Bryant 619PHA high wall ductless Error Codes
Bryant ductless systems come from Carrier. Other Bryant and Carrier ductless lines (619PHB, 619AHB, 619PB/538PR, 619RD, 619RC and others) have their own service manuals on Carrier's document site; check the code against the manual for your model.
| Code | Meaning | What to check |
|---|---|---|
| E0 / EA | Indoor unit EEPROM parameter error. | Indoor PCB. |
| E1 | Indoor/outdoor unit communication error. | Interconnect wiring first, then the indoor PCB, outdoor PCB and reactor. How to fix → |
| E2 | Zero crossing detection error. | Supply power and the indoor PCB (manual p. 30). |
| E3 | Indoor fan speed outside the normal range. | Indoor fan motor and indoor PCB. |
| E4 | Indoor room temperature sensor T1 open or shorted. | Measure the sensor; indoor PCB. How to fix → |
| E5 | Evaporator coil temperature sensor T2 open or shorted. | Measure the sensor; indoor PCB. How to fix → |
| EB | Communication error between the indoor PCB and display board. | Indoor PCB; display board and its cable (Bryant's table leaves the display board cell blank for this code). |
| EF | Occupancy sensor module error. | Occupancy sensor. How to fix → |
| F0 | Overload current protection. | Outdoor PCB, compressor; Bryant's table also lists the outdoor unit. |
| F1 | Outdoor ambient temperature sensor T4 open or shorted. | Measure the sensor; outdoor PCB. How to fix → |
| F2 | Condenser coil temperature sensor T3 open or shorted. | Measure the sensor; outdoor PCB. How to fix → |
| F3 | Compressor discharge temperature sensor TP open or shorted. | Measure the sensor; outdoor PCB. How to fix → |
| F4 | Outdoor unit EEPROM parameter error. | Outdoor PCB. |
| F5 | Outdoor fan speed outside the normal range. | Outdoor fan motor and outdoor PCB. |
| P0 | IPM malfunction or IGBT over-strong current protection. | IPM board, compressor, outdoor PCB. How to fix → |
| P1 | Over voltage or over low voltage protection. | Supply voltage; outdoor PCB, reactor, IPM board. How to fix → |
| P2 | High temperature protection of the IPM module. | Outdoor PCB; outdoor airflow. How to fix → |
| P3 | Outdoor ambient temperature too low. | Not a part failure; the manual gives no solution page for it. |
| P4 | Inverter compressor drive error. | Compressor, IPM board, outdoor PCB. How to fix → |
How to read the codes
- The indicator light flashes a series, the timer display may turn on or flash, and the code shows on the display.
- A garbled or unlisted code can be a temperature reading; make sure it isn't. If the display works but the unit ignores the remote, Bryant points to the indoor PCB. If there's no display after pressing LED and the unit responds, it points to the display board.
- The 'check' column follows Bryant's quick maintenance tables (Tables 15 and 16), which list the parts to replace for each code. Test them before replacing anything; the manual's troubleshooting pages give the tests.
Source: Bryant 619PHA High Wall Ductless System Service Manual SM619PHA-03, Table 10 Error Codes p. 19, Tables 15-16 Quick Maintenance by Error Code p. 24. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- Mini-split communication error troubleshooting
- Mini-split flare connections (the usual leak point)
- Ductless mini-split maintenance
- Look up any mini-split code
Other brands
- Daikin FTX / FVXS / FDMQ with RXL outdoor (19 Series)
- Fujitsu Halcyon / Airstage splits (indicator lamp codes)
- MRCOOL DIY E Star 4th Generation
- Mitsubishi Electric MSZ-GL / MSY-GL (failure mode recall)
- Senville AURA / LETO
- LG Single / multi-split wall units (CH codes)
- Gree Livo / All-Match with LIV outdoor (R-32)
- Pioneer Diamante / Quantum (WYT-17, WYT-20, WYT-24, WYT-25, WYT-FA)
- Lennox Mini-splits: MLB / MPC / 3PC outdoor with M22A, M33C, MWMC, MCFA/B, MFMA indoor
- ACiQ Single-zone wall mount, R-454B (ACiQ-xxWS / -xxW-BL with -xxZS / -xxZPL outdoor)
- Midea High wall ductless DLFSHB (DLFSHBH09XAK, -12XAJ, -12XAK, -18XAK, -24XAK)
- Durastar Single-zone wall mount (indoor DRAW09F1A, DRAW12F1A, DRAW18F1A, DRAW24F1A; outdoor DRA1U09S1A, DRA1U12S1A, DRA1U18S1A, DRA1U24S1A)
- Friedrich Floating Air Pro R-454B (single zone; systems FPHW093B, FPHW123B, FPHW183B, FPHW243B; indoor FAHFW09A3A, FAHFW12A3A, FAHFW18A3A, FAHFW24A3A; outdoor FPHSR09A3B, FPHSR12A3B, FPHSR18A3B, FPHSR24A3B)
- Bryant 619RE Console and Cassette (floor console 619REQ009FBMA, 619REQ012FBMA; cassette 619REQ009CBMA, 619REQ012CBMA, 619REQ018CBMA)
- Bryant 619RE Console and Cassette (floor console 619REQ009FBMA, 619REQ012FBMA; cassette 619REQ009CBMA, 619REQ012CBMA, 619REQ018CBMA)
- Bryant 619RE Console/Cassette/Ducted (floor console 619REQ009FBMA, 619REQ012FBMA; cassette 619REQ009CBMA, 619REQ012CBMA, 619REQ018CBMA; ducted 619REQ009DBMA, 619REQ012DBMA, 619REQ018DBMA, 619REQ024DBMA, 619REQ036DBMA, 619REQ048DBMA)
- Bryant 619AHB/619PHB High Wall (619PHBQ09XA3, 619PHBQ12XA3, 619PHBQ18XA3, 619AHBQ06XA3, 619AHBQ09XA3, 619AHBQ12XA3, 619AHBQ12XA1, 619AHBQ18XA3, 619AHBQ24XA3, 619AHBQ30XA3, 619AHBQ36XA3)
- Durastar Multi-zone (outdoor DRA2U18M1A, DRA3U28M1A, DRA4U36M1A, DRA5U48M1A; indoor DRAW, DRAC, DRAD, DRAF and DRAS F1A heads)
- Friedrich Floating Air R-454B (single zone; systems FPHW091C, FPHW121C; indoor FAHSW09A1C, FAHSW12A1C, FAHFW09A1C, FAHFW09A3D, FAHFW12A3D, FAHFW18A3D, FAHFW24A3D; outdoor FPHSR09A1C, FPHSR12A1C, FPHSR09A3D, FPHSR12A3D, FPHSR18A3D, FPHSR24A3D)
- Klimaire KSIE inverter wall mount (2014–2016 models, e.g. KSIE012-H120-SW)
Did you find your code?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
HVAC Cheat Sheet · Free PT charts, code lookups and calculators for techs at hvaccheatsheet.com