Rheem / Ruud RA20 Air Conditioner Codes
The (-) stands for the brand prefix (Rheem or Ruud). The RP20 heat pump uses the same control and a nearly identical list; see its own chart.
| Code | Meaning | What to check |
|---|---|---|
| d1 | No model data. | Replace the memory card with one that has the correct system information. |
| L8 | Compressor model unknown (A900 inverter identity fault). | Check the model data card is properly connected. Cycle power: remove power until all the lights on the inverter are out, then restore power to the inverter, then the ICC. Replace the model data card. |
| 09 | Low secondary volts: 24 V at R and C below 18 VAC. | Control transformer overloaded, or low line voltage. How to fix → |
| L15 | Inverter fault (T901, A903, A904, A905, A908, A909, A910, T911, T914, T917, T918, T922): overcurrent, DC bus voltage, temperature or lost rotor position. | Check high-voltage connections at the terminal block, filter and inverter are tight; the inverter communication cable connection; the U/V/W output wires; no short in the filter or choke; input voltage between 187 and 252 VAC; outdoor airflow and fan; the inverter heat sink for debris. Replace the model data card; if none of that fixes it, replace the drive. How to fix → |
| L16 | Inverter fault (A912, A913, A919, A920, A921, A929): microprocessor, sensor or internal communication. | Power cycle; verify all lights on the inverter are off before restoring power. Check the U/V/W output wires, charge level, and continuity of the discharge line thermistor and its connection at the drive. If none of that fixes it, replace the drive. How to fix → |
| L17 | Discharge line temperature (T916 inverter fault). | Outdoor ambient above 125°F or below 0°F: let conditions change before restarting. Check charge level and discharge thermistor continuity (10k thermistor; see the 10k thermistor chart). How to fix → |
| L18 | Communication failure between inverter and ICC (A915). | Check the communication cable connection, its shielding at the connector, and that the crimp terminals in the ICC-to-inverter cable are fully inserted. |
| 21 | Low pressure control open. Ignored for the first 90 seconds of compressor operation. | Low refrigerant charge; frozen or dirty indoor coil or filter, or indoor blower not running (cooling); frozen outdoor coil (heating); expansion valve not operating correctly. How to fix → |
| 21L | Low-pressure control trip lockout: the LPC opened 3 times in the same cooling operation. Flashes L and 21. | Same causes as 21. The ICC has locked out the compressor to protect it. How to fix → |
| 27 | AC input under voltage (A907 inverter fault). | Check incoming line voltage to the disconnect and unit, and wiring connections. |
| 28 | AC input over voltage (A906 inverter fault). | Check line voltage. |
| 29 | High-pressure control open (T923 inverter fault). | Outdoor coil dirty or outdoor fan not running (cooling); indoor coil or filter dirty or indoor blower not running (heating); liquid line restriction; excessive refrigerant charge. How to fix → |
| 29L | High-pressure control trip lockout (A923): the HPC opened 3 times in the same cooling operation. Flashes L and 29. | Same causes as 29. The ICC has locked out the compressor to protect it. How to fix → |
| 31 | Compressor envelope protection (T902 inverter fault): compressor operating outside its envelope. | Check charge level; refrigerant migration may have caused a high compression ratio; above 110°F or below 0°F outdoors the ratio may be too high for low speed. Demand increases automatically under the control center and the system restarts; the ICC clears this fault and restarts on its own. How to fix → |
| L31 | Compressor envelope protection lockout (T902 inverter fault): compressor outside its operating envelope. | Check charge level. Outdoor ambient above 125°F: let the unit cool and condensing pressure drop before restarting. Cycle power to restart. How to fix → |
| L32 | Compressor temperature thermistor failure (A902 inverter fault). | Check thermistor continuity. The compressor thermistor is a 10k thermistor; see the 10k thermistor chart. |
| L33 | The manual's description reads "compressor envelope protection lockout, T902", but its check is for the evaporator thermistor. | Check evaporator thermistor continuity (10k thermistor; see the 10k thermistor chart). Also check charge level if it repeats. |
| L36 | Suction pressure sensor failure (A956). | Check the transducer harness for continuity, 5 Vdc constant between black and red at the sensor, and the return voltage between black and green at the control board. PSIG = (375 × (Vout/Vin) − 22.8) − 14.7. If the voltages convert to a pressure matching your gauges, replace the control; if not, replace the harness and/or transducer. |
| L42 | Compressor temperature thermistor failure (T955). | Check thermistor continuity. The compressor thermistor is a 10k thermistor; see the 10k thermistor chart. |
| 83 | Condenser coil temperature fault: abnormally low or high reading. | Replace the sensor; check it is installed correctly on the control. How to fix → |
| 84 | Outdoor ambient temperature fault (T952). | If the unit is in a high-temperature area, wait for the ambient to drop and recheck. Replace the sensor; check it is installed correctly on the control. |
| 93 | Configuration data restore failure (A950): the control is not functioning properly. | Check the control for proper operation; replace the control. |
How to read the codes
- Read the display from the correct side; the manual warns codes read upside down otherwise.
- Letters show the current call: c first-stage cooling, C second-stage cooling, 0 standby. A flashing letter means an anti-short-cycle timer (3 minutes) or minimum run timer (30 seconds) is active; press TEST to skip the delay.
- Codes shown as L followed by a number (L15, L16...) are lockouts: the display flashes L, then the number. Many must be reset manually.
- Fault recall: hold SW2 and TEST together for 5–8 seconds; the display shows FC (fault codes). Press SW2 to enter a menu, TEST to move to the next one.
Source: Rheem Variable Speed R-410A Air Conditioning Outdoor Units Installation Instructions (RA20), 92-104921-12 Rev. 00, ICC Diagnostic Codes, pp. 54-57. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- How the heat pump defrost cycle works
- Checking heat pump charge in heat mode
- Look up any heat pump code
Other brands
- Lennox XP17 (Dave Lennox Signature two-stage heat pump, heat pump control A175)
- Lennox SL25XPV (Dave Lennox Signature variable-capacity heat pump, R-410A)
- Trane 5TWR4 (single-stage heat pump: 5TWR4018A1000A to 5TWR4060A1000A)
- Carrier 25HNB6 / 25HNB9 (Infinity two-stage heat pump, Puron)
- Carrier 25HNA6 / 25HNA9 (Infinity two-stage heat pump, Puron)
- Rheem / Ruud RP20 (EcoNet variable-speed heat pump, models (-)P20; e.g. RP2024AJVCA)
- Goodman / Amana AVZC18 (Amana inverter heat pump, ComfortNet communicating)
- Goodman / Amana GSZC18 (Goodman two-stage heat pump, ComfortNet compatible)
- Goodman / Amana AVZC20 (Amana inverter heat pump, ComfortNet communicating)
- Goodman / Amana AVXC20 / GVXC20 (inverter air conditioner, ComfortNet communicating)