Lennox Energence / Strategos Prodigy 2.0 M3 Unit Controller Rooftop Unit Alarm Codes

Applies to: Lennox Energence / Strategos Prodigy 2.0 M3 Unit Controller (packaged rooftop units, model numbers such as LGH060 and LGH360). Alarm number on the Prodigy M3 unit controller display.

CodeMeaningWhat to check
1Loss of power detection (single-phase units).Check power connections. The controller sets an "Erratic Power" alarm on power loss and clears it after the Compressor Min OFF Delay; compressors restart after that delay. How to fix →
4Smoke detector input (A173). Closes the service relay.Input is closed. Unit won't run cooling, heating or ventilation. Clears when the input opens. In smoke mode, find the source of smoke.
5Blower S52 (air flow switch). Closes the service relay.Unit off. The normally closed air flow switch is monitored from 16 seconds after the blower starts; if it's open, compressors stop, gas valves close, electric heat and economizer close and the blower stops. Clears after the error off delay. Check blower operation. How to fix →
6Dirty filter switch S27. Closes the service relay.Switch closed. Replace the filter or check switch S27. Clears when the switch opens.
8Strike 3 on blower S52. Closes the service relay.Lockout after repeated alarm 5. Clear through the user interface or by resetting the M3. Check blower operation. How to fix →
12Compressor 1 high pressure S4 or high temperature S5.Compressor off. Check charge, fans and coil. On Energence Ultra-High Efficiency units, alarm 12 alone may point to high temperature switch S5; with alarm 14, more likely the S4 high pressure cutout. Restarts after the switch closes and the minimum off delay.
13Strike 3 on compressor 1 high pressure S4 or high temp S5. Closes the service relay.Check charge, condenser fans and coil. Use the service menu to clear lockouts. Lockout after repeated high pressure trips. Default 3 occurrences, adjustable 1 to 7.
14Compressor 2 high pressure S7.Compressor off. Check charge, fans and coil. On Energence Ultra-High Efficiency tandem units, compressor 2 high temperature S8; with alarm 15, likely the S4 high pressure cutout.
15Strike 3 on compressor 2 high pressure S5 or S7. Closes the service relay.Check charge, condenser fans and coil. Use the service menu to clear lockouts. Lockout after repeated high pressure trips. Default 3 occurrences, adjustable 1 to 7.
16Compressor 3 high pressure S28.Compressor off. Check charge, fans and coil.
17Strike 3 on compressor 3 high pressure S28. Closes the service relay.Check charge, condenser fans and coil. Use the service menu to clear lockouts. Lockout after repeated high pressure trips. Default 3 occurrences, adjustable 1 to 7.
18Compressor 4 high pressure S96.Compressor off. Check charge, fans and coil.
19Strike 3 on compressor 4 high pressure S96. Closes the service relay.Check charge, condenser fans and coil. Use the service menu to clear lockouts. Lockout after repeated high pressure trips. Default 3 occurrences, adjustable 1 to 7.
20Unit shutdown A42.Phase monitor. How to fix →
22Compressor 1 low pressure S87.Compressor off. Check charge, fans and coil.
23Strike 3 on compressor 1 S87. Closes the service relay.Check charge, condenser fans and coil. Use the service menu to clear lockouts. Lockout after repeated low pressure trips. Number of occurrences set by Parameter 99 (default 3).
24Compressor 2 low pressure S88.Compressor off. Check charge, fans and coil.
25Strike 3 on compressor 2 S88. Closes the service relay.Check charge, condenser fans and coil. Use the service menu to clear lockouts. Lockout after repeated low pressure trips. Number of occurrences set by Parameter 99 (default 3).
26Compressor 3 low pressure S98.Compressor off. Check charge, fans and coil.
27Strike 3 on compressor 3 S98. Closes the service relay.Check charge, condenser fans and coil. Use the service menu to clear lockouts. Lockout after repeated low pressure trips. Number of occurrences set by Parameter 99 (default 3).
28Compressor 4 low pressure S97.Compressor off. Check charge, fans and coil.
29Strike 3 on compressor 4 S97. Closes the service relay.Check charge, condenser fans and coil. Use the service menu to clear lockouts. Lockout after repeated low pressure trips. Number of occurrences set by Parameter 99 (default 3).
30Drain pan overflow shutdown (S149). Closes the service relay.Compressors locked out. Check for a blocked drain, condensate lines and the overflow switch. Clears when the switch closes; runs again after the error off delay.
32Compressor 1 freezestat open S49.Compressor off. Check the freezestat, airflow, charge, coil, air filter and outdoor air temperature. How to fix →
33Strike 3 on compressor 1 freezestat S49. Closes the service relay.Compressor locked out. Check the freezestat, airflow, charge, coil, air filter and outdoor air temperature. Occurrences set by Parameter 81 (default 3). How to fix →
34Compressor 2 freezestat open S50.Compressor off. Check the freezestat, airflow, charge, coil, air filter and outdoor air temperature. How to fix →
35Strike 3 on compressor 2 freezestat S50. Closes the service relay.Compressor locked out. Check the freezestat, airflow, charge, coil, air filter and outdoor air temperature. Occurrences set by Parameter 81 (default 3). How to fix →
36Compressor 3 freezestat open S53.Compressor off. Check the freezestat, airflow, charge, coil, air filter and outdoor air temperature. How to fix →
37Strike 3 on compressor 3 freezestat S53. Closes the service relay.Compressor locked out. Check the freezestat, airflow, charge, coil, air filter and outdoor air temperature. Occurrences set by Parameter 81 (default 3). How to fix →
38Compressor 4 freezestat open S95.Compressor off. Check the freezestat, airflow, charge, coil, air filter and outdoor air temperature. How to fix →
39Strike 3 on compressor 4 freezestat S95. Closes the service relay.Compressor locked out. Check the freezestat, airflow, charge, coil, air filter and outdoor air temperature. Occurrences set by Parameter 81 (default 3). How to fix →
40Return air over heat limit RT16.Heat is above set point. Check space conditions and sensors.
41Return air under cool limit RT16.Cool is below set point. Check space conditions and sensors.
42Blower motor overload (S42 or S135) shutdown. Closes the service relay.Overload switch open. Check external motor overloads. Clears when the switch closes; runs again after the error off delay. How to fix →
44Gas valve 1 on with no demand (GV1). Closes the service relay.Unit off. Gas valve 1 has power but there is no heat demand. Check the gas valve and wiring.
45Gas valve 2 on with no demand (GV2). Closes the service relay.Unit off. Gas valve 2 has power but there is no heat demand. Check the gas valve and wiring.
49No 24 VAC on A178 (C3) control.Compressors 3 and 4 off. Clears when 24 VAC returns; runs again after the error off delay (Parameter 110, default 300 seconds).
50Primary heat 1 limit open S10.Heat section 1 primary gas heat limit open. Check airflow, air filter, limit switch and wiring. How to fix →
51Strike 3 primary heat 1 limit open S10. Closes the service relay.Same as alarm 50, number of occurrences reached. How to fix →
52Secondary heat 1 limit open S21.Heat section 1 secondary gas heat limit open. Check airflow, air filter, limit switch and wiring. How to fix →
53Strike 3 secondary heat 1 limit open S21. Closes the service relay.Same as alarm 52, number of occurrences reached. How to fix →
54Heat 1 S15 limit open.Heat section 1 primary electric heat limit open. Check airflow, air filter, limit switch and wiring. How to fix →
55Roll out open. Closes the service relay.Heat section 1 burner flame rollout switch open. Check gas rollout switch S47. How to fix →
56Heat 1 CAI switch S18.Check the heat section 1 combustion air inducer motor and proof switch. How to fix →
57Strike 3 heat 1 CAI switch S18. Closes the service relay.Same as alarm 56, number of occurrences reached. How to fix →
58Heat 1 no proof gas valve GV1.Check heat section 1 ignition control, flame proof, gas valve 1 and gas supply. How to fix →
59Strike 3 no proof gas valve GV1. Closes the service relay.Same as alarm 58, number of occurrences reached. How to fix →
60Primary heat 2 limit open S99.Heat section 2 primary burner limit open. Check airflow, limit switch and wiring. How to fix →
61Strike 3 primary heat 2 limit open S99. Closes the service relay.Same as alarm 60, number of occurrences reached. How to fix →
62Heat 2 limit open S100.Heat section 2 secondary heat limit open. Check airflow, limit switch and wiring. How to fix →
63Strike 3 heat 2 limit open S100. Closes the service relay.Same as alarm 62, number of occurrences reached. How to fix →
65Heat 2 rollout open S69. Closes the service relay.Check the rollout sensor and gas supply. How to fix →
66Heat 2 CAI switch S45.Check the heat section 2 combustion air inducer motor and proof switch. How to fix →
67Strike 3 heat 2 CAI switch S45. Closes the service relay.Same as alarm 66, number of occurrences reached. How to fix →
68Heat 2 no proof gas valve GV2.Check heat section 2 ignition control, flame proof, gas valve 2 and gas supply. How to fix →
69Strike 3 no proof gas valve GV2. Closes the service relay.Same as alarm 68, number of occurrences reached. How to fix →
73Network sensor error.Check with the integrator for refresh rate, network status lights and wiring.
74Zone (room) sensor A2. Closes the service relay.Sensor out of range (including open or short). The unit ignores it, or switches to its backup mode (none, local thermistor or return air temperature). Clears when the reading is back in range. Check the zone sensor and wiring.
75Outdoor temperature sensor (RT17). Closes the service relay.Out of range, including open or short. Clears when back in range. Check sensor and wiring.
76Humidity sensor A91. Closes the service relay.Below 5% RH the reading is ignored; above 100% RH it is limited to 100%. Alarm if low while RH dehumidification is enabled. Check sensor and wiring.
77Discharge air temp sensor RT6. Closes the service relay.Out of range, including open or short. Clears when back in range. Check sensor and wiring.
78Return air temp sensor (RT16). Closes the service relay.Out of range, including open or short. Clears when back in range. Check sensor and wiring.
79Add-on board problem. Closes the service relay.Logged when alarm 80 persists more than 30 seconds after several retries. Cleared only by resetting the M3.
80Add-on board communication problem.The M3 can't communicate with an add-on board (C3, GP3). Retries every 5 seconds; clears when communication returns.
81Reheat setup error.Supermarket reheat set on a non-gas unit, or Humiditrol reheat set on a heat pump. Check reheat settings.
82Controller reset.Logged when the M3 powers up; shows the reason for the reset if known.
83Incorrect settings. Closes the service relay.Check model number and Configuration ID 1 and ID 2. Also set if the model needs a daughter card that isn't detected. Cleared only by reset or power cycle.
85Incorrect Humiditrol settings.Configuration ID 1, position 1 must be N (not installed) or H (Humiditrol). Clears once corrected.
86Conflicting thermostat input. Closes the service relay.Heat and cool calls at the same time. Check thermostat wiring. Resumes after the error off delay. How to fix →
91Outdoor enthalpy sensor A7. Closes the service relay.Sensor failure disables free cooling. Check economizer parameters 160 and 161 and enthalpy parameters 162 and 163, then the sensor and wiring. How to fix →
92Indoor enthalpy sensor A62. Closes the service relay.Sensor failure disables free cooling. Check wiring and test A62 as described in the M3 application guide. How to fix →
93Backup mode. Closes the service relay.Communication lost with the network sensor (or standalone with return air backup). Returns to the primary sensor after a reset, or once the room sensor has been good for 300 seconds.
94Bad zone sensor set point. Closes the service relay.Heating and cooling set points must keep the auto-changeover deadband.
99Outdoor econ sensor A24. Closes the service relay.Reading above 25% of range for more than five minutes with the blower stopped. Disables outdoor air CFM control. Clears when below 10% for one minute. Check sensor and wiring. How to fix →
100Air volume control setup error. Closes the service relay.Check installation of the GP board and its settings.
101MGV control setup error. Closes the service relay.Check installation of the GP board and its settings.
102GP control setup error. Closes the service relay.Check installation of the GP board and its settings.
103Advanced control setup error. Closes the service relay.Check M3 Configuration ID 1 settings.
106Building pressure sensor A34. Closes the service relay.Check sensor and wiring.
107Duct supply pressure sensor A30. Closes the service relay.Set if the signal is above 4.9 in. w.c. for more than 30 seconds, or below 0.1 in. w.c. 20 seconds after the blower starts. Check sensor and wiring. How to fix →
108Duct supply high pressure A30.Supply static exceeded the shutdown set point (Parameter 42) for 20 seconds; unit shuts down for the error off time (Parameter 110). Check sensor and wiring. How to fix →
109Strike 3 duct supply pressure A30. Closes the service relay.Lockout after repeated alarms 107 or 108. Clear through the user interface or reset. Default 3 strikes (Parameter 43, 1 to 7). How to fix →
110Waiting on network data.Check the network or comfort sensor and wiring.
111Profile error.Configuration profile unrecoverable. Settings may have changed.
121Line frequency does not match unit configuration. Closes the service relay.Supply frequency doesn't match the entered model number (Phase/Voltage Detection feature). Needs a power cycle or reset to re-check. How to fix →
12224 VAC primary voltage low. Closes the service relay.T1 transformer output below 18 VAC for more than two seconds. Cooling, heating and ventilation stop. Clears when voltage recovers; demands are ignored until the error off delay expires.
12324 VAC primary voltage high. Closes the service relay.T1 transformer output above the 30 VAC high threshold for more than two seconds. Cooling, heating and ventilation stop until it clears and the error off delay expires.
12424 VAC secondary voltage low. Closes the service relay.Same as alarm 122, on the secondary (18 VAC threshold).
12524 VAC secondary voltage high. Closes the service relay.Same as alarm 123, on the secondary (30 VAC threshold).
126Line phasing does not match unit configuration. Closes the service relay.At power-up or reset: single- vs three-phase mismatch, or reverse rotation on three-phase power. How to fix →
129VFD shutdown. Closes the service relay.VFD fault. Check the belt and blower overload, fix the cause and reset the M3. How to fix →
130VFD bypass engaged.Bypass mode is on. The blower may or may not be disengaged.
132VFD bypass not configured.Bypass not selected; unit runs as if bypass isn't installed.
134Advanced airflow low supply CFM.Airflow target can't be reached. Look for a dirty filter or duct changes. How to fix →
135Advanced airflow no airflow. Closes the service relay.Blower RPM too low: the blower isn't working. Repair the blower and reset the M3.
136Advanced airflow outside air damper/economizer mechanical fault. Closes the service relay.Outdoor air damper stuck or actuator problem. How to fix →
137Advanced airflow low outdoor airflow.Building isn't getting its design outdoor airflow. How to fix →
139Advanced airflow outdoor airflow too high.Ventilation CFM too high; the unit is wasting energy. How to fix →
140Advanced airflow CFM unattainable, target too low.Check the MSAV blower settings and set targets below set CFM.
141Advanced airflow CFM unattainable, target too high.Check the MSAV blower settings and set targets below set CFM.
143Advanced airflow damper pressure error. Closes the service relay.Outdoor air differential pressure reading out of range. Could be a tubing problem or high return duct resistance. How to fix →
146Service logged.A service event was logged.
147OA damper error. Closes the service relay.Damper not modulating during free cooling. How to fix →
148Advanced airflow config error. Closes the service relay.Needs an economizer and an ECM blower.
149Outdoor air differential pressure sensor error. Closes the service relay.Check the outdoor air damper differential pressure sensor and wiring. How to fix →
150Not economizing when outdoor air is suitable. Closes the service relay.May be a damper motor unplugged or disconnected. How to fix →
151Economizing when outdoor air is not suitable. Closes the service relay.May be a damper motor blocked or stuck open. How to fix →
165Economizer not configured.Configuration ID 1, position 2 is U. Select the option in the setup/install wizard. How to fix →
166CAI pressure switch stuck closed GV1.Combustion air proving switch S18 was closed right after the heat demand and before the inducer started. How to fix →
167CAI pressure switch stuck closed GV2.Same as alarm 166, switch S45, gas valve 2. How to fix →
168Combustion air switch not open lockout GV1. Closes the service relay.Locked out after the switch stayed closed the number of times set by Parameter 72 in one cycle. How to fix →
169Combustion air switch not open lockout GV2. Closes the service relay.Same as alarm 168, heat section 2. How to fix →
170Power exhaust not configured.Configuration ID 1, position 3 is U.
171Power exhaust configuration error.If Configuration ID 1 position 3 is set, position 4 must be set too.
173Air flow switch config error.Check Configuration ID 2, position 1.
174Zone (room) bypass damper configuration error.Room bypass only works with cab blowers.
175Invalid load shedding input configuration.The load shedding input is shared with another input (global, blower overload, drain pan overflow).
176SBUS received an obsolete M3 command.A building controller sent an M2-style command. Cleared immediately; logged in history.
177Model number not defined.Run Setup > Install and enter the full model number.
182Ultra: suction pressure sensor error.0-5 VDC sensor, 0-300 psig range. On Energence Ultra-High Efficiency units, a reading below 30 psig is treated as a sensor fault. Value 0 = tandem 1, 1 = tandem 2.
183Ultra: compressor 1 sump temperature sensor error.Open, short or out of the 30-150°F range. Check the sensor and installation.
184Ultra: compressor 2 sump temperature sensor error.Open, short or out of the 30-150°F range. Check the sensor and installation.
186Blower motor fault. Closes the service relay.EBM blower units: motor alarm contact opened after the blower was commanded on; unit stops.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a safety switch to keep a unit running. Gas, line-voltage and three-phase work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Lennox Prodigy 2.0 (M3 Unit Controller) Setup Guide, 507241-07 (5/2022), Table 15, Prodigy 2.0 Alarm and Event Codes, pp. 38-45. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.