voltage under load. How to fix →
PC 11Outdoor board DC bus high voltage protection. How to fix →
PC 12Outdoor board DC bus low voltage protection. How to fix →
PC 30System overpressure protection.
PC 31System pressure too low protection. How to fix →
PC 40Communication error between the outdoor main chip and the compressor drive chip. How to fix →
PC 41Compressor current sampling circuit failure.
PC 42Compressor start failure.
PC 43Compressor lack-of-phase protection.Compressor U/V/W wiring and terminals.
PC 44Outdoor zero-speed protection.
PC 45Outdoor IR chip drive failure. How to fix →
PC 46Compressor speed out of control.
PC 49Compressor overcurrent failure. How to fix →
PH 09Anti-cold-air in heating mode (normal at heating start-up; not a fault).
PH 90Evaporator high temperature protection.Dirty filter or indoor coil, indoor fan speed.
PH 91Evaporator low temperature protection.Dirty filter, low indoor airflow, low charge.
- -Indoor units calling for conflicting modes (multi-zone). Not a failure.

How to read the codes

Codes point to a circuit, not a part. Test before replacing boards or sensors. Inverter boards hold a dangerous charge after power-off; wait and verify DC bus voltage is gone before touching them. Refrigerant work requires EPA 608 certification.

Source: ACiQ Single-Zone Service Manual (6K–24K, R-454B), Error code of engineer mode, pp. TS 11–12. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.