Rooftop Unit (RTU) Maintenance Checklist

Quarterly and seasonal PM sheet for packaged rooftop units: filters, coils, drain, economizer, gas heat and three-phase electrical readings.

Schedule follows Carrier's rooftop unit service instructions: routine items every quarter (and 30 days after start-up), seasonal items at the start of each cooling and heating season. Other manufacturers' schedules differ; their instructions win.

Never run the unit without the return air filters in place.

Saves on this device as you type. Nothing is sent to us.
Job
Equipment
Every visit (quarterly)
Return air filters replacedSame size and type
Filter size and quantityin. / qty
Outdoor air hood inlet screens cleanedWash with hot low-pressure water and soft detergent; dry before restarting; flow arrows the right way
Condenser coils checked for dirt and debris; cleaned if needed
Condensate drain and trap checked; trap full; drains freely
Unit runs without unusual noise or vibration
Cooling season start
Outdoor fan motor mounting bolts tight
Outdoor fan blade position correct in its orifice
Compressor mounting bolts tightDon't loosen spring-mounted compressors
Control box clean; wiring in good condition; terminals tight
Indoor coil clean
Supply blower motor amps (nameplate / measured)A
Refrigerant charge check: circuit A (method per unit chart)°F / psig
Refrigerant charge check: circuit B°F / psig
Return air temperature°F
Supply air temperature (cooling)°F
Heating season start (gas heat)
Heat exchanger flue passageways clean
Burners in good condition; flame looks right
Flue hood and combustion air inlet clear
Inlet gas pressurein. w.c.
Manifold gas pressure (per unit data)in. w.c.
Temperature rise (nameplate range / measured)°F
Burners shut down when the heat call ends
Economizer and outdoor air
Inlet filters / screens condition checked
Damper travels freely, fully open to fully closedUse the controller's test mode
Gears, linkage and dampers free of debris and dirt
Minimum position settingV / %
Changeover (high limit) setting°F
Controller shows no active economizer alarms
Electrical (three-phase)
Supply voltage L1-L2 / L2-L3 / L1-L3V
Voltage imbalance (2% max on Carrier units)Use the three-phase imbalance calculator%
Compressor amps L1 / L2 / L3, circuit AA
Compressor amps L1 / L2 / L3, circuit BA
Indoor fan motor amps L1 / L2 / L3A
Contactors not pitted or burned
Unit controller: alarm history read and cleared after repairs
Belt-drive blowers only
Belt condition and tension checkedPer the unit's belt tension instructions
Pulleys aligned and set screws tight
Blower and motor bearings: no noise or play
Notes and recommendations