Durastar Multi-zone Error Codes

Applies to: Durastar Multi-zone (outdoor DRA2U18M1A, DRA3U28M1A, DRA4U36M1A, DRA5U48M1A; indoor DRAW, DRAC, DRAD, DRAF and DRAS F1A heads). Code on the indoor unit display (with operation and timer lamps) or on the outdoor unit's display.

Durastar is a Ferguson brand. The single-zone units have their own chart.

CodeMeaningWhat to check
dF (indoor)Defrost.Normal operation.
cF (indoor)Warming in heating mode (anti-cold air).Normal operation.
SC (indoor)Self clean.Normal operation.
CL (indoor)Clean filter.Clean the filter.
nF (indoor)Replace filter.Replace the filter.
FP (indoor)Heating with room temperature under 8°C (46°F).Freeze protection mode; normal.
FC (indoor)Forced cooling.Service mode.
AP (indoor)AP mode of Wi-Fi connection.Wi-Fi setup mode.
CP (indoor)Remote switched off.Remote shutdown input is active.
E0 (indoor)Indoor unit EEPROM parameter error (operation lamp 1 flash, timer off).Indoor PCB.
E1 (indoor)Indoor/outdoor units communication error (2 flashes, timer off).Interconnect wiring; indoor PCB, outdoor PCB, reactor, IPM module board. How to fix →
E2 (indoor)Zero-crossing signal detection error, some models (3 flashes, timer off).Indoor PCB and supply power (TS03).
E3 (indoor)Indoor fan speed outside the normal range (4 flashes, timer off).Indoor fan motor; indoor PCB.
E4 (indoor)Indoor room temperature sensor T1 open or shorted (5 flashes, timer off).T1 sensor; indoor PCB. How to fix →
E5 (indoor)Evaporator coil inlet temperature sensor T2 open or shorted (6 flashes, timer off).T2 sensor; indoor PCB. How to fix →
EE (indoor)Water-level alarm, some models (8 flashes, timer off).Water-level switch, water (condensate) pump, indoor PCB.
F0 (indoor)Current overload protection (1 flash, timer on).Outdoor PCB, outdoor fan motor, reactor, compressor, IPM module board, bridge rectifier, refrigerant charge. How to fix →
F1 (indoor)Outdoor room temperature sensor T4 open or shorted (2 flashes, timer on).T4 sensor; outdoor PCB. How to fix →
F2 (indoor)Condenser coil temperature sensor T3 open or shorted (3 flashes, timer on).T3 sensor; outdoor PCB. How to fix →
F3 (indoor)Compressor discharge temperature sensor TP open or shorted (4 flashes, timer on).TP sensor; outdoor PCB. How to fix →
F4 (indoor)Outdoor unit EEPROM parameter error (5 flashes, timer on).Outdoor PCB.
F5 (indoor)Outdoor fan speed outside the normal range, some models (6 flashes, timer on).Outdoor fan motor; outdoor PCB.
F6 (indoor)Evaporator coil outlet temperature sensor T2B open or shorted (7 flashes, timer on).T2B sensor; outdoor PCB. How to fix →
fa (indoor)Communication error between the indoor unit's two chips, some models (11 flashes, timer on).Indoor PCB (TS23).
P0 (indoor)IPM malfunction or IGBT over-strong current protection (1 flash, timer flashing).Outdoor PCB, outdoor fan motor, TP sensor, reactor, compressor, IPM module board, bridge rectifier. How to fix →
P1 (indoor)Over voltage or over low voltage protection (2 flashes, timer flashing).Supply voltage; outdoor PCB, reactor, IPM module board, bridge rectifier. How to fix →
P2 (indoor)High temperature protection of the IPM module, high pressure protection, or compressor top temperature protection (3 flashes, timer flashing).Outdoor airflow and charge; see the outdoor code for which one (TS11). How to fix →
P3 (indoor)Low ambient temperature protection (4 flashes, timer flashing).Not a part failure.
P4 (indoor)Inverter compressor drive error (5 flashes, timer flashing).Outdoor PCB, outdoor fan motor, TP sensor, reactor, compressor, IPM module board, bridge rectifier. How to fix →
-- / P5 (indoor)Indoor units mode conflict (6 flashes, timer flashing).Not a part failure: indoor units are calling for opposite modes.
P6 (indoor)Low pressure protection (7 flashes, timer flashing).Low pressure switch, refrigerant charge, outdoor PCB (TS13).
P7 (indoor)Outdoor IGBT sensor fault, some models (8 flashes, timer flashing).Outdoor PCB (TS05). How to fix →
RO (outdoor)Oil return.Normal operation.
PH (outdoor)Compressor pre-heating.Normal operation.
LC (outdoor)Low ambient cooling.Normal operation.
E0 (outdoor)Outdoor EEPROM malfunction.Outdoor PCB.
E2 (outdoor)Indoor/outdoor units communication error.Interconnect wiring; indoor PCB, outdoor PCB, reactor, IPM module board. How to fix →
E3 (outdoor)Communication error between the outdoor main PCB and the IPM board.Outdoor PCB, IPM module board, electric control box wiring. How to fix →
E4 (outdoor)Outdoor unit temperature sensor open or shorted.T3, T4 and TP sensors; outdoor PCB. How to fix →
E5 (outdoor)Over voltage or over low voltage protection.Supply voltage; outdoor PCB, reactor, IPM module board, bridge rectifier. How to fix →
E6 (outdoor)PFC module protection.Outdoor PCB, reactor or inductance, IPM module board. How to fix →
E8 (outdoor)Outdoor fan speed outside the normal range.Outdoor fan motor; outdoor PCB.
F1 (outdoor)Indoor unit A coil outlet temperature sensor (or its connector) defective.T2B sensor for zone A; outdoor PCB. How to fix →
F2 (outdoor)Indoor unit B coil outlet temperature sensor (or its connector) defective.T2B sensor for zone B; outdoor PCB. How to fix →
F3 (outdoor)Indoor unit C coil outlet temperature sensor (or its connector) defective.T2B sensor for zone C; outdoor PCB. How to fix →
F4 (outdoor)Indoor unit D coil outlet temperature sensor (or its connector) defective.T2B sensor for zone D; outdoor PCB. How to fix →
F5 (outdoor)Indoor unit E coil outlet temperature sensor (or its connector) defective.T2B sensor for zone E; outdoor PCB. How to fix →
F6 (outdoor)Indoor unit F coil outlet temperature sensor (or its connector) defective.T2B sensor for zone F; outdoor PCB. How to fix →
P0 (outdoor)Top temperature protection of the compressor.Charge, airflow and the compressor top temperature switch (TS11).
P1 (outdoor)High pressure protection.High pressure switch, condenser airflow, outdoor PCB (TS28).
P2 (outdoor)Low pressure protection.Low pressure switch, refrigerant charge, outdoor PCB (TS13).
P3 (outdoor)Current overload protection.Outdoor PCB, outdoor fan motor, reactor, compressor, IPM module board, bridge rectifier, refrigerant charge. How to fix →
P4 (outdoor)Compressor discharge temperature protection.TP sensor, refrigerant charge, outdoor PCB. How to fix →
P5 (outdoor)High temperature protection of the condenser.Outdoor fan motor, T3 sensor, refrigerant charge, outdoor PCB. How to fix →
P6 (outdoor)IPM module protection.Outdoor PCB, outdoor fan motor, TP sensor, reactor, compressor, IPM module board, bridge rectifier. How to fix →
LP (outdoor)Low ambient temperature protection.Not a part failure.

How to read the codes

Codes point to a circuit, not a part. Test before replacing boards or sensors. Inverter boards hold a dangerous charge after power-off; wait and verify DC bus voltage is gone before touching them. Refrigerant work requires EPA 608 certification.

Source: Durastar Multi Zone Service Manual, Error Display (Indoor Unit) pp. 125-126, Error Display (Outdoor Unit) p. 127, Quick Maintenance by Error Code p. 142. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.