Home / Charts / Carrier rooftop unit codes

Carrier 48PG / 50PG 03-14 and 48PM / 50PM 16-28 ComfortLink Controller Version 5.X Rooftop Unit Alarm Codes

Applies to: Carrier 48PG / 50PG 03-14 and 48PM / 50PM 16-28 ComfortLink Controller Version 5.X (packaged rooftop units, R-410A). Alarm and alert codes on the ComfortLink Scrolling Marquee or Navigator display; Alarm Status light.

CodeMeaningWhat to check
T051Compressor A1 safety trip, or compressor A1 current detected after turnoff.Safety trip: the current sensor saw no compressor current while it should be running. Adds a strike for circuit A. High-pressure switch open (wired in series with the compressor relays on the MBB), compressor internal protection open, or a wiring error. Run the compressor in Service Test: if it won't start, it's the HPS, internal protection or wiring; if the sensor always reads current, check the contactor and MBB relay. Current after turnoff turns off all compressors: check for 24 VAC at the contactor coil in Service Test (MBB relay, wiring), a welded contactor, and current sensor wiring. How to fix →
T052Compressor A2 safety trip, or compressor A2 current detected after turnoff.Same as T051 for compressor A2 (second compressor on circuit A). Safety trip adds a strike for circuit A. How to fix →
T055Compressor B1 safety trip, or compressor B1 current detected after turnoff.Same as T051 for compressor B1. Safety trip adds a strike for circuit B. How to fix →
T059Compressor C1 safety trip, or compressor C1 current detected after turnoff.Same as T051 for compressor C1. Safety trip adds a strike for circuit C. How to fix →
T064Circuit A saturated condensing temperature thermistor failure.Reading outside -40 to 240°F. The control runs the outdoor fans on outdoor temperature only; if the OAT sensor has also failed, the circuit shuts down. Faulty, shorted or open thermistor, wiring error or loose connection.
T065Circuit B saturated condensing temperature thermistor failure.Same as T064 for circuit B.
T066Circuit A saturated suction temperature thermistor failure.No circuit A cooling. The suction transducer has been turned off internally, usually by a network force on a non-exposed CCN point. Reload factory defaults or reinstall software on the MBB; consult the network manager if it continues.
T067Circuit B saturated suction temperature thermistor failure.No circuit B cooling. Same causes as T066.
T073Outdoor air temperature thermistor failure.Reading outside -40 to 240°F. Cooling and heating ambient lockouts are ignored; the economizer won't cool but still ventilates; outdoor fans run on condenser temperatures; with crankcase heat relay control, the heater relay turns on when any compressor is off. Faulty thermistor or wiring. How to fix →
T074Space temperature thermistor failure.Only when the unit control type is Space Sensor (U.CTL = 3); then no heating or cooling (economizer still ventilates). Check the T-55, T-56 or T-58 sensor and wiring.
T075Supply air temperature thermistor failure.No economizer cooling and no adaptive compressor staging. Faulty, shorted or open thermistor or wiring. How to fix →
T076Return air thermistor failure.Only if a return air sensor is configured (RAT.S = Yes); no economizer differential dry bulb control. Faulty thermistor or wiring. How to fix →
T077Space relative humidity sensor failure.Input below 3.5 mA with the sensor configured (RH.S = Yes); no indoor humidity control. Check sensor and wiring. An ECB must be installed to use the space humidity sensor.
T080Circuit C saturated condensing temperature thermistor failure.Same as T064 for circuit C.
T081Circuit C saturated suction temperature thermistor failure.No circuit C cooling. Same causes as T066.
T092Circuit A suction pressure transducer failure.Locks out circuit A; reset with the Scrolling Marquee. The board can't read the transducer voltage: faulty transducer, faulty 5-volt supply, or loose connection.
T093Circuit B suction pressure transducer failure.Locks out circuit B; manual reset. Same causes as T092.
T101Circuit C suction pressure transducer failure.Locks out circuit C; manual reset. Same causes as T092.
T102Compressor A1 (or A2) current sensor failure.The current sensor output is stuck high. Wiring error or loose connection. While waiting on a replacement CS board, set Configuration > COOL > CIR.A > CS.A1 to DISABLE (then T051 can't report current faults). Table 12 lists the A2 sensor failure under this code too.
T103Compressor B1 current sensor failure.Same as T102 for compressor B1 (CS.B1).
T104Compressor C1 current sensor failure.Same as T102 for compressor C1 (CS.C1).
T110Circuit A loss of charge.Locks out circuit A; manual reset. With the compressor off, suction below 5 psig while outdoor air is above -5°F for one continuous minute. Low refrigerant or faulty suction transducer. (Low pressure while running is T133.) How to fix →
T111Circuit B loss of charge.Locks out circuit B; manual reset. Same test and causes as T110. How to fix →
T126Circuit A high discharge pressure.Shuts down circuit A; resets automatically. T051 active while condensing temperature is above 150°F. Overcharge, high outdoor ambient with a dirty outdoor coil, plugged filter drier, or faulty high-pressure switch. Diagnose as for T051.
T127Circuit B high discharge pressure.Shuts down circuit B. T055 active while condensing temperature is above 150°F. Same causes as T126.
T133Circuit A low refrigerant pressure.Adds a strike for circuit A. Saturated suction below the low suction levels SST.1, SST.2 or SST.3 (Configuration > COOL > SST) for 5, 4 or 3 minutes (1.5 minutes at level 3 without the economizer), or below SST.3 minus 5°F for 20 seconds with outdoor air above 40°F. Levels drop 1°F for every 2°F of outdoor air below 40°F; below 10°F outdoor the circuit shuts down without a strike. A frosted coil sets it and should thaw during the 15-minute reset. Low charge, dirty filters, evaporator fan backwards, loose or broken belt, plugged filter drier, faulty transducer, very cold return air, or an economizer stuck open in low ambient. How to fix →
T134Circuit B low refrigerant pressure.Adds a strike for circuit B. Same test and causes as T133. How to fix →
T140Circuit C loss of charge.Locks out circuit C; manual reset. Same test and causes as T110. How to fix →
T141Circuit C low refrigerant pressure.Adds a strike for circuit C. Same test and causes as T133. How to fix →
T142Circuit C high discharge pressure.Shuts down circuit C. T059 active while condensing temperature is above 150°F. Same causes as T126.
T143Circuit A failure to pressurize.Adds a strike for circuit A. At compressor start, suction didn't drop at least 10 psig and stay there for 20 seconds AND condensing temperature didn't rise at least 5°F and stay there for 65 seconds (both have to happen). Compressor wiring causing reverse rotation, or a faulty compressor.
T144Circuit B failure to pressurize.Adds a strike for circuit B. Same test and causes as T143.
T145Circuit C failure to pressurize.Adds a strike for circuit C. Same test and causes as T143.
T153Real time clock hardware failure.No time and date schedules; unit defaults to 24/7 unoccupied. Cycle power and reconfigure time and date before replacing the MBB.
A154Serial EEPROM hardware failure.Unit shutdown. The EEPROM chip on the MBB that stores the configuration isn't responding. Cycle power before replacing the board.
T155Serial EEPROM storage failure error.Configuration can't be verified; the unit runs on last known good values or defaults, so operating errors may occur. Cycle power and reconfigure the control points before replacing the MBB.
A156Critical serial EEPROM storage fail error.Unit shutdown. Cycle power and check the critical points before replacing the MBB: Configuration > COOL > N.CIR (number of circuits), COOL > N.A (compressors on circuit A), COOL > OFC > OFC.3, HMZR > REHT (Humidi-MiZer equipped), HMZR > RH.FN (reheat fan control).
A157A/D hardware failure.Unit shutdown. The analog-to-digital chip on the MBB failed. Cycle power before replacing the board.
A163Circuit A down due to failure.Locks out circuit A; manual reset. The circuit has 3 strikes or was locked out by another alarm. Find the alert that caused the strikes before resetting.
A164Circuit B down due to failure.Locks out circuit B; manual reset. Same as A163.
A165Circuit C down due to failure.Locks out circuit C; manual reset. Same as A163.
T173Loss of communication with the Energy Management Module.These units don't support an EMM; an internal force is looking for one. Reload software on the MBB without restoring configurations (use factory configurations first); replace the MBB if it continues.
T179Loss of communication with the economizer control board (ECB).Economizer disabled. Usually wiring, a faulty MBB or ECB, or a humidity sensor configured without an ECB installed. Check the ECB address and the resistance between pins on the LEN connections (Table 13). How to fix →
T180Loss of communication with the economizer actuator.The ECB can't talk to the Belimo actuator. Wiring, actuator failure, or the wrong actuator (it must be an MFT communicating actuator). If the analog signal is connected, the economizer can still be controlled through it. Verify the actuator feedback signal. How to fix →
T181Loss of communication with outside air unit.OAU type (Configuration > OAU > OA.TY) is set but the OAU operating mode hasn't been received for 3 minutes; all OAU data resets. Wiring problem or OAU communication failure.
A200Linkage timeout, communication failure.Lost communication with a Linkage device it had talked to since the last power cycle; falls back to local setpoint. Without a backup sensor, T074 follows. Reset power and verify Linkage is communicating.
A404Fire shutdown.Unit shutdown. The shutdown input is open or closed per its configuration, usually from a smoke detector. Check Configuration > UNIT > FS.SW, the wiring and the device.
T408Dirty air filter.Filter status switch sensed a plugged filter for 120 seconds after the indoor fan ran 10 seconds. Check Configuration > UNIT > FL.SW, the wiring, and that the hose is on the low side of the switch.
T409Fan status switch on with fan commanded off, or off with fan commanded on.Bad fan status switch or wrong configuration (Configuration > UNIT > FN.SW); with the fan commanded on, also a tripped breaker, broken belt or bad indoor fan motor. The hose goes on the high side of the switch. If IDF.F = YES the unit shuts down and needs a manual reset; otherwise it resets automatically.
T410R-W1 jumper not installed in space temp mode, or must be installed to run heat in Service Test.Install a jumper between R and W1, or confirm space temperature mode is wanted. For Service Test heat, remove the jumper afterward if the unit runs on a thermostat; leave it only with a space temperature probe.
T411Thermostat Y2 input activated without Y1.Unit runs as if Y1 and Y2 are both on. Bad thermostat or thermostat wiring. Resets when Y1 comes on. How to fix →
T412Thermostat W2 input activated without W1.Unit runs as if W1 and W2 are both on. Bad thermostat or thermostat wiring. Resets when W1 comes on. How to fix →
T413Thermostat Y and W inputs activated simultaneously.Unit runs in whichever mode came on first. Bad thermostat or thermostat wiring. How to fix →
T414Economizer damper actuator fault (six texts: out of calibration, torque above load limit, hunting excessively, stuck or jammed, mechanical failure, direction switch wrong).Only when the ECB controls the Belimo actuator digitally (MFT). Run economizer calibration (Service Test > INDP > E.CAL); if it doesn't clear, power off, loosen the actuator clamp, push the damper closed, tighten and recalibrate. Check damper load and actuator size; stuck means actual position is more than 3% off the command for 20 seconds; hunting clears when the stop jog ratio is under 21% (leave the actuator powered with no signal for a few hours); the direction switch goes clockwise with the CW face accessible. How to fix →
T415IAQ input out of range.No IAQ operation. Bad sensor, bad wiring, or sensor configured incorrectly. How to fix →
T416OAQ input out of range.No OAQ operation. Bad sensor, bad wiring, or sensor configured incorrectly. How to fix →
T418Outside air unit alarm (four texts: OAU motor failure, OAU dirty filter, OAU low CFM, OAU general alarm).Reported by the outside air unit. Check OAU motors, filters and airflow, or the OAU itself for a general alarm.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a safety switch to keep a unit running. Gas, line-voltage and three-phase work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Carrier 48/50PG C03-14 and 48/50PM C16-28 with ComfortLink Controls Version 5.x, Controls, Start-Up, Operation, Service and Troubleshooting Instructions (48-50PGPM-03T, edition 1/11), alert descriptions pp. 38-40 and 43, Table 12 ComfortLink Alarm Codes pp. 41-42. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.