Friedrich Floating Air Pro R-454B Error Codes
Friedrich is a Rheem company. Other Floating Air lines (Select, Premier, Pro X, older R-410A units) have their own service manuals; check the code against the manual for your model.
| Code | Meaning | What to check |
|---|---|---|
| EA | Communication between the display board and control board interrupted. | Loose connection between display and control board; indoor control board; display board wiring. |
| 0 | Normal. | |
| 1 | Outdoor coil temperature sensor failure. | Sensor connector loose; outdoor coil sensor; indoor control board. How to fix → |
| 2 | Compressor exhaust (discharge) temperature sensor failure. | Sensor connector loose; discharge sensor; outdoor control board. How to fix → |
| 5 | IPM module protection. | IPM board; outdoor fan broken, failed or blocked; dirty condenser. How to fix → |
| 6 | AC voltage higher or lower protection. | Supply voltage; the unit's internal supply voltage. How to fix → |
| 7 | Communication failure between the indoor and outdoor unit. | Communication cable loose, miswired or failed; filter board to terminal and to outdoor board connections; indoor control board, PFC board, power board, outdoor control board. How to fix → |
| 8 | Current overload protection. | Fan motor running abnormally; dirty condenser or evaporator; blocked air inlet or outlet. |
| 9 | Maximum current protection. | Outdoor control board or drive board short circuited; other components shorted. How to fix → |
| 10 | Communication trouble between the outdoor unit and the driver. | Loose connection wires; outdoor board or drive board. How to fix → |
| 11 | Outdoor EEPROM fault. | EEPROM chip loose, inserted incorrectly or failed. |
| 12 | Outdoor ambient temperature too low or too high protection. | Outdoor temperature outside the operating range; not a part failure. |
| 13 | Compressor exhaust (discharge) temperature too high protection. | Discharge temperature sensor; low refrigerant charge. How to fix → |
| 14 | Outdoor ambient temperature sensor failure. | Sensor connector loose; ambient sensor; outdoor control board. How to fix → |
| 15 | Compressor shell temperature too high protection. | Friedrich lists the compressor exhaust temperature sensor connector and a low refrigerant charge. How to fix → |
| 16 | Anti-freeze protection in cooling, or overload protection in heating. | Indoor coil sensor connector or sensor; indoor control board; refrigerant system problem. How to fix → |
| 17 | PFC protection. | PFC; outdoor drive board. How to fix → |
| 18 | DC compressor start failure. | Outdoor drive board; compressor. How to fix → |
| 19 | Compressor drive failure. | Outdoor drive board; compressor; outdoor control board. How to fix → |
| 20 | Outdoor fan motor locked rotor protection. | Fan motor connection loose; something blocking the fan; fan motor; outdoor control board. How to fix → |
| 21 | Outdoor coil anti-overload protection in cooling. | Overcharge; outdoor fan motor failed or fan broken; dirty condenser; indoor or outdoor airflow problem. |
| 22 | Compressor preheating. | Normal in cold weather. |
| 23 | Refrigerant leak in the product. | Leak at the indoor unit, outdoor unit or connecting pipe. How to fix → |
| 24 | Outdoor board chip failure. | Wrong drive board or wrong compressor installed. How to fix → |
| 26 | Overheated outdoor radiator (heat sink). | Radiator sensor; sensor detection circuit on the control board. How to fix → |
| 27 | Protection against too high system pressure. | Pressure switch; pressure detection on the control board; system pressure actually over the limit. |
| 33 | Indoor room temperature sensor failure. | Sensor loose or failed; indoor control board. How to fix → |
| 34 | Indoor coil temperature sensor failure. | Sensor loose or failed; indoor control board. How to fix → |
| 36 | Communication failure between the indoor and outdoor unit. | Communication cable connector loose or cable failed; filter board connections; indoor control board, PFC board, power board, outdoor control board. How to fix → |
| 38 | Indoor EEPROM failure. | EEPROM chip loose; indoor control board. |
| 39 | Indoor fan motor runs abnormally. | Something blocking the fan; motor cord disconnected or loose; fan motor; indoor control board. |
| 41 | Indoor grounding protection. | Indoor control board. |
| 77 | Wi-Fi connection enabled. | Cycle power off and on. |
How to read the codes
- The indoor display shows the code automatically. If the compressor has stopped, pressing SLEEP on the remote 10 times within 10 seconds shows the code; if two faults happened together, press SLEEP 10 more times to see the other one.
- Codes show as numbers on the 7-segment display. Without the 7-segment readout, only the display board's LED shows.
- Friedrich's manual also has an outdoor board LED table (LED1-LED3) for faults while the compressor is stopped or running; see pp. 55-57 for those patterns.
Source: Friedrich Floating Air Pro Single Zone R-454B Service Manual 966011403_00, Indoor Unit Diagnostic Codes pp. 58-60. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- Mini-split communication error troubleshooting
- Mini-split flare connections (the usual leak point)
- Ductless mini-split maintenance
- Look up any mini-split code
Other brands
- Daikin FTX / FVXS / FDMQ with RXL outdoor (19 Series)
- Fujitsu Halcyon / Airstage splits (indicator lamp codes)
- MRCOOL DIY E Star 4th Generation
- Mitsubishi Electric MSZ-GL / MSY-GL (failure mode recall)
- Senville AURA / LETO
- LG Single / multi-split wall units (CH codes)
- Gree Livo / All-Match with LIV outdoor (R-32)
- Pioneer Diamante / Quantum (WYT-17, WYT-20, WYT-24, WYT-25, WYT-FA)
- Lennox Mini-splits: MLB / MPC / 3PC outdoor with M22A, M33C, MWMC, MCFA/B, MFMA indoor
- ACiQ Single-zone wall mount, R-454B (ACiQ-xxWS / -xxW-BL with -xxZS / -xxZPL outdoor)
- Midea High wall ductless DLFSHB (DLFSHBH09XAK, -12XAJ, -12XAK, -18XAK, -24XAK)
- Durastar Single-zone wall mount (indoor DRAW09F1A, DRAW12F1A, DRAW18F1A, DRAW24F1A; outdoor DRA1U09S1A, DRA1U12S1A, DRA1U18S1A, DRA1U24S1A)
- Bryant 619PHA high wall ductless (619PHAQ09XA3, 619PHAQ12XA3, 619PHAQ18XA3, 619PHAQ24XA3)
- Bryant 619RE Console and Cassette (floor console 619REQ009FBMA, 619REQ012FBMA; cassette 619REQ009CBMA, 619REQ012CBMA, 619REQ018CBMA)
- Bryant 619RE Console and Cassette (floor console 619REQ009FBMA, 619REQ012FBMA; cassette 619REQ009CBMA, 619REQ012CBMA, 619REQ018CBMA)
- Bryant 619RE Console/Cassette/Ducted (floor console 619REQ009FBMA, 619REQ012FBMA; cassette 619REQ009CBMA, 619REQ012CBMA, 619REQ018CBMA; ducted 619REQ009DBMA, 619REQ012DBMA, 619REQ018DBMA, 619REQ024DBMA, 619REQ036DBMA, 619REQ048DBMA)
- Bryant 619AHB/619PHB High Wall (619PHBQ09XA3, 619PHBQ12XA3, 619PHBQ18XA3, 619AHBQ06XA3, 619AHBQ09XA3, 619AHBQ12XA3, 619AHBQ12XA1, 619AHBQ18XA3, 619AHBQ24XA3, 619AHBQ30XA3, 619AHBQ36XA3)
- Durastar Multi-zone (outdoor DRA2U18M1A, DRA3U28M1A, DRA4U36M1A, DRA5U48M1A; indoor DRAW, DRAC, DRAD, DRAF and DRAS F1A heads)
- Friedrich Floating Air R-454B (single zone; systems FPHW091C, FPHW121C; indoor FAHSW09A1C, FAHSW12A1C, FAHFW09A1C, FAHFW09A3D, FAHFW12A3D, FAHFW18A3D, FAHFW24A3D; outdoor FPHSR09A1C, FPHSR12A1C, FPHSR09A3D, FPHSR12A3D, FPHSR18A3D, FPHSR24A3D)
- Klimaire KSIE inverter wall mount (2014–2016 models, e.g. KSIE012-H120-SW)
Did you find your code?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
HVAC Cheat Sheet · Free PT charts, code lookups and calculators for techs at hvaccheatsheet.com