Trane Voyager ReliaTel Hot Surface Ignition Control Rooftop Gas Heat Codes
| Code | Meaning | What to check |
|---|---|---|
| Steady off | No power or internal failure. | The ignition module runs on 18 to 32 VAC. Check control voltage at the module before replacing it. |
| Steady on | Normal power-up, with no heat call. | |
| Slow flash | Normal call for heat (3/4 second on, 1/4 second off). | |
| Fast flash | Used for error indication only. | |
| 1 flash | Communication loss between the RTRM and the ignition module. | The module and RTRM talk over a Modbus link; the module locks out after 10 seconds without communication. |
| 2 flashes | System lockout: failed to detect or sustain flame. | Loss of flame lockout is 3 tries, locking out after the 3rd. On these units the hot surface igniter also acts as the flame sensor; flame sense current is 4.5 microamps nominal, 1 microamp minimum. Igniter voltage is 115 VAC. How to fix → |
| 3 flashes | Not used. | |
| 4 flashes | High limit switch open. | The module checks high limit switches TCO1 and TCO2 for normally closed contacts at the start of each cycle. How to fix → |
| 5 flashes | Flame sensed and gas valve not energized, or flame sensed and no call for heat. | How to fix → |
How to read the codes
- Count the flashes on the green LED of the ignition module. The pause between groups of flashes is about two seconds.
- At initial power-up the LED flashes for one second.
- A gas heat failure also shows at the ReliaTel Refrigeration Module (RTRM): with a DC voltmeter between RTRM J6-7 (Heat) and J6-6 (Common), a pulsing reading means a heat failure. The ignition module LED gives the detail.
- Lockout reset: interrupt power for at least 3 seconds. The module also resets itself after 1 hour.
Codes point to a circuit, not a part. Test before replacing anything, and never jumper a safety switch to keep a unit running. Gas, line-voltage and three-phase work is for trained technicians, and refrigerant work requires EPA 608 certification.
Source: Trane RT-SVD03N-EN, ReliaTel Microprocessor Controls Service and Diagnostic Support Manual (August 2022), Tables 99 and 100 and Ignition Control Module Diagnostics, p. 138. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- Rooftop unit start-up checks
- Rooftop unit economizer setup and troubleshooting
- Rooftop unit maintenance checklist
Other rooftop unit charts
- Carrier 48FE IGC Board (17.5-27.5 ton packaged rooftop units, gas heat)
- Trane Precedent ReliaTel Direct Spark Ignition Module (gas heat, 3-10 ton packaged rooftop units, model numbers such as YSC060 and YHC092)
- Lennox Energence / Strategos Prodigy 2.0 M3 Unit Controller (packaged rooftop units, model numbers such as LGH060 and LGH360)
- Carrier 48LC / 50LC 04-06 ComfortLink Controller Version 1.X (packaged rooftop units, R-410A)
- Carrier 48HC / 50HC 04-28 ComfortLink Controller Version 2.X (packaged rooftop units, R-410A)
- Carrier 48PG / 50PG 03-14 and 48PM / 50PM 16-28 ComfortLink Controller Version 5.X (packaged rooftop units, R-410A)
- Carrier 48LC / 50LC SystemVu Controller Version 4.X (sizes 04-26 packaged rooftop units)