Home / Tools / Gas Heat

Flame Signal Checker

Pick the furnace or ignition control, enter the flame current you measured, and see how it compares with that manufacturer's minimum, low-flame warning point and normal reading.

µA

Minimum 0.5 µA. Normal 4–6 µA. Source: Carrier 58CT-12SI service label, code 34 (see the chart).

Manufacturer flame current figures

Every number comes from the manual cited on the linked chart. All readings are DC microamps (µA).

Furnace or controlMinimumWarning belowNormalSource
Carrier 58CTA / 58CTX (two-stage)0.5–4–6Carrier 58CT-12SI service label, code 34
Carrier 58STA / 58STX (single-stage)0.5––Carrier 58ST-24SI service label, code 34
ICP N9MSE (Heil, Tempstar, Comfortmaker, Arcoaire)0.5–4–6ICP 440 04 4402 07 service label, code 6
ICP N8MSN / N8MSL0.5–4–6ICP 441 01 1402 03 service label, code 6
York TG9S0.1 (lockout)1.5about 3.7York 1083287-UIM-L-1219, p. 38
York TM9V0.1 (lockout)1.5about 3.7York 1083294-UIM-A-0114, pp. 41-42
Trane / American Standard S9X1 / S9X2 / S9B1–0.5–Trane FNR-SVX002A-EN, Table 43
Lennox G60DF / G60DFV (older two-stage SureLight boards)–0.2–Lennox SureLight service literature 0222-L7, Table 5
Trane Precedent rooftop, ReliaTel spark ignition1.2–about 4.5Trane RT-SVD03N-EN, Table 97
Trane Voyager rooftop, ReliaTel hot surface ignition1–about 4.5Trane RT-SVD03N-EN, p. 138
Honeywell S8610U intermittent pilot module1––Honeywell S8610U quick reference, 69-2042

How to take the reading

  • Set the meter to DC microamps. Most furnace boards are read with the meter in series between the flame sensor wire and the sensor terminal; York boards have a flame current test pad.
  • Some controls want a different hookup (Honeywell's S8610U guide says not to measure in series with the wiring), so follow the manual for the control in front of you.
  • Read it once the flame is steady, not during ignition.
  • Fix a weak reading at the cause: an oxidized rod, a poor burner ground, a flame that doesn't fully cover the rod, or low gas pressure. See flame sensor readings and cleaning.

Related tools

Results are estimates for field reference. Always confirm against the equipment manufacturer's charging chart, installation instructions and local code. Found a problem with this tool? Tell us.