Home / Charts / Carrier rooftop unit codes

Carrier 48LC / 50LC SystemVu Controller Version 4.X Rooftop Unit Alarm Codes

Applies to: Carrier 48LC / 50LC SystemVu Controller Version 4.X (sizes 04-26 packaged rooftop units). Fault (F) and alert (A) codes on the SystemVu controller display.

CodeMeaningWhat to check
F010MBB low voltage. Unit shutdown. Automatic reset.Main base board supply below 17 VAC; clears above 19 VAC. Brownout, low supply voltage, or supply power missing a phase. How to fix →
F011MBB reference voltage. Unit shutdown. Automatic reset.MBB failure or supply voltage low.
A012MBB zero crossing. Alert. Automatic reset.Supply voltage frequency too high or too low, or MBB failure.
F013MBB fuse 2 open. Unit shutdown. Automatic reset.Internal fuse 2 overheated: a switch input has a wiring error (short) or the switch drew too much current. Fuse 2 feeds the fire shutdown input and the IGC fan request.
F014MBB fuse 3 open. Unit shutdown. Automatic reset.Internal fuse 3 overheated: a switch input has a wiring error or the switch drew too much current. Fuse 3 feeds configurable discrete inputs 12, 13 and 14.
A015MBB Rnet voltage range. Alert. Automatic reset.Rnet 12 V output out of range; an accessory on the Rnet plug may not work. MBB failure or supply voltage low.
A016MBB 24 VDC range. 4-20 mA inputs go into error. Automatic reset.24 VDC output below 17 VDC; clears above 19 VDC. MBB failure or supply voltage low.
A017MBB 5 VDC range. Transducer inputs go into error. Automatic reset.5 VDC output below 4.5 VDC. MBB failure or supply voltage low.
F018MBB EEPROM failure. Unit shutdown. Automatic reset.Software failure or MBB failure. Try cycling power before replacing the board.
A019MBB clock failure. No time, date or schedule operation. Automatic reset.Clock chip not responding; the unit defaults to 24/7 unoccupied. Software or MBB failure. Try cycling power and resetting time and date before replacing the board.
F020Software error. Unit shutdown. Automatic reset.Corrupt software or software failure. Try cycling power before replacing the board.
A099Communication loss with SIOB on LEN bus. Inputs from the I/O board ignored, outputs not controlled. Automatic reset.Wiring problem between the MBB and the SIOB.
A100SAT sensor error. No free cooling and no supply air temperature limit protection. Automatic reset.Faulty, shorted or open thermistor from a wiring error or loose connection.
A101FST sensor range (fan supply temperature, outside -40 to 245°F). Alert. Automatic reset.Faulty or incorrect thermistor (improper ohm reading).
A102FST open sensor. Alert. Automatic reset.Missing or open thermistor from a wiring error or loose connection.
A103FST shorted sensor. Alert. Automatic reset.Faulty or shorted thermistor from a wiring error or loose connection.
A104OAT sensor range (outside -40 to 245°F). No free cooling, no low ambient operation. Automatic reset.Ambient lockouts are ignored and the control assumes outdoor temperature is high; the economizer still ventilates. Faulty or incorrect thermistor (improper ohm reading).
A105OAT open sensor. No free cooling, no low ambient operation. Automatic reset.Missing or open thermistor from a wiring error or loose connection.
A106OAT shorted sensor. No free cooling, no low ambient operation. Automatic reset.Faulty or shorted thermistor from a wiring error or loose connection.
A107RAT sensor range. No differential dry bulb crossover. Automatic reset.Free cooling can only use outdoor temperature and the enthalpy switch. Faulty or incorrect thermistor (improper ohm reading). How to fix →
A108RAT open sensor. No differential dry bulb crossover. Automatic reset.Missing or open thermistor from a wiring error or loose connection. How to fix →
A109RAT shorted sensor. No differential dry bulb crossover. Automatic reset.Faulty or shorted thermistor from a wiring error or loose connection. How to fix →
A110SPT sensor range (space temperature). No heating or cooling. Automatic reset.The economizer still ventilates. Faulty thermistor in the T-55, T-56 or T-58 sensor, an open or short from wiring, or a loose connection.
A111SPT open sensor. No heating or cooling. Automatic reset.Missing or open thermistor from a wiring error or loose connection.
A112SPT shorted sensor. No heating or cooling. Automatic reset.Faulty or shorted thermistor from a wiring error or loose connection.
A130Circuit A suction pressure sensor range (outside -6.7 to 420 psig). Shuts down circuit A. Automatic reset.Faulty transducer, faulty 5 V power supply, or loose connection.
A131Circuit A suction pressure open sensor. Shuts down circuit A. Automatic reset.Faulty transducer, faulty 5 V power supply, or loose connection.
A132Circuit A suction pressure shorted sensor. Shuts down circuit A. Automatic reset.Faulty transducer, faulty 5 V power supply, or loose connection.
A133Circuit A discharge pressure sensor range (outside 14.5 to 667 psig). Shuts down circuit A. Automatic reset.Faulty transducer, faulty 5 V power supply, or loose connection.
A134Circuit A discharge pressure open sensor. Shuts down circuit A. Automatic reset.Faulty transducer, faulty 5 V power supply, or loose connection.
A135Circuit A discharge pressure shorted sensor. Shuts down circuit A. Automatic reset.Faulty transducer, faulty 5 V power supply, or loose connection.
A150Outdoor airflow (CFM) open sensor. No outdoor air CFM operation. Automatic reset.Input reads 0 mA with the sensor configured as installed. Wiring problem or configuration error. How to fix →
A151Outdoor airflow (CFM) shorted sensor. No outdoor air CFM operation. Automatic reset.Wiring problem or configuration error. How to fix →
A160Outdoor air RH open sensor. No enthalpy crossover. Automatic reset.Only dry bulb is used for free cooling. Bad sensor, bad wiring, or sensor configured wrong. How to fix →
A161Outdoor air RH shorted sensor. No enthalpy crossover. Automatic reset.Bad sensor, bad wiring, or sensor configured wrong. How to fix →
A162Return air RH open sensor. No differential enthalpy crossover. Automatic reset.Bad sensor, bad wiring, or sensor configured wrong. How to fix →
A163Return air RH shorted sensor. No differential enthalpy crossover. Automatic reset.Bad sensor, bad wiring, or sensor configured wrong. How to fix →
A164IAQ open sensor. No IAQ operation. Automatic reset.Bad sensor, bad wiring, or sensor configured wrong.
A165IAQ shorted sensor. No IAQ operation. Automatic reset.Bad sensor, bad wiring, or sensor configured wrong.
A166OAQ open sensor. No OAQ operation. Automatic reset.Bad sensor, bad wiring, or sensor configured wrong.
A167OAQ shorted sensor. No OAQ operation. Automatic reset.Bad sensor, bad wiring, or sensor configured wrong.
A168Space relative humidity open sensor. No dehumidifying. Automatic reset.Bad sensor, bad wiring, sensor configured wrong, or loss of communication to the SIOB.
A169Space relative humidity shorted sensor. No dehumidifying. Automatic reset.Bad sensor, bad wiring, sensor configured wrong, or loss of communication to the SIOB.
A170Economizer feedback range (outside 1.3 to 10.3 VDC). No economizer diagnostics. Automatic reset.Wiring problem, actuator failure, wrong actuator, or configuration error. Check the feedback signal from the actuator and run a damper calibration. How to fix →
A171Economizer feedback open. No economizer diagnostics. Automatic reset.Wiring problem with the actuator or configuration error. How to fix →
A172Economizer feedback shorted. No economizer diagnostics. Automatic reset.Wiring problem with the actuator or configuration error. How to fix →
A190Thermostat heat/cool calls. Runs in the mode that came on first. Automatic reset.Y1, Y2 or Y3 energized at the same time as W1 or W2. Bad thermostat or thermostat wiring. How to fix →
A191Thermostat improper cool. Runs cooling by the number of active inputs. Automatic reset.Y2 or Y3 on without Y1. Bad thermostat or thermostat wiring. How to fix →
A192Thermostat improper heat. Runs heating by the number of active inputs. Automatic reset.W2 on without W1. Bad thermostat or thermostat wiring. How to fix →
F200Fire shutdown. Unit shutdown. Automatic reset.Smoke detected by the smoke detector (or another device on the fire shutdown input). Check configuration, wiring and the device.
F201Condensate overflow. Cooling shutdown. Automatic reset.Drain pan plugged, sensor error, or configuration error.
A203Dirty filter. Alert. Automatic reset.Dirty filter or expired filter timer. If the timer tripped it, reset with RESET FILTER TIME under RUN STATUS > GENERAL (or INPUTS > GENERAL INPUTS) after changing the filter.
F204Remote shutdown. Unit shutdown. Automatic reset.Remote shutdown switch activated.
A210General status (alert). Automatic reset.General switch input activated, or wrong configuration.
F211General status (fault). Unit shutdown. Automatic reset.General switch input activated, or wrong configuration.
F310Circuit A down due to failure. Shuts down circuit A. Manual reset.Compressors have 3 strikes or were locked out by another alarm. Find the alerts that caused the strikes. Reset from the display or by cycling power.
F311Circuit A low charge. Shuts down circuit A. Manual reset.With compressors off, suction and discharge pressure are both below the low charge level while outdoor temperature is above the low charge limit. Low refrigerant or a faulty pressure transducer.
A312Circuit A unexpected off. Strike for the active compressors. Automatic reset.Suction pressure jumped and pressure ratio dropped within 10 seconds while running. Compressor failure, open high pressure switch, compressor internal protection, transducer failure, wiring, or nuisance operating conditions.
A313Circuit A high discharge. Unloads compression and runs outdoor fans at high cool speed. Automatic reset.Clears when pressure falls 20 psig below the limit. Overcharge, high outdoor ambient with a dirty outdoor coil, plugged filter drier, or outdoor fan speeds set too low. How to fix →
A314Circuit A high pressure switch trip. Adds compressor strikes. Automatic reset.Resets when pressure falls and the switch stays closed 3 minutes. Overcharge, high outdoor ambient with a dirty outdoor coil, plugged filter drier, or outdoor fan speeds set too low. How to fix →
A315Circuit A low discharge. Adds compressor strikes. Automatic reset.Discharge pressure below outdoor temperature plus the configured offset for 1 minute. Undercharge, low outdoor ambient with a dirty outdoor coil, plugged filter drier, or outdoor fan speeds set too high.
A316Circuit A low suction. Adds compressor strikes. Automatic reset.Evaporating temperature below the low suction levels. Low charge, dirty filters, indoor fan turning backward, loose or broken belt, plugged filter drier, faulty transducer, very cold return air, or economizer stuck open in cold weather. How to fix →
A317Circuit A pressure ratio. Adds compressor strikes. Automatic reset.Low charge, plugged filter drier, faulty transducer, or low ambient with outdoor fans running too fast.
F318Compressor stuck on. Unit in safety shutdown. Manual reset.Suction didn't rise and pressure ratio didn't fall after the compressor was told to stop. Welded contactor or frozen compressor relay on the MBB. How to fix →
F319Compressor A1 down due to failure. Locks out compressor A1. Manual reset.A1 has 3 strikes or was locked out by another alarm.
A320Compressor A1 reverse rotation. Adds a strike for A1. Automatic reset.10 seconds after start, suction rose and discharge dropped. Wiring causing reverse rotation, or a faulty compressor. How to fix →
A321Compressor A1 fail to pressure. Adds a strike for A1. Automatic reset.10 seconds after start, suction didn't drop and discharge didn't rise enough. Wiring causing reverse rotation, or a faulty compressor. How to fix →
F322Compressor A2 down due to failure. Locks out compressor A2. Manual reset.A2 has 3 strikes or was locked out by another alarm.
A323Compressor A2 reverse rotation. Adds a strike for A2. Automatic reset.Wiring causing reverse rotation, or a faulty compressor. How to fix →
A324Compressor A2 fail to pressure. Adds a strike for A2. Automatic reset.Wiring causing reverse rotation, or a faulty compressor. How to fix →
A410IGC ignition failure. Locks out heat. Automatic reset.No IGC fan request 15 minutes after heat stage 1 came on. Faulty IGC wiring, no gas flow, or wrong configuration. Read the IGC board's LED flash code for detail. How to fix →
F411Rollout without heat. Unit in safety shutdown. Automatic reset.IGC fan request came on with heat off for at least 3 minutes; resets 10 minutes after the fan request clears. Faulty IGC wiring, or a rollout switch trip without a heat call. How to fix →
F412Runaway heat. Unit in safety shutdown. Automatic reset.Supply air above the maximum; resets when it falls 50°F below the maximum. Heat stuck on, or low airflow.
A510Indoor fan status. Alert. Automatic reset.Fan speed feedback didn't follow the command within the VFD ramp time. Broken belt, motor failure, or configuration error. How to fix →
F511Indoor fan off when commanded on. Unit shutdown. Manual reset.As printed in the manual: fan stuck on, or incorrect configuration.
F512Indoor fan on when commanded off. Unit shutdown. Manual reset.As printed in the manual: tripped circuit breaker, broken belt, bad indoor fan motor, or incorrect configuration. How to fix →
F600Indoor fan VFD communication. Unit shutdown. Automatic reset.Communication failure, noise on the LEN bus, wiring error, or configuration error.
F601Indoor fan VFD unexpected (VFD reports a fault). Unit shutdown. Automatic reset.VFD fault; refer to the VFD section. Usually needs a manual reset at the VFD.
F602Indoor fan VFD lockout. Unit shutdown. Reset by power cycle.The VFD locked itself out. Cycle power to the VFD.
A603Indoor fan VFD in hand (alert). Automatic reset.VFD keypad put the drive in hand or off mode. Clears when it's back in auto.
F604Indoor fan VFD in hand (fault). Unit shutdown. Automatic reset.VFD keypad put the drive in hand or off mode. Clears when it's back in auto.
A605Indoor fan VFD thermal warning. Fan speed reduced 10%. Automatic reset.Motor wrong size, motor overload, or configuration error.
A606Indoor fan VFD voltage warning. Fan speed reduced. Automatic reset.Motor wrong size, motor overload, or configuration error.
A607Indoor fan VFD current limit. Fan speed reduced. Automatic reset.Motor wrong size, motor overload, or configuration error.
A608Indoor fan VFD warning. Fan speed reduced. Automatic reset.Motor wrong size, motor overload, or configuration error.
F611Indoor fan VFD earth fault. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F612Indoor fan VFD control word loss. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F613Indoor fan VFD over current. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F614Indoor fan VFD motor over temperature. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F615Indoor fan VFD overload. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F616Indoor fan VFD under voltage. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F617Indoor fan VFD over voltage. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F618Indoor fan VFD short circuit. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F619Indoor fan VFD main phase loss. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F620Indoor fan VFD phase U loss. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F621Indoor fan VFD phase V loss. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F622Indoor fan VFD phase W loss. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F623Indoor fan VFD control voltage. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
F624Indoor fan VFD supply VDD. Unit shutdown. Automatic reset.VFD fault; refer to the VFD section of the manual.
A700Economizer not modulating. Alert. Automatic reset.No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix →
A701Economizer stuck closed. Alert. Automatic reset.No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix →
A702Economizer stuck open. Alert. Automatic reset.No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix →
A703Economizer mechanically disconnected. Alert. Manual reset.Damper position changes don't match temperature changes, usually because the actuator isn't secured to the damper shaft. Manual reset so the economizer gets inspected. How to fix →
A710Economizer not cooling. Alert. Automatic reset.No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix →
A711Economizer improper cooling. Alert. Automatic reset.No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix →
A712Excessive outdoor air. Alert. Automatic reset.No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a safety switch to keep a unit running. Gas, line-voltage and three-phase work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Carrier 48/50LC 04-26 with SystemVu Controls Version 4.X, Controls, Start-Up, Operation, and Troubleshooting, S-VU-LC-4-26-03T (2-2020), Faults and Alerts pp. 33-37 and Table 19 pp. 38-40. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.