Home / Charts / Midea mini-split codes

Midea High wall ductless DLFSHB Error Codes

Applies to: Midea High wall ductless DLFSHB (DLFSHBH09XAK, -12XAJ, -12XAK, -18XAK, -24XAK). Code shown on the indoor unit display.

Many Midea-built brands use this same code set. Older Midea units show short codes (for example E1 instead of EL 01).

CodeMeaningWhat to check
EH 00 / EH 0AIndoor unit EEPROM parameter error.Indoor control board.
EL 01Indoor/outdoor unit communication error.Interconnect wiring, terminal screws, power at the outdoor unit. How to fix →
EH 02Zero-crossing signal detection error.Supply power and indoor board.
EH 03Indoor fan speed outside the normal range.Indoor fan motor, blower wheel binding, connector.
EH 30Low voltage protection of the indoor external fan.
EH 31Over voltage protection of the indoor external fan.
EH 0bIndoor PCB / display board communication error.Display board cable and connectors.
EH 60Indoor room temperature sensor T1 open or shorted.Measure the sensor; check the connector. How to fix →
EH 61Evaporator coil temperature sensor T2 open or shorted.Measure the sensor; check the connector. How to fix →
EC 07Outdoor fan speed outside the normal range.Outdoor fan motor, obstruction, connector.
EC 51Outdoor unit EEPROM parameter error.Outdoor control board.
EC 52Condenser coil temperature sensor T3 open or shorted.Measure the sensor; check the connector. How to fix →
EC 53Outdoor ambient temperature sensor T4 open or shorted.Measure the sensor; check the connector. How to fix →
EC 54Compressor discharge temperature sensor TP open or shorted.Measure the sensor; check the connector. How to fix →
EC 56Evaporator coil outlet sensor T2B open or shorted. How to fix →
EL 0CRefrigerant leak detected.Leak search, starting at the flare connections. How to fix →
PC 00IPM malfunction or IGBT over-strong current protection.Inverter board and compressor. How to fix →
PC 02Compressor top high temperature protection (OLP).Charge, outdoor airflow, dirty coil.
PC 03Pressure protection.Charge, airflow, closed service valve, restriction.
PC 06Compressor discharge temperature protection.Low charge or restriction is the usual cause. How to fix →
PC 08Outdoor current protection.
PC 0ACondenser high temperature protection.Dirty outdoor coil, blocked airflow, outdoor fan.
PC 0FPFC module malfunction.
PC 0LOutdoor ambient temperature too low (below the operating range).
PC 10Low voltage protection.Supply voltage under load. How to fix →
PC 11Over voltage protection.Supply voltage. How to fix →
PC 12DC voltage protection. How to fix →
PC 40Communication error between the outdoor main chip and the compressor drive chip. How to fix →
PC 41Current input detection protection.
PC 42Compressor start error.
PC 43Lack of phase protection.Compressor U/V/W wiring and terminals.
PC 44No-speed protection.
PC 45341 PWM error.
PC 46Compressor speed malfunction.
PC 49Compressor overcurrent protection. How to fix →
PH 09Anti-cold-air in heating mode (normal at heating start-up; not a fault).
PH 90Evaporator coil temperature too high protection.Dirty filter or indoor coil, indoor fan speed.
PH 91Evaporator coil temperature too low protection.Dirty filter, low indoor airflow, low charge.
- -Indoor units calling for conflicting modes (multi-zone). Not a failure.

How to read the codes

Codes point to a circuit, not a part. Test before replacing boards or sensors. Inverter boards hold a dangerous charge after power-off; wait and verify DC bus voltage is gone before touching them. Refrigerant work requires EPA 608 certification.

Source: Midea DLFSHB High Wall Ductless Service Manual, Table 9 Error Codes, p. 17 (copy on ManualsLib). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.