Trane Precedent ReliaTel Direct Spark Ignition Module Rooftop Gas Heat Codes
| Code | Meaning | What to check |
|---|---|---|
| Steady light | Module is powered up, but no active call for heat. | |
| Steady blinking | Active call for heat (blinking at a continuous steady rate). | |
| 1 blink | Loss of communication. | The ignition module and RTRM communicate over a Modbus link; the module locks out after 10 seconds without communication. |
| 2 blinks | System lockout: failure to ignite, no spark, low or no gas pressure, etc. | Loss of flame lockout is 3 tries, locking out after the 3rd. Flame sense signal is nominally 4.5 microamps, 1.2 microamps minimum. How to fix → |
| 3 blinks | Pressure switch: no vent air flow, bad combustion blower motor (CBM), or switch closed at the initial call for heat. Auto reset. (3 to 10 ton units only.) | How to fix → |
| 4 blinks | High limit: excessive heat in the combustion chamber, low airflow. Auto reset. | How to fix → |
| 5 blinks | Flame sensed and gas valve not energized, or flame sensed and no call for heat. | How to fix → |
| 6 blinks | Flame rollout: CBM failure, incorrect gas pressure, incorrect primary air. Requires manual reset of the switch. (3 to 10 ton units only.) | How to fix → |
| 7 blinks | W1 and W2 swapped (electromechanical 3 to 10 ton units). A ReliaTel module communicates a heat fail diagnostic back to the RTRM. | How to fix → |
How to read the codes
- Count the blinks on the green LED of the ignition module. The pause between groups of flashes is about two seconds.
- A heat failure also shows at the ReliaTel Refrigeration Module (RTRM): with a DC voltmeter between RTRM J6-7 (Heat) and J6-6 (Common), a pulsing reading means a gas heat failure such as loss of flame, a limit trip or rollout. The ignition module LED gives the detail.
- RTRM J6 readings with a thermostat or no zone sensor: about 32 VDC is ON, 0.75 VDC is OFF, 20 to 30 VDC is PULSING (all within about 10%). With a programmable zone sensor: 26 VDC on, 14 to 30 VDC pulsing.
- Lockout reset: interrupt power for at least 3 seconds. The module also resets itself after 1 hour.
Codes point to a circuit, not a part. Test before replacing anything, and never jumper a safety switch to keep a unit running. Gas, line-voltage and three-phase work is for trained technicians, and refrigerant work requires EPA 608 certification.
Source: Trane RT-SVD03N-EN, ReliaTel Microprocessor Controls Service and Diagnostic Support Manual (August 2022), Table 97 (p. 134) and RTRM diagnostics (pp. 34-36). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- Rooftop unit start-up checks
- Rooftop unit economizer setup and troubleshooting
- Rooftop unit maintenance checklist
Other rooftop unit charts
- Carrier 48FE IGC Board (17.5-27.5 ton packaged rooftop units, gas heat)
- Trane Voyager ReliaTel Hot Surface Ignition Control (gas heat, 12.5-50 ton packaged rooftop units, model numbers such as YSD150, YSD240 and YHH250)
- Lennox Energence / Strategos Prodigy 2.0 M3 Unit Controller (packaged rooftop units, model numbers such as LGH060 and LGH360)
- Carrier 48LC / 50LC 04-06 ComfortLink Controller Version 1.X (packaged rooftop units, R-410A)
- Carrier 48HC / 50HC 04-28 ComfortLink Controller Version 2.X (packaged rooftop units, R-410A)
- Carrier 48PG / 50PG 03-14 and 48PM / 50PM 16-28 ComfortLink Controller Version 5.X (packaged rooftop units, R-410A)
- Carrier 48LC / 50LC SystemVu Controller Version 4.X (sizes 04-26 packaged rooftop units)