Friedrich Floating Air Pro R-454B Error Codes

Applies to: Friedrich Floating Air Pro R-454B (single zone; systems FPHW093B, FPHW123B, FPHW183B, FPHW243B; indoor FAHFW09A3A, FAHFW12A3A, FAHFW18A3A, FAHFW24A3A; outdoor FPHSR09A3B, FPHSR12A3B, FPHSR18A3B, FPHSR24A3B). Number shown on the indoor unit's display.

Friedrich is a Rheem company. Other Floating Air lines (Select, Premier, Pro X, older R-410A units) have their own service manuals; check the code against the manual for your model.

CodeMeaningWhat to check
EACommunication between the display board and control board interrupted.Loose connection between display and control board; indoor control board; display board wiring.
0Normal.
1Outdoor coil temperature sensor failure.Sensor connector loose; outdoor coil sensor; indoor control board. How to fix →
2Compressor exhaust (discharge) temperature sensor failure.Sensor connector loose; discharge sensor; outdoor control board. How to fix →
5IPM module protection.IPM board; outdoor fan broken, failed or blocked; dirty condenser. How to fix →
6AC voltage higher or lower protection.Supply voltage; the unit's internal supply voltage. How to fix →
7Communication failure between the indoor and outdoor unit.Communication cable loose, miswired or failed; filter board to terminal and to outdoor board connections; indoor control board, PFC board, power board, outdoor control board. How to fix →
8Current overload protection.Fan motor running abnormally; dirty condenser or evaporator; blocked air inlet or outlet.
9Maximum current protection.Outdoor control board or drive board short circuited; other components shorted. How to fix →
10Communication trouble between the outdoor unit and the driver.Loose connection wires; outdoor board or drive board. How to fix →
11Outdoor EEPROM fault.EEPROM chip loose, inserted incorrectly or failed.
12Outdoor ambient temperature too low or too high protection.Outdoor temperature outside the operating range; not a part failure.
13Compressor exhaust (discharge) temperature too high protection.Discharge temperature sensor; low refrigerant charge. How to fix →
14Outdoor ambient temperature sensor failure.Sensor connector loose; ambient sensor; outdoor control board. How to fix →
15Compressor shell temperature too high protection.Friedrich lists the compressor exhaust temperature sensor connector and a low refrigerant charge. How to fix →
16Anti-freeze protection in cooling, or overload protection in heating.Indoor coil sensor connector or sensor; indoor control board; refrigerant system problem. How to fix →
17PFC protection.PFC; outdoor drive board. How to fix →
18DC compressor start failure.Outdoor drive board; compressor. How to fix →
19Compressor drive failure.Outdoor drive board; compressor; outdoor control board. How to fix →
20Outdoor fan motor locked rotor protection.Fan motor connection loose; something blocking the fan; fan motor; outdoor control board. How to fix →
21Outdoor coil anti-overload protection in cooling.Overcharge; outdoor fan motor failed or fan broken; dirty condenser; indoor or outdoor airflow problem.
22Compressor preheating.Normal in cold weather.
23Refrigerant leak in the product.Leak at the indoor unit, outdoor unit or connecting pipe. How to fix →
24Outdoor board chip failure.Wrong drive board or wrong compressor installed. How to fix →
26Overheated outdoor radiator (heat sink).Radiator sensor; sensor detection circuit on the control board. How to fix →
27Protection against too high system pressure.Pressure switch; pressure detection on the control board; system pressure actually over the limit.
33Indoor room temperature sensor failure.Sensor loose or failed; indoor control board. How to fix →
34Indoor coil temperature sensor failure.Sensor loose or failed; indoor control board. How to fix →
36Communication failure between the indoor and outdoor unit.Communication cable connector loose or cable failed; filter board connections; indoor control board, PFC board, power board, outdoor control board. How to fix →
38Indoor EEPROM failure.EEPROM chip loose; indoor control board.
39Indoor fan motor runs abnormally.Something blocking the fan; motor cord disconnected or loose; fan motor; indoor control board.
41Indoor grounding protection.Indoor control board.
77Wi-Fi connection enabled.Cycle power off and on.

How to read the codes

Codes point to a circuit, not a part. Test before replacing boards or sensors. Inverter boards hold a dangerous charge after power-off; wait and verify DC bus voltage is gone before touching them. Refrigerant work requires EPA 608 certification.

Source: Friedrich Floating Air Pro Single Zone R-454B Service Manual 966011403_00, Indoor Unit Diagnostic Codes pp. 58-60. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.