Flame Signal Checker
Pick the furnace or ignition control, enter the flame current you measured, and see how it compares with that manufacturer's minimum, low-flame warning point and normal reading.
Minimum 0.5 µA. Normal 4–6 µA. Source: Carrier 58CT-12SI service label, code 34 (see the chart).
Manufacturer flame current figures
Every number comes from the manual cited on the linked chart. All readings are DC microamps (µA).
| Furnace or control | Minimum | Warning below | Normal | Source |
|---|---|---|---|---|
| Carrier 58CTA / 58CTX (two-stage) | 0.5 | – | 4–6 | Carrier 58CT-12SI service label, code 34 |
| Carrier 58STA / 58STX (single-stage) | 0.5 | – | – | Carrier 58ST-24SI service label, code 34 |
| ICP N9MSE (Heil, Tempstar, Comfortmaker, Arcoaire) | 0.5 | – | 4–6 | ICP 440 04 4402 07 service label, code 6 |
| ICP N8MSN / N8MSL | 0.5 | – | 4–6 | ICP 441 01 1402 03 service label, code 6 |
| York TG9S | 0.1 (lockout) | 1.5 | about 3.7 | York 1083287-UIM-L-1219, p. 38 |
| York TM9V | 0.1 (lockout) | 1.5 | about 3.7 | York 1083294-UIM-A-0114, pp. 41-42 |
| Trane / American Standard S9X1 / S9X2 / S9B1 | – | 0.5 | – | Trane FNR-SVX002A-EN, Table 43 |
| Lennox G60DF / G60DFV (older two-stage SureLight boards) | – | 0.2 | – | Lennox SureLight service literature 0222-L7, Table 5 |
| Trane Precedent rooftop, ReliaTel spark ignition | 1.2 | – | about 4.5 | Trane RT-SVD03N-EN, Table 97 |
| Trane Voyager rooftop, ReliaTel hot surface ignition | 1 | – | about 4.5 | Trane RT-SVD03N-EN, p. 138 |
| Honeywell S8610U intermittent pilot module | 1 | – | – | Honeywell S8610U quick reference, 69-2042 |
How to take the reading
- Set the meter to DC microamps. Most furnace boards are read with the meter in series between the flame sensor wire and the sensor terminal; York boards have a flame current test pad.
- Some controls want a different hookup (Honeywell's S8610U guide says not to measure in series with the wiring), so follow the manual for the control in front of you.
- Read it once the flame is steady, not during ignition.
- Fix a weak reading at the cause: an oxidized rod, a poor burner ground, a flame that doesn't fully cover the rod, or low gas pressure. See flame sensor readings and cleaning.
Was this tool useful?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Related tools
Furnace Pressure Switch Checker
Compare the measured draft with the setpoint printed on the switch and see whether it's the switch or the venting.
BTUGas Meter Clocking Calculator
Seconds per meter revolution to furnace input in BTU/h, compared with the rating plate, with the target time to aim for.
SH/SCSuperheat & Subcooling Calculator
Enter your line temps and saturation temps; get superheat and subcooling instantly.
Results are estimates for field reference. Always confirm against the equipment manufacturer's charging chart, installation instructions and local code. Found a problem with this tool? Tell us.