Durastar Single-zone wall mount Error Codes
Durastar is a Ferguson brand. Later generations (F1B, and the R-454B F2A/S2A units) have their own installation manuals with error code pages; check the code against the manual for your model.
| Code | Meaning | What to check |
|---|---|---|
| E0 | Indoor unit EEPROM parameter error (operation lamp 1 flash, timer off). | Indoor PCB. |
| E1 | Indoor/outdoor unit communication error (2 flashes, timer off). | Interconnect wiring first, then the indoor PCB, outdoor PCB and reactor. How to fix → |
| E3 | Indoor fan speed outside the normal range (4 flashes, timer off). | Indoor fan motor and indoor PCB. |
| E4 | Indoor room temperature sensor T1 open or shorted (5 flashes, timer off). | Measure the sensor; indoor PCB. How to fix → |
| E5 | Evaporator coil temperature sensor T2 open or shorted (6 flashes, timer off). | Measure the sensor; indoor PCB. How to fix → |
| EC | Refrigerant leak detected (7 flashes, timer off). | Leak check the system; T2 sensor and other temperature sensors; indoor PCB. How to fix → |
| F0 | Overload current protection (1 flash, timer on). | Outdoor PCB, compressor; Durastar's table also lists the outdoor unit. |
| F1 | Outdoor ambient temperature sensor T4 open or shorted (2 flashes, timer on). | Measure the sensor; outdoor PCB. How to fix → |
| F2 | Condenser coil temperature sensor T3 open or shorted (3 flashes, timer on). | Measure the sensor; outdoor PCB. How to fix → |
| F3 | Compressor discharge temperature sensor TP open or shorted (4 flashes, timer on). | Measure the sensor; outdoor PCB. How to fix → |
| F4 | Outdoor unit EEPROM parameter error (5 flashes, timer on). | Outdoor PCB. |
| F5 | Outdoor fan speed outside the normal range (6 flashes, timer on). | Outdoor fan motor and outdoor PCB. |
| P0 | IPM malfunction or IGBT over-strong current protection (1 flash, timer flashing). | IPM board, compressor, outdoor PCB. How to fix → |
| P1 | Over voltage or over low voltage protection (2 flashes, timer flashing). | Supply voltage; outdoor PCB, reactor, IPM board. How to fix → |
| P2 | High temperature protection of IPM module (3 flashes, timer flashing). | Outdoor PCB; outdoor airflow. How to fix → |
| P3 | Outdoor ambient temperature too low (4 flashes, timer flashing). | Not a part failure. In heating, shown when it's below −25°C (−13°F) outdoors for 1 hour; the unit returns to work when it's above −22°C (about −8°F) for 10 minutes and the compressor has been stopped 1 hour, or above −5°C (23°F) for 10 minutes. |
| P4 | Inverter compressor drive error (5 flashes, timer flashing). | Compressor, IPM board, outdoor PCB. Check compressor winding resistance (see How to read). How to fix → |
| P5 | Indoor units mode conflict (6 flashes, timer flashing). Multi-zone only. | Not a part failure: indoor units are calling for opposite modes. |
| P6 | Low pressure or high pressure protection (36k model only), or high temperature protection of the IPM module (under 36k) (7 flashes, timer flashing). | Durastar's table lists the outdoor PCB, indoor and outdoor fan motors, refrigerant charge, compressor, and the low and high pressure protectors. How to fix → |
How to read the codes
- Count the operation lamp flashes and note whether the timer lamp is off, on or flashing: E codes have the timer lamp off, F codes on, P codes flashing.
- A garbled or unlisted code can be a temperature reading; make sure it isn't. If the unit doesn't respond to the remote, Durastar points to the indoor PCB; if it responds, to the display board.
- The 'check' column follows Durastar's quick maintenance table, which lists the parts to replace for each code. Test them before replacing anything.
- Compressor winding resistance, all three pairs (blue-red, blue-black, red-blue): ASN98D22UFZ 1.57 Ω, ASM135D23UFZ 1.75 Ω, ATF235D22UMT and ATF250D22UMT 0.75 Ω.
Source: Durastar Single Zone Wall Mounted Mini Split Service Manual (DRA1U..S1A / DRAW..F1A), Error Display p. 72, Quick Maintenance by Error Code p. 80, Compressor checking p. 81. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- Mini-split communication error troubleshooting
- Mini-split flare connections (the usual leak point)
- Ductless mini-split maintenance
- Look up any mini-split code
Other brands
- Daikin FTX / FVXS / FDMQ with RXL outdoor (19 Series)
- Fujitsu Halcyon / Airstage splits (indicator lamp codes)
- MRCOOL DIY E Star 4th Generation
- Mitsubishi Electric MSZ-GL / MSY-GL (failure mode recall)
- Senville AURA / LETO
- LG Single / multi-split wall units (CH codes)
- Gree Livo / All-Match with LIV outdoor (R-32)
- Pioneer Diamante / Quantum (WYT-17, WYT-20, WYT-24, WYT-25, WYT-FA)
- Lennox Mini-splits: MLB / MPC / 3PC outdoor with M22A, M33C, MWMC, MCFA/B, MFMA indoor
- ACiQ Single-zone wall mount, R-454B (ACiQ-xxWS / -xxW-BL with -xxZS / -xxZPL outdoor)
- Midea High wall ductless DLFSHB (DLFSHBH09XAK, -12XAJ, -12XAK, -18XAK, -24XAK)
- Friedrich Floating Air Pro R-454B (single zone; systems FPHW093B, FPHW123B, FPHW183B, FPHW243B; indoor FAHFW09A3A, FAHFW12A3A, FAHFW18A3A, FAHFW24A3A; outdoor FPHSR09A3B, FPHSR12A3B, FPHSR18A3B, FPHSR24A3B)
- Bryant 619PHA high wall ductless (619PHAQ09XA3, 619PHAQ12XA3, 619PHAQ18XA3, 619PHAQ24XA3)
- Bryant 619RE Console and Cassette (floor console 619REQ009FBMA, 619REQ012FBMA; cassette 619REQ009CBMA, 619REQ012CBMA, 619REQ018CBMA)
- Bryant 619RE Console and Cassette (floor console 619REQ009FBMA, 619REQ012FBMA; cassette 619REQ009CBMA, 619REQ012CBMA, 619REQ018CBMA)
- Bryant 619RE Console/Cassette/Ducted (floor console 619REQ009FBMA, 619REQ012FBMA; cassette 619REQ009CBMA, 619REQ012CBMA, 619REQ018CBMA; ducted 619REQ009DBMA, 619REQ012DBMA, 619REQ018DBMA, 619REQ024DBMA, 619REQ036DBMA, 619REQ048DBMA)
- Bryant 619AHB/619PHB High Wall (619PHBQ09XA3, 619PHBQ12XA3, 619PHBQ18XA3, 619AHBQ06XA3, 619AHBQ09XA3, 619AHBQ12XA3, 619AHBQ12XA1, 619AHBQ18XA3, 619AHBQ24XA3, 619AHBQ30XA3, 619AHBQ36XA3)
- Durastar Multi-zone (outdoor DRA2U18M1A, DRA3U28M1A, DRA4U36M1A, DRA5U48M1A; indoor DRAW, DRAC, DRAD, DRAF and DRAS F1A heads)
- Friedrich Floating Air R-454B (single zone; systems FPHW091C, FPHW121C; indoor FAHSW09A1C, FAHSW12A1C, FAHFW09A1C, FAHFW09A3D, FAHFW12A3D, FAHFW18A3D, FAHFW24A3D; outdoor FPHSR09A1C, FPHSR12A1C, FPHSR09A3D, FPHSR12A3D, FPHSR18A3D, FPHSR24A3D)
- Klimaire KSIE inverter wall mount (2014–2016 models, e.g. KSIE012-H120-SW)