Carrier 48LC / 50LC 04-06 ComfortLink Controller Version 1.X Rooftop Unit Alarm Codes
| Code | Meaning | What to check |
|---|---|---|
| T051 | Compressor A1 safety trip, or compressor A1 detected after turnoff. | Safety trip adds a strike for circuit A: high-pressure switch or condensate overflow switch open, compressor internal protection open, or a wiring error. Detected after turnoff turns off all compressors and keeps the indoor fan on: welded contactor or frozen compressor relay on the MBB. Expand the text to see which. How to fix → |
| T064 | Circuit A saturated condensing temperature thermistor failure. | Reading outside -40 to 240°F. Faulty, shorted or open thermistor, wiring error or loose connection. |
| T066 | Circuit A saturated suction temperature thermistor failure. | No circuit A cooling. The suction transducer has been forced inactive internally, usually by a network force on a non-exposed CCN point. Reload factory defaults or reinstall software on the MBB. |
| T073 | Outdoor air temperature thermistor failure. | No cooling with the economizer; ambient lockouts ignored. Faulty, shorted or open thermistor or wiring. How to fix → |
| T074 | Space temperature thermistor failure. | If the unit is set for a space sensor, no heating or cooling. Check the T-55, T-56 or T-58 sensor and wiring. |
| T075 | Supply air temperature thermistor failure. | No cooling with the economizer and no adaptive compressor staging. Faulty, shorted or open thermistor or wiring. How to fix → |
| T076 | Return air thermistor failure. | If configured for a return air sensor, no economizer differential dry bulb control. Faulty thermistor or wiring. How to fix → |
| T077 | Space relative humidity sensor failure. | Input below 3.5 mA with the sensor configured. Dehumidification won't work. Check sensor and wiring; an ECB must be installed to use the sensor. |
| T092 | Circuit A suction pressure transducer failure. | Locks out circuit A; manual reset. Faulty transducer, faulty 5-volt supply, or loose connection. |
| T102 | Compressor current sensor failure. | Only if the unit is configured with a current sensor (CS.A1). Miswired or bad current sensor board, or configured for a board that isn't installed. |
| T110 | Circuit A loss of charge. | Locks out circuit A; manual reset. With the compressor off, suction below 5 psig while outdoor air is above -5°F for one minute. Low refrigerant pressure or faulty suction transducer. How to fix → |
| T126 | Circuit A high discharge pressure. | Shuts down circuit A. T051 active while condensing temperature is above 150°F. Overcharge, high outdoor ambient with a dirty outdoor coil, plugged filter drier, or faulty high-pressure switch. |
| T133 | Circuit A low refrigerant pressure. | Adds a strike for circuit A. Low charge, dirty filters, evaporator fan turning backwards, loose or broken fan belt, plugged filter drier, faulty transducer, excessively cold return air, or an economizer stuck open in low ambient. How to fix → |
| T143 | Circuit A failure to pressurize. | Adds a strike for circuit A. Suction pressure didn't drop at least 10 psig in the first 20 seconds of compressor run (5 psig if outdoor air is below 40°F). Wiring causing reverse rotation, or a faulty compressor. |
| T153 | Real time clock hardware failure. | No time and date schedules; unit defaults to 24/7 unoccupied. No time/date configured, software failure or MBB failure. Cycle power and reconfigure before replacing the board. |
| A154 | Serial EEPROM hardware failure. | Unit shutdown. Software failure or MBB failure. Cycle power and reconfigure before replacing the board. |
| T155 | Serial EEPROM storage failure error. | Unit runs on last known good values or defaults, so operating errors may occur. Software or MBB failure. |
| A156 | Critical serial EEPROM storage fail error. | Unit shutdown. Software or MBB failure. |
| A157 | A/D hardware failure. | Unit shutdown. The analog-to-digital chip on the MBB failed. Cycle power and reconfigure before replacing the board. |
| A163 | Circuit A down due to failure. | Locks out circuit A; manual reset. The circuit has 3 strikes or was locked out by another alarm. Find the alarm that caused the strikes before resetting. |
| T173 | Loss of communication with the Energy Management Module. | These units don't support an EMM. Reload software on the MBB; replace the MBB if it continues. |
| T175 | Loss of communication with VFD. | Unit shutdown while the indoor fan type is set for a VFD. Wiring problem or incorrect configuration in the VFD or MBB. |
| T179 | Loss of communication with the economizer control board (ECB). | Economizer disabled. Wiring problem, or a humidity sensor configured without an ECB installed. Check the ECB address and resistance between pins on the LEN connections. How to fix → |
| T180 | Loss of communication with the economizer actuator. | Wiring problem, actuator failure, or wrong actuator. If the analog signal is connected the economizer can still be controlled through it. How to fix → |
| A200 | Linkage timeout, communication failure. | Lost communication with a Linkage device it had talked to since power-up; falls back to local setpoint. Reset power and verify Linkage is communicating. |
| A404 | Fire shutdown. | Unit shutdown. The shutdown input is open or closed (per configuration), usually from a smoke detector or other auxiliary device. Check the FS.SW configuration, wiring and device. |
| T408 | Dirty air filter. | Filter status switch sensed a plugged filter for 120 seconds with the fan running. Check the FL.SW configuration, wiring, and that the hose is on the low side of the switch. |
| T409 | Fan status switch on with fan commanded off, or off with fan commanded on. | Bad fan status switch or wrong configuration; with fan commanded on, also a tripped breaker, broken belt or bad indoor fan motor. If IDF.F = YES the unit shuts down and needs a manual reset. Check the hose is on the high side of the switch. |
| T410 | R-W1 jumper not installed in space temp mode, or must be installed to run heat in Service Test. | Install the jumper between R and W1 on the terminal board, or confirm space temperature mode is wanted. Remove a Service Test jumper afterward unless the unit runs on a space temperature probe. |
| T411 | Thermostat Y2 input activated without Y1. | Unit runs as if Y1 and Y2 are both on. Bad thermostat or thermostat wiring. How to fix → |
| T412 | Thermostat W2 input activated without W1. | Unit runs as if W1 and W2 are both on. Bad thermostat or thermostat wiring. How to fix → |
| T413 | Thermostat Y and W inputs activated simultaneously. | Unit runs in whichever mode came on first. Bad thermostat or thermostat wiring. How to fix → |
| T414 | Economizer damper actuator fault (six texts: out of calibration, torque above load limit, hunting excessively, stuck or jammed, mechanical failure, direction switch wrong position). | From the Belimo actuator through the ECB. Run economizer calibration (E.CAL); check damper load, blades and gears; replace a failed actuator; set the direction switch so the CW face is accessible. Expand the text to see which. How to fix → |
| T415 | IAQ input out of range. | Input below 3.5 mA with the sensor configured; IAQ operation disabled. Bad sensor, wiring or configuration. How to fix → |
| T416 | OAQ input out of range. | Input below 3.5 mA with the sensor configured; OAQ operation disabled. Bad sensor, wiring or configuration. How to fix → |
| A420 | Supply VFD fault. | Unit shutdown. The VFD faulted; the last fault number is under Run Status > S.VFD > LFC. See the VFD section of the manual. |
How to read the codes
- Codes starting with T are alerts and codes starting with A are alarms. The Alarm Status light on the Scrolling Marquee comes on when any are active, along with the number of active alarms in the automatic View of Run Status.
- Alarms > CURR lists active alarms in numerical order; Alarms > HIST lists up to 20 in order of occurrence, with time and date. Press ESCAPE and ENTER together on a code to expand its description, because some codes (T051, T409, T410, T414) have more than one meaning.
- Alarms > R.CURR = YES resets all current alarms; turning unit power off also resets them. Alarms > R.HIST = YES clears the history.
- Before restarting, check the alarm list for the cause. If there's a problem, diagnose it in Service Test mode; alarms must be reset before the unit will run in Normal or Service Test mode.
- A circuit gets a strike for some faults (T051, T133, T143) and locks out at 3 strikes (A163).
- This list is for 48/50LC 04-06 with ComfortLink version 1.x. Other ComfortLink units (48/50PG, PM, HC and others) use similar numbers with different texts; see the 48/50HC and 48/50PG / PM charts for those units and check the controls manual for others.
Codes point to a circuit, not a part. Test before replacing anything, and never jumper a safety switch to keep a unit running. Gas, line-voltage and three-phase work is for trained technicians, and refrigerant work requires EPA 608 certification.
Source: Carrier 48/50LC 04-06 with ComfortLink Controls Version 1.X, Controls, Start-Up, Operation and Troubleshooting (48-50LC-C01T), Alarms and Alerts pp. 26-29 and Table 6 ComfortLink Alarm Codes p. 30. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- Rooftop unit start-up checks
- Rooftop unit economizer setup and troubleshooting
- Rooftop unit maintenance checklist
Other rooftop unit charts
- Carrier 48FE IGC Board (17.5-27.5 ton packaged rooftop units, gas heat)
- Trane Precedent ReliaTel Direct Spark Ignition Module (gas heat, 3-10 ton packaged rooftop units, model numbers such as YSC060 and YHC092)
- Trane Voyager ReliaTel Hot Surface Ignition Control (gas heat, 12.5-50 ton packaged rooftop units, model numbers such as YSD150, YSD240 and YHH250)
- Lennox Energence / Strategos Prodigy 2.0 M3 Unit Controller (packaged rooftop units, model numbers such as LGH060 and LGH360)
- Carrier 48HC / 50HC 04-28 ComfortLink Controller Version 2.X (packaged rooftop units, R-410A)
- Carrier 48PG / 50PG 03-14 and 48PM / 50PM 16-28 ComfortLink Controller Version 5.X (packaged rooftop units, R-410A)
- Carrier 48LC / 50LC SystemVu Controller Version 4.X (sizes 04-26 packaged rooftop units)