Lennox Mini-splits: MLB / MPC / 3PC outdoor with M22A, M33C, MWMC, MCFA/B, MFMA indoor Error Codes

Applies to: Lennox Mini-splits: MLB / MPC / 3PC outdoor with M22A, M33C, MWMC, MCFA/B, MFMA indoor. Code shown on the indoor unit display.

Older Lennox mini-splits show short codes (for example E1); newer ones show the longer form (EL 01). Old codes are listed in parentheses only where Lennox's manual pairs them consistently. Ducted MMDB units with wired remotes use a different display.

CodeMeaningWhat to check
EH 00Indoor EEPROM fault.Indoor control board.
EL 01 (E1)Indoor/outdoor communication fault.Interconnect wiring, connections, outdoor power. How to fix →
EH 03 (E3)Indoor fan speed fault.Indoor fan motor, wheel binding, connector.
EH 60Indoor room temperature sensor (T1) fault.Measure the sensor; check connector. How to fix →
EH 61Indoor coil temperature sensor (T2) fault.Measure the sensor; check connector. How to fix →
EL 0C (EC)Refrigerant leak detection (cooling mode).Leak search, flare joints; service valves fully open. How to fix →
PC 08 (F0)Outdoor current overload.Supply voltage, dirty coils, compressor, overcharge. How to fix →
EC 53 (F1)Outdoor ambient temperature sensor (T4) fault.Measure the sensor; check connector. How to fix →
EC 52 (F2)Outdoor coil temperature sensor (T3) fault.Measure the sensor; check connector. How to fix →
EC 54 (F3)Compressor discharge temperature sensor fault.Measure the sensor; check connector. How to fix →
EC 51Outdoor EEPROM fault.Outdoor control board.
EC 07 (F5)Outdoor fan speed fault.Outdoor fan motor, obstruction, connector.
EC 72Outdoor DC fan lack-phase fault.Fan motor wiring and outdoor board.
PC 00 (P0)IPM module error.Supply voltage, outdoor airflow, compressor, inverter board. How to fix →
PC 01 (P1)High or low voltage protection.Supply voltage under load. How to fix →
PC 02 (P2)High temperature at compressor top.Low charge, restriction, outdoor airflow. How to fix →
PC 0L (P3)Outdoor low ambient protection.Normal in very cold weather.
PC 04 (P4)Compressor drive error.Compressor wiring and windings, inverter board. How to fix →
PC 43Compressor lack-phase protection.Compressor U-V-W wiring, inverter board. How to fix →
PC 45Outdoor IR chip drive failure.Outdoor inverter board. How to fix →
- -Mode conflict (multi-zone).Set all indoor units to the same mode.
CPRemote switched off (status, not an error).

How to read the codes

Codes point to a circuit, not a part. Test before replacing boards or sensors. Inverter boards hold a dangerous charge after power-off; wait and verify DC bus voltage is gone before touching them. Refrigerant work requires EPA 608 certification.

Source: Lennox Mini-Split Systems Service Manual 100030 (4/2022), Indoor and Outdoor Unit Error Codes. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.