Intermittent Pilot Ignition Troubleshooting: Honeywell S8610U Sequence, LED Codes and Checks
Intermittent pilot (IP) ignition was the step between the standing pilot and hot surface ignition. You'll still find it on plenty of older furnaces, boilers, unit heaters and water heaters. The pilot only burns during a call for heat: a module sparks it, proves it, then opens the main valve.
The Honeywell (now Resideo) S8610U is the universal replacement module for many of these systems, so this guide uses it as the example. Other modules work the same way, but timings and codes vary. Always check the appliance's own wiring diagram and the module's instructions.
Safety: The spark lead carries high voltage. Keep the burner door and gas safety checks in place, and leak-test any gas connection you disturb.
How the sequence works
From Resideo's Y8610U retrofit kit instructions (form 68-0291):
- A call for heat powers the module. It runs a self-check.
- The trial for ignition starts: the spark turns on and the pilot valve opens.
- The pilot flame is proved by flame rectification through the igniter-sensor and the burner ground.
- Spark stops. After a 2-second flame stabilization period, the main valve opens.
- If the pilot isn't proved during the trial, the module shuts the pilot valve and spark off (100% shutoff), waits 5 minutes and tries again. This repeats until the pilot lights or the call for heat ends.
- If flame is lost during the run, the module closes both valves and starts a new trial. After more than 5 flame losses in one call for heat, it closes the valves.
The 5-minute wait can be cut short by cycling the thermostat or removing and restoring power.
Prepurge and trial time (DIP switches)
| SW1 | SW2 | Prepurge | Trial for ignition |
|---|---|---|---|
| OFF | OFF | None | 90 seconds (factory default) |
| ON | OFF | 30 seconds | 90 seconds |
| OFF | ON | None | 15 seconds |
| ON | ON | 30 seconds | 15 seconds |
Resideo recommends 0 seconds prepurge and a 90-second trial unless the appliance calls for something else. Set the switches before powering the module.
Read the LED first
The S8610U's green LED tells you where it stopped.
| LED | Meaning | Where to look |
|---|---|---|
| Off | No call for heat | Thermostat, limit, transformer, 24 V at TH-W |
| Fast flash | Power-up self-check | Normal |
| Heartbeat | Normal startup; ignition sequence running | Normal |
| 4 seconds on, then x flashes | Running; x = flame current in µA | Normal |
| 2 flashes | Pilot not proved during the trial; 5-minute retry delay | Gas supply, pilot burner, spark and sense wiring, flame rod, burner ground |
| 3 flashes | Flame lost during run; recycling | Gas supply, pilot burner, sense wiring, dirty flame rod, burner ground |
| 4 flashes | Flame sensed out of sequence | Look for a pilot flame with no call. If present, replace the gas valve. If not, cycle the call; replace the module if it repeats |
| 5 flashes | Vent damper error | Damper plug, wiring and 24 V; replace the damper if needed |
| 6 flashes | Module internal error | Cycle the call; replace the module if it repeats |
| 7 flashes | Flame rod shorted to ground | Sense lead, rod position, cracked or tracking ceramic |
| 8 flashes | Low 24 V supply | Transformer and line voltage under full load |
No spark
- Confirm 24 V at TH-W (and GND) on a call for heat. No voltage: check the thermostat, limits, transformer and wiring upstream.
- Arc test: pull the ignition cable at the module and hold it near the SPARK terminal (insulated pliers). Resideo's guide: an arc of 1/8 inch (3 mm) or longer means the module's output is fine. No arc, or an arc shorter than 1/8 inch, means check the module's external fuse and power at its input; if they're good, replace the module.
- Good arc at the module but none at the pilot: check the ignition cable for cracks and continuity, the ceramic insulator for cracks, and the electrode position.
Spark, but the pilot won't light
- Manual gas valves open and inlet pressure to spec. See furnace gas pressure check.
- On a new install or after a repair, recycle the call a few times to purge air from the pilot tube.
- Check the pilot orifice for blockage (spiders and lint are common).
- Measure 24 VAC across the pilot valve terminals (PV to MV/PV) during the trial. No voltage: replace the module. Voltage but no pilot gas: replace the gas valve.
Pilot lights, but the spark doesn't stop
The module isn't seeing the flame.
- Check continuity of the ignition cable and the ground wire. The igniter-sensor, module and pilot burner need a common ground through the GND (BURNER) terminal to the burner bracket.
- Clean the flame rod and check its ceramic for cracks.
- The pilot flame should be steady, blue and wrap 3/8 to 1/2 inch of the flame rod. Adjust the pilot if it's lazy or lifting.
- Measure flame current (below). If everything checks out and it still won't prove, replace the module.
Pilot lit, main burner won't come on
- Check the connections between module and gas valve.
- Measure 24 V at the main valve (MV to MV/PV) after the pilot is proved. Voltage present with no main flame: replace the gas valve. No voltage with a proven pilot: replace the module.
- If the main valve stays open after the call ends, remove the MV lead at the module. If the valve closes, recheck the thermostat and wiring. If not, replace the gas valve.
Measuring flame current
Resideo's technician quick reference (69-2042) for the S8610U:
- Measure with the pilot lit and no main gas: disconnect the MV lead first.
- Use the DC microamp scale with correct polarity. The guide says not to measure in series with the wiring; follow its meter hookup.
- Minimum: a steady 1 µA DC. Recommended: 2 µA or more for reliable operation.
In run mode the LED also reports flame current: after 4 seconds on, it flashes once per microamp.
For more on flame rectification, see flame sensor microamps and cleaning.
Replacing an old module with the S8610U
The S8610U is a universal replacement for many Honeywell, Robertshaw, Penn-Johnson, Fenwal and other IP modules, but not all of them. Check the replacement table in its instructions before you swap. Don't use it to replace a module that isn't listed unless you're sure the specs match (lockout type, timings, pilot flow rate up to 1,500 Btuh). Label each wire before you pull it.
Common mistakes
- Replacing the module for a ground problem. A loose or corroded burner ground is the most common reason a pilot lights but won't prove.
- Calling 2 flashes a dead module. It's waiting out its 5-minute retry.
- Measuring flame current with main gas on. Measure on pilot only.
- Ignoring the vent damper. On boilers with a damper, a damper fault (5 flashes) stops the sequence.
- Changing DIP switches with power on.
FAQ
What's the difference between intermittent pilot and standing pilot?
A standing pilot burns all the time and is proved by a thermocouple or thermopile. An intermittent pilot lights only on a call for heat, sparked and proved by an electronic module. See standing pilot thermocouple troubleshooting.
Why does my boiler spark but never light?
Usually no pilot gas (closed valve, air in the line, blocked orifice) or a pilot valve that isn't opening. Check for 24 V at the pilot valve terminals during the trial.
Why does it keep sparking after the pilot is lit?
The module can't sense the flame: a dirty or misplaced flame rod, a cracked ceramic, a bad cable, or a poor burner ground.
How long does the S8610U wait between tries?
5 minutes after a failed trial, as long as the call for heat remains.
Sources
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
Related guides
Furnace Ignition Lockout: Failed Ignition Troubleshooting Step by Step
Diagnose a furnace that tries to light and locks out by following the ignition sequence: inducer, pressure switch, igniter, gas valve, flame sense.
Standing Pilot Won't Stay Lit: Thermocouple Testing on Older Furnaces and Boilers
How a standing pilot and thermocouple work on older furnaces, boilers and water heaters, how to test the thermocouple with open-circuit and closed-circuit millivolt readings, and what else makes a pilot go out.
Furnace Blowing Cold Air: A Diagnostic Order That Finds It Fast
Why a gas furnace blows cold or lukewarm air, in the order to check it: thermostat fan setting, lockouts, flame proving, limits, gas supply, and duct leaks.
Furnace Gas Valve Not Opening: Igniter Glows but No Flame
How to tell whether a furnace that glows or sparks but never lights has a bad gas valve, a board that isn't sending 24 volts, a closed gas supply or a pressure problem, with the checks in order.
Field reference for trained technicians. Always follow the equipment manufacturer's instructions, local code and safe work practices. See our editorial standards, or report a correction.