Home / Charts / Carrier rooftop unit codes

Carrier 48HC / 50HC 04-28 ComfortLink Controller Version 2.X Rooftop Unit Alarm Codes

Applies to: Carrier 48HC / 50HC 04-28 ComfortLink Controller Version 2.X (packaged rooftop units, R-410A). Alarm and alert codes on the ComfortLink Scrolling Marquee or Navigator display; Alarm Status light.

CodeMeaningWhat to check
T051Compressor A1 safety trip, or compressor A1 detected after turnoff.Without current sensors this only works if Diagnose Compressor Safety (Configuration > COOL > D.CMP) is Yes; the control watches for suction pressure changes. Safety trip adds a strike for circuit A: high-pressure switch or condensate overflow switch open (both wired in series with the compressor relays), compressor internal protection open, or a wiring error. Detected after turnoff turns off all compressors, stays in cooling mode and keeps the indoor fan on: welded contactor, frozen compressor relay on the MBB, or adverse conditions. Expand the text to see which. How to fix →
T055Compressor B1 safety trip, or compressor B1 detected after turnoff.Same as T051 for circuit B. Safety trip adds a strike for circuit B: high-pressure switch open, compressor internal protection open, or wiring error. Detected after turnoff turns off all compressors: welded contactor. How to fix →
T064Circuit A saturated condensing temperature thermistor failure.Reading outside -40 to 240°F; limited diagnostics. Faulty, shorted or open thermistor, wiring error or loose connection.
T065Circuit B saturated condensing temperature thermistor failure.Same as T064 for circuit B.
T066Circuit A saturated suction temperature thermistor failure.No circuit A cooling. The suction transducer has been turned off internally, usually by a network force on a non-exposed CCN point. Reload factory defaults or reinstall software on the MBB; check with the network manager if it continues.
T067Circuit B saturated suction temperature thermistor failure.No circuit B cooling. Same causes as T066.
T073Outdoor air temperature thermistor failure.Reading outside -40 to 240°F. Ambient lockouts for cooling and heating are ignored; the economizer won't cool but still ventilates. Faulty, shorted or open thermistor or wiring. How to fix →
T074Space temperature thermistor failure.Only if the unit is set for a space sensor; then no heating or cooling (economizer still ventilates). Check the T-55, T-56 or T-58 sensor and wiring.
T075Supply air temperature thermistor failure.No cooling with the economizer and no adaptive compressor staging. Faulty, shorted or open thermistor or wiring. How to fix →
T076Return air thermistor failure.Only if configured for a return air sensor; no economizer differential dry bulb control. Faulty thermistor or wiring. How to fix →
T077Space relative humidity sensor failure.Input below 3.5 mA with the sensor configured; no indoor humidity control. Check sensor and wiring. An ECB must be installed to use the space humidity sensor.
T092Circuit A suction pressure transducer failure.Locks out circuit A; reset with the Scrolling Marquee (manual). The board can't read the transducer voltage: faulty transducer, faulty 5-volt supply, or loose connection.
T093Circuit B suction pressure transducer failure.Locks out circuit B; manual reset. Same causes as T092.
T102Compressor A1 current sensor failure.Only if the unit is configured with current sensors (Configuration > COOL > CIRA > CS.A1); they're field installed. The sensor output is stuck high. Wiring error, loose connection, or configured for a sensor that isn't installed. Set CS.A1 to DISABLE to run while waiting on a replacement board.
T103Compressor B1 current sensor failure.Same as T102 for compressor B1 (CS.B1). (Table 9 in this manual labels it A1; the description text says B1.)
T110Circuit A loss of charge.Locks out circuit A; manual reset. With the compressor off, suction below 5 psig while outdoor air is above -5°F for one minute. Low refrigerant or faulty suction transducer. (Low pressure while running is T133.) How to fix →
T111Circuit B loss of charge.Locks out circuit B; manual reset. Same test and causes as T110. How to fix →
T126Circuit A high discharge pressure.Shuts down circuit A; resets automatically. T051 active while condensing temperature is above 150°F. Overcharge, high outdoor ambient with a dirty outdoor coil, plugged filter drier, or faulty high-pressure switch.
T127Circuit B high discharge pressure.Shuts down circuit B. T055 active while condensing temperature is above 150°F. Same causes as T126.
T133Circuit A low refrigerant pressure.Adds a strike for circuit A. Saturated suction below the low suction levels SST.1, SST.2 or SST.3 (Configuration > COOL > SST) for 5, 4 or 3 minutes (1.5 minutes at level 3 without the economizer), or below SST.3 minus 5°F for 20 seconds. Levels drop 1°F for every 2°F of outdoor air below 40°F; below 10°F outdoor the circuit shuts down without a strike. A frosted coil sets it; the coil should thaw in the 15-minute reset. Low charge, dirty filters, evaporator fan turning backwards, loose or broken belt, plugged filter drier, faulty transducer, very cold return air, or an economizer stuck open in low ambient. How to fix →
T134Circuit B low refrigerant pressure.Adds a strike for circuit B. Same test and causes as T133. How to fix →
T143Circuit A failure to pressurize.Adds a strike for circuit A. Suction pressure didn't drop at least 10 psig in the first 20 seconds of compressor run (5 psig if outdoor air is below 40°F). Wiring causing reverse rotation, or a faulty compressor.
T144Circuit B failure to pressurize.Adds a strike for circuit B. Same test and causes as T143.
T153Real time clock hardware failure.No time and date schedules; unit defaults to 24/7 unoccupied. No time/date configured, software failure or MBB failure. Cycle power and reconfigure the time and date before replacing the board.
A154Serial EEPROM hardware failure.Unit shutdown. Software failure or MBB failure. Cycle power before replacing the board.
T155Serial EEPROM storage failure error.Unit runs on last known good values or defaults, so operating errors may occur. Cycle power and reconfigure the control points before replacing the MBB.
A156Critical serial EEPROM storage fail error.Unit shutdown. Cycle power and reconfigure the critical points, Configuration > COOL > N.CIR (number of circuits) and Configuration > HMZR > REHT (Humidi-MiZer equipped), before replacing the MBB.
A157A/D hardware failure.Unit shutdown. The analog-to-digital chip on the MBB failed. Cycle power before replacing the board.
A163Circuit A down due to failure.Locks out circuit A; manual reset. The circuit has 3 strikes or was locked out by another alarm. Find the alarm that caused the strikes before resetting.
A164Circuit B down due to failure.Locks out circuit B; manual reset. Same as A163 for circuit B.
T173Loss of communication with the Energy Management Module.These units don't support an EMM; an internal force is looking for one. Reload software on the MBB without restoring configurations (use factory configurations first); replace the MBB if it continues.
T175Loss of communication with VFD.Unit shutdown while the indoor fan type (Configuration > I.FAN > FTYP) is set to 1. Resets when communication returns. Wiring problem or incorrect configuration in the VFD or MBB.
T179Loss of communication with the economizer control board (ECB).Economizer disabled. Wiring problem, faulty MBB or ECB, or a humidity sensor configured without an ECB installed. Check the ECB address and resistance between pins on the LEN connections. How to fix →
T180Loss of communication with the economizer actuator.Wiring problem, actuator failure, or wrong actuator (it must be an MFT communicating actuator). If the analog signal is connected the economizer can still be controlled through it. Verify the actuator feedback signal. How to fix →
T181Loss of communication with outside air unit.Outdoor air unit type (Configuration > OAU > OA.TY) is set but the OAU operating mode hasn't been received for 3 minutes; all OAU data resets. Wiring problem or OAU communication failure.
A200Linkage timeout, communication failure.Lost communication with a Linkage device it had talked to since power-up; falls back to local setpoint. If no backup sensor is installed, T074 follows. Reset power and verify Linkage is communicating.
A404Fire shutdown.Unit shutdown. The shutdown input is open or closed (per configuration), usually from a smoke detector. Check the Configuration > UNIT > FS.SW setting, wiring and device.
T408Dirty air filter.Filter status switch sensed a plugged filter for 120 seconds after the fan had run 10 seconds. Check the FL.SW configuration, wiring, and that the hose is on the low side of the switch.
T409Fan status switch on with fan commanded off, or off with fan commanded on.Bad fan status switch or wrong configuration (FN.SW); with fan commanded on, also a tripped breaker, broken belt or bad indoor fan motor. If IDF.F = YES the unit shuts down and needs a manual reset, otherwise it resets automatically. Check the hose is on the high side of the switch.
T410R-W1 jumper not installed in space temp mode, or must be installed to run heat in Service Test.Install the jumper between R and W1 on the terminal board, or confirm space temperature mode is wanted. Remove a Service Test jumper afterward unless the unit runs on a space temperature probe.
T411Thermostat Y2 input activated without Y1.Unit runs as if Y1 and Y2 are both on. Bad thermostat or thermostat wiring. How to fix →
T412Thermostat W2 input activated without W1.Unit runs as if W1 and W2 are both on. Bad thermostat or thermostat wiring. How to fix →
T413Thermostat Y and W inputs activated simultaneously.Unit runs in whichever mode came on first. Bad thermostat or thermostat wiring. How to fix →
T414Economizer fault (ten texts: actuator out of calibration, torque above load limit, hunting excessively, damper stuck or jammed, actuator mechanical failure, direction switch wrong position, excess outdoor air, economizing when it should not, not economizing when it should, damper not modulating).Only when the ECB controls a Belimo actuator digitally (MFT). Run economizer calibration (Service Test > INDP > E.CAL); if it won't clear, power off, loosen the actuator clamp, push the damper closed, tighten and recalibrate. Check damper load, blades and gears; stuck means actual position is off more than 3% for 20 seconds; hunting clears when the stop jog ratio is under 21%; the direction switch goes clockwise with the CW face accessible. Expand the text to see which. How to fix →
T415IAQ input out of range.Input below 3.5 mA with the sensor configured; IAQ operation disabled. Bad sensor, wiring or configuration. How to fix →
T416OAQ input out of range.Input below 3.5 mA with the sensor configured; OAQ operation disabled. Bad sensor, wiring or configuration. How to fix →
T418Outside air unit alarm (four texts: OAU motor failure, OAU dirty filter, OAU low CFM, OAU general alarm).Reported by the OAU (EnergyX) when OA.TY is set; the OAU takes the action and the alert clears when the OAU clears it. Check OAU motors, filters, airflow. With low CFM, a VFD indoor fan and OAU fan boost (EFBE = Yes), the fan steps up a speed every 10 minutes until the alarm clears. See the EnergyX supplemental installation instructions.
A420Supply VFD fault.Unit shuts down if the fan ramps down to 0%. The last VFD fault is under Run Status > S.VFD > LFC. Resets automatically or from the display; see the VFD section of the manual.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a safety switch to keep a unit running. Gas, line-voltage and three-phase work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Carrier 48/50HC 04-28 with ComfortLink Controls Version 2.X, Controls, Start-Up, Operation and Troubleshooting (48-50HC-C04T, edition 05/14), Alarms and Alerts pp. 34-38 and Table 9 ComfortLink Alarm Codes pp. 39-40. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.