Durastar Single-zone wall mount Error Codes

Applies to: Durastar Single-zone wall mount (indoor DRAW09F1A, DRAW12F1A, DRAW18F1A, DRAW24F1A; outdoor DRA1U09S1A, DRA1U12S1A, DRA1U18S1A, DRA1U24S1A). Code shown on the indoor unit display, with the operation lamp flash count and timer lamp state.

Durastar is a Ferguson brand. Later generations (F1B, and the R-454B F2A/S2A units) have their own installation manuals with error code pages; check the code against the manual for your model.

CodeMeaningWhat to check
E0Indoor unit EEPROM parameter error (operation lamp 1 flash, timer off).Indoor PCB.
E1Indoor/outdoor unit communication error (2 flashes, timer off).Interconnect wiring first, then the indoor PCB, outdoor PCB and reactor. How to fix →
E3Indoor fan speed outside the normal range (4 flashes, timer off).Indoor fan motor and indoor PCB.
E4Indoor room temperature sensor T1 open or shorted (5 flashes, timer off).Measure the sensor; indoor PCB. How to fix →
E5Evaporator coil temperature sensor T2 open or shorted (6 flashes, timer off).Measure the sensor; indoor PCB. How to fix →
ECRefrigerant leak detected (7 flashes, timer off).Leak check the system; T2 sensor and other temperature sensors; indoor PCB. How to fix →
F0Overload current protection (1 flash, timer on).Outdoor PCB, compressor; Durastar's table also lists the outdoor unit.
F1Outdoor ambient temperature sensor T4 open or shorted (2 flashes, timer on).Measure the sensor; outdoor PCB. How to fix →
F2Condenser coil temperature sensor T3 open or shorted (3 flashes, timer on).Measure the sensor; outdoor PCB. How to fix →
F3Compressor discharge temperature sensor TP open or shorted (4 flashes, timer on).Measure the sensor; outdoor PCB. How to fix →
F4Outdoor unit EEPROM parameter error (5 flashes, timer on).Outdoor PCB.
F5Outdoor fan speed outside the normal range (6 flashes, timer on).Outdoor fan motor and outdoor PCB.
P0IPM malfunction or IGBT over-strong current protection (1 flash, timer flashing).IPM board, compressor, outdoor PCB. How to fix →
P1Over voltage or over low voltage protection (2 flashes, timer flashing).Supply voltage; outdoor PCB, reactor, IPM board. How to fix →
P2High temperature protection of IPM module (3 flashes, timer flashing).Outdoor PCB; outdoor airflow. How to fix →
P3Outdoor ambient temperature too low (4 flashes, timer flashing).Not a part failure. In heating, shown when it's below −25°C (−13°F) outdoors for 1 hour; the unit returns to work when it's above −22°C (about −8°F) for 10 minutes and the compressor has been stopped 1 hour, or above −5°C (23°F) for 10 minutes.
P4Inverter compressor drive error (5 flashes, timer flashing).Compressor, IPM board, outdoor PCB. Check compressor winding resistance (see How to read). How to fix →
P5Indoor units mode conflict (6 flashes, timer flashing). Multi-zone only.Not a part failure: indoor units are calling for opposite modes.
P6Low pressure or high pressure protection (36k model only), or high temperature protection of the IPM module (under 36k) (7 flashes, timer flashing).Durastar's table lists the outdoor PCB, indoor and outdoor fan motors, refrigerant charge, compressor, and the low and high pressure protectors. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing boards or sensors. Inverter boards hold a dangerous charge after power-off; wait and verify DC bus voltage is gone before touching them. Refrigerant work requires EPA 608 certification.

Source: Durastar Single Zone Wall Mounted Mini Split Service Manual (DRA1U..S1A / DRAW..F1A), Error Display p. 72, Quick Maintenance by Error Code p. 80, Compressor checking p. 81. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.