Carrier 48FE IGC Board Rooftop Gas Heat Codes
| Code | Meaning | What to check |
|---|---|---|
| On | Normal operation. | |
| Off | Hardware failure. | Loss of power to the IGC. Check the 5 amp fuse on the IGC, power to the unit, the 24-v circuit breaker, the transformer and wiring to the IGC. How to fix → |
| 1 flash | Indoor fan on/off delay modified. Control subtracts 5 seconds from the on delay and adds 5 seconds to the off delay (3 minute maximum). Reset: power reset. | High temperature limit switch opens during the heat exchanger warm-up period before the fan-on delay expires, or opens within 10 minutes of the heat call (W) going off. See the limit switch fault. How to fix → |
| 2 flashes | Limit switch fault. Gas valve and igniter off; indoor fan and inducer on. Resets when the limit switch closes or the heat call (W) is off. | High temperature limit switch is open. Check the indoor (evaporator) fan motor operation. Make sure the supply-air temperature rise is within the range on the unit nameplate. Check wiring and limit switch operation. How to fix → |
| 3 flashes | Flame sense fault. Indoor fan and inducer on. Resets when flame sense is normal; power reset to clear the LED. | The IGC sensed a flame when the gas valve should be closed. Check wiring, flame sensor and gas valve operation. How to fix → |
| 4 flashes | Four consecutive limit switch faults. No gas heating. Reset: heat call (W) off; power reset to clear the LED. | Four consecutive limit switch faults within a single call for heat. See the limit switch fault. How to fix → |
| 5 flashes | Ignition fault. No gas heating. Reset: heat call (W) off; power reset to clear the LED. | Unit unsuccessfully attempted ignition for 15 minutes. Check igniter and flame sensor electrode spacing and gaps. Check flame sense and igniter wiring. Check gas valve operation and gas supply. How to fix → |
| 6 flashes | Induced draft motor / pressure switch fault. If heat is off: no gas heating. If heat is on: gas valve off and inducer on. Resets when inducer sense is normal or the heat call (W) is off. | Inducer sense on when the heat call is off, or inducer sense off when the heat call is on. Check wiring, voltage and operation of the IGC motor. Check the inducer motor and flue gas pressure switch. How to fix → |
| 7 flashes | Rollout switch lockout. Gas valve and igniter off; indoor fan and inducer on. Reset: power reset. | Rollout switch has opened. Check gas valve operation. Check that the induced-draft blower wheel is properly secured to the motor shaft. How to fix → |
| 8 flashes | Internal control lockout. No gas heating. Reset: power reset. | IGC has sensed an internal hardware or software error. If the fault is not cleared by resetting 24-v power, check for a bad gas valve, then replace the IGC. |
| 9 flashes | Temporary software lockout. No gas heating. Resets automatically after one hour, or with a power reset. | Electrical interference is disrupting the IGC software. |
How to read the codes
- Count the LED flashes on the IGC board. There is a 3-second pause between alarm code displays.
- If more than one alarm exists, all of them are displayed in numerical sequence.
- Read the code before shutting off power: IGC alarm codes are lost if power to the unit is interrupted.
- If the flue gas inducer pressure switch is stuck closed on a W1 call, the unit sits idle and the IGC shows no fault code.
Codes point to a circuit, not a part. Test before replacing anything, and never jumper a safety switch to keep a unit running. Gas, line-voltage and three-phase work is for trained technicians, and refrigerant work requires EPA 608 certification.
Source: Carrier 48FE 20-30 Service and Maintenance Instructions, 48FE-20-30-02SM, Table 11 (IGC Board LED Alarm Codes), page 49. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- Rooftop unit start-up checks
- Rooftop unit economizer setup and troubleshooting
- Rooftop unit maintenance checklist
Other rooftop unit charts
- Trane Precedent ReliaTel Direct Spark Ignition Module (gas heat, 3-10 ton packaged rooftop units, model numbers such as YSC060 and YHC092)
- Trane Voyager ReliaTel Hot Surface Ignition Control (gas heat, 12.5-50 ton packaged rooftop units, model numbers such as YSD150, YSD240 and YHH250)
- Lennox Energence / Strategos Prodigy 2.0 M3 Unit Controller (packaged rooftop units, model numbers such as LGH060 and LGH360)
- Carrier 48LC / 50LC 04-06 ComfortLink Controller Version 1.X (packaged rooftop units, R-410A)
- Carrier 48HC / 50HC 04-28 ComfortLink Controller Version 2.X (packaged rooftop units, R-410A)
- Carrier 48PG / 50PG 03-14 and 48PM / 50PM 16-28 ComfortLink Controller Version 5.X (packaged rooftop units, R-410A)
- Carrier 48LC / 50LC SystemVu Controller Version 4.X (sizes 04-26 packaged rooftop units)
Did you find your code?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
HVAC Cheat Sheet · Free PT charts, code lookups and calculators for techs at hvaccheatsheet.com