Carrier 48LC / 50LC SystemVu Controller Version 4.X Rooftop Unit Alarm Codes
| Code | Meaning | What to check |
|---|---|---|
| F010 | MBB low voltage. Unit shutdown. Automatic reset. | Main base board supply below 17 VAC; clears above 19 VAC. Brownout, low supply voltage, or supply power missing a phase. How to fix → |
| F011 | MBB reference voltage. Unit shutdown. Automatic reset. | MBB failure or supply voltage low. |
| A012 | MBB zero crossing. Alert. Automatic reset. | Supply voltage frequency too high or too low, or MBB failure. |
| F013 | MBB fuse 2 open. Unit shutdown. Automatic reset. | Internal fuse 2 overheated: a switch input has a wiring error (short) or the switch drew too much current. Fuse 2 feeds the fire shutdown input and the IGC fan request. |
| F014 | MBB fuse 3 open. Unit shutdown. Automatic reset. | Internal fuse 3 overheated: a switch input has a wiring error or the switch drew too much current. Fuse 3 feeds configurable discrete inputs 12, 13 and 14. |
| A015 | MBB Rnet voltage range. Alert. Automatic reset. | Rnet 12 V output out of range; an accessory on the Rnet plug may not work. MBB failure or supply voltage low. |
| A016 | MBB 24 VDC range. 4-20 mA inputs go into error. Automatic reset. | 24 VDC output below 17 VDC; clears above 19 VDC. MBB failure or supply voltage low. |
| A017 | MBB 5 VDC range. Transducer inputs go into error. Automatic reset. | 5 VDC output below 4.5 VDC. MBB failure or supply voltage low. |
| F018 | MBB EEPROM failure. Unit shutdown. Automatic reset. | Software failure or MBB failure. Try cycling power before replacing the board. |
| A019 | MBB clock failure. No time, date or schedule operation. Automatic reset. | Clock chip not responding; the unit defaults to 24/7 unoccupied. Software or MBB failure. Try cycling power and resetting time and date before replacing the board. |
| F020 | Software error. Unit shutdown. Automatic reset. | Corrupt software or software failure. Try cycling power before replacing the board. |
| A099 | Communication loss with SIOB on LEN bus. Inputs from the I/O board ignored, outputs not controlled. Automatic reset. | Wiring problem between the MBB and the SIOB. |
| A100 | SAT sensor error. No free cooling and no supply air temperature limit protection. Automatic reset. | Faulty, shorted or open thermistor from a wiring error or loose connection. |
| A101 | FST sensor range (fan supply temperature, outside -40 to 245°F). Alert. Automatic reset. | Faulty or incorrect thermistor (improper ohm reading). |
| A102 | FST open sensor. Alert. Automatic reset. | Missing or open thermistor from a wiring error or loose connection. |
| A103 | FST shorted sensor. Alert. Automatic reset. | Faulty or shorted thermistor from a wiring error or loose connection. |
| A104 | OAT sensor range (outside -40 to 245°F). No free cooling, no low ambient operation. Automatic reset. | Ambient lockouts are ignored and the control assumes outdoor temperature is high; the economizer still ventilates. Faulty or incorrect thermistor (improper ohm reading). |
| A105 | OAT open sensor. No free cooling, no low ambient operation. Automatic reset. | Missing or open thermistor from a wiring error or loose connection. |
| A106 | OAT shorted sensor. No free cooling, no low ambient operation. Automatic reset. | Faulty or shorted thermistor from a wiring error or loose connection. |
| A107 | RAT sensor range. No differential dry bulb crossover. Automatic reset. | Free cooling can only use outdoor temperature and the enthalpy switch. Faulty or incorrect thermistor (improper ohm reading). How to fix → |
| A108 | RAT open sensor. No differential dry bulb crossover. Automatic reset. | Missing or open thermistor from a wiring error or loose connection. How to fix → |
| A109 | RAT shorted sensor. No differential dry bulb crossover. Automatic reset. | Faulty or shorted thermistor from a wiring error or loose connection. How to fix → |
| A110 | SPT sensor range (space temperature). No heating or cooling. Automatic reset. | The economizer still ventilates. Faulty thermistor in the T-55, T-56 or T-58 sensor, an open or short from wiring, or a loose connection. |
| A111 | SPT open sensor. No heating or cooling. Automatic reset. | Missing or open thermistor from a wiring error or loose connection. |
| A112 | SPT shorted sensor. No heating or cooling. Automatic reset. | Faulty or shorted thermistor from a wiring error or loose connection. |
| A130 | Circuit A suction pressure sensor range (outside -6.7 to 420 psig). Shuts down circuit A. Automatic reset. | Faulty transducer, faulty 5 V power supply, or loose connection. |
| A131 | Circuit A suction pressure open sensor. Shuts down circuit A. Automatic reset. | Faulty transducer, faulty 5 V power supply, or loose connection. |
| A132 | Circuit A suction pressure shorted sensor. Shuts down circuit A. Automatic reset. | Faulty transducer, faulty 5 V power supply, or loose connection. |
| A133 | Circuit A discharge pressure sensor range (outside 14.5 to 667 psig). Shuts down circuit A. Automatic reset. | Faulty transducer, faulty 5 V power supply, or loose connection. |
| A134 | Circuit A discharge pressure open sensor. Shuts down circuit A. Automatic reset. | Faulty transducer, faulty 5 V power supply, or loose connection. |
| A135 | Circuit A discharge pressure shorted sensor. Shuts down circuit A. Automatic reset. | Faulty transducer, faulty 5 V power supply, or loose connection. |
| A150 | Outdoor airflow (CFM) open sensor. No outdoor air CFM operation. Automatic reset. | Input reads 0 mA with the sensor configured as installed. Wiring problem or configuration error. How to fix → |
| A151 | Outdoor airflow (CFM) shorted sensor. No outdoor air CFM operation. Automatic reset. | Wiring problem or configuration error. How to fix → |
| A160 | Outdoor air RH open sensor. No enthalpy crossover. Automatic reset. | Only dry bulb is used for free cooling. Bad sensor, bad wiring, or sensor configured wrong. How to fix → |
| A161 | Outdoor air RH shorted sensor. No enthalpy crossover. Automatic reset. | Bad sensor, bad wiring, or sensor configured wrong. How to fix → |
| A162 | Return air RH open sensor. No differential enthalpy crossover. Automatic reset. | Bad sensor, bad wiring, or sensor configured wrong. How to fix → |
| A163 | Return air RH shorted sensor. No differential enthalpy crossover. Automatic reset. | Bad sensor, bad wiring, or sensor configured wrong. How to fix → |
| A164 | IAQ open sensor. No IAQ operation. Automatic reset. | Bad sensor, bad wiring, or sensor configured wrong. |
| A165 | IAQ shorted sensor. No IAQ operation. Automatic reset. | Bad sensor, bad wiring, or sensor configured wrong. |
| A166 | OAQ open sensor. No OAQ operation. Automatic reset. | Bad sensor, bad wiring, or sensor configured wrong. |
| A167 | OAQ shorted sensor. No OAQ operation. Automatic reset. | Bad sensor, bad wiring, or sensor configured wrong. |
| A168 | Space relative humidity open sensor. No dehumidifying. Automatic reset. | Bad sensor, bad wiring, sensor configured wrong, or loss of communication to the SIOB. |
| A169 | Space relative humidity shorted sensor. No dehumidifying. Automatic reset. | Bad sensor, bad wiring, sensor configured wrong, or loss of communication to the SIOB. |
| A170 | Economizer feedback range (outside 1.3 to 10.3 VDC). No economizer diagnostics. Automatic reset. | Wiring problem, actuator failure, wrong actuator, or configuration error. Check the feedback signal from the actuator and run a damper calibration. How to fix → |
| A171 | Economizer feedback open. No economizer diagnostics. Automatic reset. | Wiring problem with the actuator or configuration error. How to fix → |
| A172 | Economizer feedback shorted. No economizer diagnostics. Automatic reset. | Wiring problem with the actuator or configuration error. How to fix → |
| A190 | Thermostat heat/cool calls. Runs in the mode that came on first. Automatic reset. | Y1, Y2 or Y3 energized at the same time as W1 or W2. Bad thermostat or thermostat wiring. How to fix → |
| A191 | Thermostat improper cool. Runs cooling by the number of active inputs. Automatic reset. | Y2 or Y3 on without Y1. Bad thermostat or thermostat wiring. How to fix → |
| A192 | Thermostat improper heat. Runs heating by the number of active inputs. Automatic reset. | W2 on without W1. Bad thermostat or thermostat wiring. How to fix → |
| F200 | Fire shutdown. Unit shutdown. Automatic reset. | Smoke detected by the smoke detector (or another device on the fire shutdown input). Check configuration, wiring and the device. |
| F201 | Condensate overflow. Cooling shutdown. Automatic reset. | Drain pan plugged, sensor error, or configuration error. |
| A203 | Dirty filter. Alert. Automatic reset. | Dirty filter or expired filter timer. If the timer tripped it, reset with RESET FILTER TIME under RUN STATUS > GENERAL (or INPUTS > GENERAL INPUTS) after changing the filter. |
| F204 | Remote shutdown. Unit shutdown. Automatic reset. | Remote shutdown switch activated. |
| A210 | General status (alert). Automatic reset. | General switch input activated, or wrong configuration. |
| F211 | General status (fault). Unit shutdown. Automatic reset. | General switch input activated, or wrong configuration. |
| F310 | Circuit A down due to failure. Shuts down circuit A. Manual reset. | Compressors have 3 strikes or were locked out by another alarm. Find the alerts that caused the strikes. Reset from the display or by cycling power. |
| F311 | Circuit A low charge. Shuts down circuit A. Manual reset. | With compressors off, suction and discharge pressure are both below the low charge level while outdoor temperature is above the low charge limit. Low refrigerant or a faulty pressure transducer. |
| A312 | Circuit A unexpected off. Strike for the active compressors. Automatic reset. | Suction pressure jumped and pressure ratio dropped within 10 seconds while running. Compressor failure, open high pressure switch, compressor internal protection, transducer failure, wiring, or nuisance operating conditions. |
| A313 | Circuit A high discharge. Unloads compression and runs outdoor fans at high cool speed. Automatic reset. | Clears when pressure falls 20 psig below the limit. Overcharge, high outdoor ambient with a dirty outdoor coil, plugged filter drier, or outdoor fan speeds set too low. How to fix → |
| A314 | Circuit A high pressure switch trip. Adds compressor strikes. Automatic reset. | Resets when pressure falls and the switch stays closed 3 minutes. Overcharge, high outdoor ambient with a dirty outdoor coil, plugged filter drier, or outdoor fan speeds set too low. How to fix → |
| A315 | Circuit A low discharge. Adds compressor strikes. Automatic reset. | Discharge pressure below outdoor temperature plus the configured offset for 1 minute. Undercharge, low outdoor ambient with a dirty outdoor coil, plugged filter drier, or outdoor fan speeds set too high. |
| A316 | Circuit A low suction. Adds compressor strikes. Automatic reset. | Evaporating temperature below the low suction levels. Low charge, dirty filters, indoor fan turning backward, loose or broken belt, plugged filter drier, faulty transducer, very cold return air, or economizer stuck open in cold weather. How to fix → |
| A317 | Circuit A pressure ratio. Adds compressor strikes. Automatic reset. | Low charge, plugged filter drier, faulty transducer, or low ambient with outdoor fans running too fast. |
| F318 | Compressor stuck on. Unit in safety shutdown. Manual reset. | Suction didn't rise and pressure ratio didn't fall after the compressor was told to stop. Welded contactor or frozen compressor relay on the MBB. How to fix → |
| F319 | Compressor A1 down due to failure. Locks out compressor A1. Manual reset. | A1 has 3 strikes or was locked out by another alarm. |
| A320 | Compressor A1 reverse rotation. Adds a strike for A1. Automatic reset. | 10 seconds after start, suction rose and discharge dropped. Wiring causing reverse rotation, or a faulty compressor. How to fix → |
| A321 | Compressor A1 fail to pressure. Adds a strike for A1. Automatic reset. | 10 seconds after start, suction didn't drop and discharge didn't rise enough. Wiring causing reverse rotation, or a faulty compressor. How to fix → |
| F322 | Compressor A2 down due to failure. Locks out compressor A2. Manual reset. | A2 has 3 strikes or was locked out by another alarm. |
| A323 | Compressor A2 reverse rotation. Adds a strike for A2. Automatic reset. | Wiring causing reverse rotation, or a faulty compressor. How to fix → |
| A324 | Compressor A2 fail to pressure. Adds a strike for A2. Automatic reset. | Wiring causing reverse rotation, or a faulty compressor. How to fix → |
| A410 | IGC ignition failure. Locks out heat. Automatic reset. | No IGC fan request 15 minutes after heat stage 1 came on. Faulty IGC wiring, no gas flow, or wrong configuration. Read the IGC board's LED flash code for detail. How to fix → |
| F411 | Rollout without heat. Unit in safety shutdown. Automatic reset. | IGC fan request came on with heat off for at least 3 minutes; resets 10 minutes after the fan request clears. Faulty IGC wiring, or a rollout switch trip without a heat call. How to fix → |
| F412 | Runaway heat. Unit in safety shutdown. Automatic reset. | Supply air above the maximum; resets when it falls 50°F below the maximum. Heat stuck on, or low airflow. |
| A510 | Indoor fan status. Alert. Automatic reset. | Fan speed feedback didn't follow the command within the VFD ramp time. Broken belt, motor failure, or configuration error. How to fix → |
| F511 | Indoor fan off when commanded on. Unit shutdown. Manual reset. | As printed in the manual: fan stuck on, or incorrect configuration. |
| F512 | Indoor fan on when commanded off. Unit shutdown. Manual reset. | As printed in the manual: tripped circuit breaker, broken belt, bad indoor fan motor, or incorrect configuration. How to fix → |
| F600 | Indoor fan VFD communication. Unit shutdown. Automatic reset. | Communication failure, noise on the LEN bus, wiring error, or configuration error. |
| F601 | Indoor fan VFD unexpected (VFD reports a fault). Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section. Usually needs a manual reset at the VFD. |
| F602 | Indoor fan VFD lockout. Unit shutdown. Reset by power cycle. | The VFD locked itself out. Cycle power to the VFD. |
| A603 | Indoor fan VFD in hand (alert). Automatic reset. | VFD keypad put the drive in hand or off mode. Clears when it's back in auto. |
| F604 | Indoor fan VFD in hand (fault). Unit shutdown. Automatic reset. | VFD keypad put the drive in hand or off mode. Clears when it's back in auto. |
| A605 | Indoor fan VFD thermal warning. Fan speed reduced 10%. Automatic reset. | Motor wrong size, motor overload, or configuration error. |
| A606 | Indoor fan VFD voltage warning. Fan speed reduced. Automatic reset. | Motor wrong size, motor overload, or configuration error. |
| A607 | Indoor fan VFD current limit. Fan speed reduced. Automatic reset. | Motor wrong size, motor overload, or configuration error. |
| A608 | Indoor fan VFD warning. Fan speed reduced. Automatic reset. | Motor wrong size, motor overload, or configuration error. |
| F611 | Indoor fan VFD earth fault. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F612 | Indoor fan VFD control word loss. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F613 | Indoor fan VFD over current. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F614 | Indoor fan VFD motor over temperature. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F615 | Indoor fan VFD overload. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F616 | Indoor fan VFD under voltage. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F617 | Indoor fan VFD over voltage. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F618 | Indoor fan VFD short circuit. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F619 | Indoor fan VFD main phase loss. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F620 | Indoor fan VFD phase U loss. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F621 | Indoor fan VFD phase V loss. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F622 | Indoor fan VFD phase W loss. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F623 | Indoor fan VFD control voltage. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| F624 | Indoor fan VFD supply VDD. Unit shutdown. Automatic reset. | VFD fault; refer to the VFD section of the manual. |
| A700 | Economizer not modulating. Alert. Automatic reset. | No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix → |
| A701 | Economizer stuck closed. Alert. Automatic reset. | No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix → |
| A702 | Economizer stuck open. Alert. Automatic reset. | No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix → |
| A703 | Economizer mechanically disconnected. Alert. Manual reset. | Damper position changes don't match temperature changes, usually because the actuator isn't secured to the damper shaft. Manual reset so the economizer gets inspected. How to fix → |
| A710 | Economizer not cooling. Alert. Automatic reset. | No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix → |
| A711 | Economizer improper cooling. Alert. Automatic reset. | No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix → |
| A712 | Excessive outdoor air. Alert. Automatic reset. | No economizer motion. Check damper blades, gears and actuator, and the actuator direction switch (CCW/CW). Usually comes with a more specific alert; run an economizer calibration in test mode. How to fix → |
How to read the codes
- Codes starting with F are faults; codes starting with A are alerts. On the SystemVu display the yellow ALERT light is lit when alerts are active, the red FAULT light when faults are active, and the green RUN light when the unit is operational.
- View them under ACTIVE FAULTS, ACTIVE ALERTS and HISTORY (active and past alarms with time and date). Each alarm can store up to 3 data points; press ENTER on the alarm to see them.
- Manual-reset alarms are cleared under RESET FAULTS/ALERTS, or by cycling power.
- Main base board (MBB) red LED: blinking once every 2 seconds means correct power; blinking once per second means software isn't loaded; lit steady means replace the board.
- SystemVu also covers other Carrier rooftop lines (48/50FC, FE, HC and others), but alarm lists differ by line and version. Check the controls manual for your unit.
Codes point to a circuit, not a part. Test before replacing anything, and never jumper a safety switch to keep a unit running. Gas, line-voltage and three-phase work is for trained technicians, and refrigerant work requires EPA 608 certification.
Source: Carrier 48/50LC 04-26 with SystemVu Controls Version 4.X, Controls, Start-Up, Operation, and Troubleshooting, S-VU-LC-4-26-03T (2-2020), Faults and Alerts pp. 33-37 and Table 19 pp. 38-40. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- Rooftop unit start-up checks
- Rooftop unit economizer setup and troubleshooting
- Rooftop unit maintenance checklist
Other rooftop unit charts
- Carrier 48FE IGC Board (17.5-27.5 ton packaged rooftop units, gas heat)
- Trane Precedent ReliaTel Direct Spark Ignition Module (gas heat, 3-10 ton packaged rooftop units, model numbers such as YSC060 and YHC092)
- Trane Voyager ReliaTel Hot Surface Ignition Control (gas heat, 12.5-50 ton packaged rooftop units, model numbers such as YSD150, YSD240 and YHH250)
- Lennox Energence / Strategos Prodigy 2.0 M3 Unit Controller (packaged rooftop units, model numbers such as LGH060 and LGH360)
- Carrier 48LC / 50LC 04-06 ComfortLink Controller Version 1.X (packaged rooftop units, R-410A)
- Carrier 48HC / 50HC 04-28 ComfortLink Controller Version 2.X (packaged rooftop units, R-410A)
- Carrier 48PG / 50PG 03-14 and 48PM / 50PM 16-28 ComfortLink Controller Version 5.X (packaged rooftop units, R-410A)