Home / Charts / Gree mini-split codes

Gree Livo / All-Match with LIV outdoor Error Codes

Applies to: Gree Livo / All-Match with LIV outdoor (R-32). Two-character code on the indoor display (dual-8).

Gree also builds units sold under other names, and many share this code style, but meanings can differ by model. Confirm against the manual for the unit you're on.

CodeMeaningWhat to check
C5Malfunction of jumper cap (indoor control panel).Jumper cap missing, loose or damaged.
C4Malfunction of outdoor unit jumper cap.Outdoor jumper cap not installed.
E6Communication malfunction between indoor and outdoor unit.Interconnect wiring and connections. How to fix →
E1High pressure protection of system.Dirty outdoor coil, fan, high ambient, overcharge, restriction.
E3Low pressure / low system pressure protection (compressor low pressure).Low charge (leak), low pressure switch. How to fix →
E4High discharge temperature protection of compressor.Low charge, restriction, discharge sensor. How to fix →
E5AC overcurrent protection.Supply voltage, dirty coils, fan, compressor, overcharge. How to fix →
E7Mode conflict (multi-zone).Indoor units set to cooling and heating at the same time.
E8High temperature prevention protection.Airflow and system pressures.
EEMalfunction of EEPROM (outdoor).Outdoor main board.
F0Refrigerant insufficient / refrigerant cut-off protection.Leak search, closed valves, restriction. How to fix →
FoRefrigerant recovery mode.Shown when a tech runs the pump-down/recovery function.
F1Indoor ambient temperature sensor open or shorted.Measure the sensor; check connector. How to fix →
F2Indoor evaporator temperature sensor open or shorted.Measure the sensor; check connector. How to fix →
F3Outdoor ambient temperature sensor open or shorted.Measure the sensor; check connector. How to fix →
F4Outdoor condenser temperature sensor open or shorted.Measure the sensor; check connector. How to fix →
F5Outdoor discharge temperature sensor open or shorted.Measure the sensor; check connector. How to fix →
b5Liquid valve temperature sensor open or shorted. How to fix →
b7Gas valve temperature sensor open or shorted. How to fix →
H3Overload protection of compressor.Low or high charge, compressor overload, restriction.
H4System is abnormal (high temperature / high power protection).Airflow and system pressures.
H5IPM protection.Supply voltage, outdoor airflow, inverter board, compressor. How to fix →
H6No feedback from indoor unit fan motor.Fan blocked, motor wiring, motor, indoor board.
H7Desynchronizing of compressor.Compressor wiring, compressor, drive board. How to fix →
HCPFC protection.Supply voltage stability, wiring, dirty coils. How to fix →
HEDemagnetization protection of compressor.Outdoor board, compressor.
L3 / LAMalfunction of outdoor fan / DC motor (LA = fan 2 on dual-fan units).Coil or fan blocked, motor wiring, motor, outdoor board.
L1Malfunction of humidity sensor.
L9High power protection.Airflow and system pressures.
LcStart-up failed.Compressor wiring, compressor, drive board. How to fix →
LdLost phase (compressor).Compressor wiring, outdoor board, compressor. How to fix →
LPIndoor and outdoor units can't be matched.Confirm an approved indoor/outdoor match.
oEUndefined outdoor unit error.Outdoor ambient outside operating range, compressor wiring, outdoor board.
P5Over-phase current protection of compressor.
P6Communication malfunction between drive board and main board.Board-to-board connection; drive or main board. How to fix →
P7Module temperature sensor circuit malfunction.Replace the outdoor control board. How to fix →
P8Module overheating protection.Outdoor airflow, dirty condenser, IPM mounting. How to fix →
PFAmbient temperature sensor of drive board malfunction. How to fix →
PHDC bus voltage too high.Measure L to N at the outdoor terminal block; high input voltage. How to fix →
PLDC bus voltage too low.Measure L to N at the outdoor terminal block; low input voltage. How to fix →
PUCharging malfunction of capacitor (drive board). How to fix →
U1Phase current detection circuit malfunction.Outdoor control board.
U2Lost phase protection of compressor.Compressor wiring, outdoor board, compressor. How to fix →
U3DC bus voltage drop malfunction.Unstable supply voltage. How to fix →
U5Current detection malfunction of unit.Low charge or outdoor board. How to fix →
U74-way valve is abnormal.Voltage to the coil, wiring, valve.
U8Zero-crossing signal malfunction of indoor unit.Supply power, indoor main board.
U9Zero-crossing malfunction of outdoor unit.Outdoor control board.

How to read the codes

Codes point to a circuit, not a part. Test before replacing boards or sensors. Inverter boards hold a dangerous charge after power-off; wait and verify DC bus voltage is gone before touching them. Refrigerant work requires EPA 608 certification.

Source: Gree All-Match Floor Standing R32 Service Manual (LIV outdoor), 9.1 Error Code List. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the furnace you're working on.