Home / Charts / Rheem / Ruud air conditioner codes

Rheem / Ruud RA20 Air Conditioner Codes

Applies to: Rheem / Ruud RA20 (EcoNet variable-speed air conditioner, models (-)A20). Dual seven-segment display on the EcoNet variable-speed unitary control (ICC).

The (-) stands for the brand prefix (Rheem or Ruud). The RP20 heat pump uses the same control and a nearly identical list; see its own chart.

CodeMeaningWhat to check
d1No model data.Replace the memory card with one that has the correct system information.
L8Compressor model unknown (A900 inverter identity fault).Check the model data card is properly connected. Cycle power: remove power until all the lights on the inverter are out, then restore power to the inverter, then the ICC. Replace the model data card.
09Low secondary volts: 24 V at R and C below 18 VAC.Control transformer overloaded, or low line voltage. How to fix →
L15Inverter fault (T901, A903, A904, A905, A908, A909, A910, T911, T914, T917, T918, T922): overcurrent, DC bus voltage, temperature or lost rotor position.Check high-voltage connections at the terminal block, filter and inverter are tight; the inverter communication cable connection; the U/V/W output wires; no short in the filter or choke; input voltage between 187 and 252 VAC; outdoor airflow and fan; the inverter heat sink for debris. Replace the model data card; if none of that fixes it, replace the drive. How to fix →
L16Inverter fault (A912, A913, A919, A920, A921, A929): microprocessor, sensor or internal communication.Power cycle; verify all lights on the inverter are off before restoring power. Check the U/V/W output wires, charge level, and continuity of the discharge line thermistor and its connection at the drive. If none of that fixes it, replace the drive. How to fix →
L17Discharge line temperature (T916 inverter fault).Outdoor ambient above 125°F or below 0°F: let conditions change before restarting. Check charge level and discharge thermistor continuity (10k thermistor; see the 10k thermistor chart). How to fix →
L18Communication failure between inverter and ICC (A915).Check the communication cable connection, its shielding at the connector, and that the crimp terminals in the ICC-to-inverter cable are fully inserted.
21Low pressure control open. Ignored for the first 90 seconds of compressor operation.Low refrigerant charge; frozen or dirty indoor coil or filter, or indoor blower not running (cooling); frozen outdoor coil (heating); expansion valve not operating correctly. How to fix →
21LLow-pressure control trip lockout: the LPC opened 3 times in the same cooling operation. Flashes L and 21.Same causes as 21. The ICC has locked out the compressor to protect it. How to fix →
27AC input under voltage (A907 inverter fault).Check incoming line voltage to the disconnect and unit, and wiring connections.
28AC input over voltage (A906 inverter fault).Check line voltage.
29High-pressure control open (T923 inverter fault).Outdoor coil dirty or outdoor fan not running (cooling); indoor coil or filter dirty or indoor blower not running (heating); liquid line restriction; excessive refrigerant charge. How to fix →
29LHigh-pressure control trip lockout (A923): the HPC opened 3 times in the same cooling operation. Flashes L and 29.Same causes as 29. The ICC has locked out the compressor to protect it. How to fix →
31Compressor envelope protection (T902 inverter fault): compressor operating outside its envelope.Check charge level; refrigerant migration may have caused a high compression ratio; above 110°F or below 0°F outdoors the ratio may be too high for low speed. Demand increases automatically under the control center and the system restarts; the ICC clears this fault and restarts on its own. How to fix →
L31Compressor envelope protection lockout (T902 inverter fault): compressor outside its operating envelope.Check charge level. Outdoor ambient above 125°F: let the unit cool and condensing pressure drop before restarting. Cycle power to restart. How to fix →
L32Compressor temperature thermistor failure (A902 inverter fault).Check thermistor continuity. The compressor thermistor is a 10k thermistor; see the 10k thermistor chart.
L33The manual's description reads "compressor envelope protection lockout, T902", but its check is for the evaporator thermistor.Check evaporator thermistor continuity (10k thermistor; see the 10k thermistor chart). Also check charge level if it repeats.
L36Suction pressure sensor failure (A956).Check the transducer harness for continuity, 5 Vdc constant between black and red at the sensor, and the return voltage between black and green at the control board. PSIG = (375 × (Vout/Vin) − 22.8) − 14.7. If the voltages convert to a pressure matching your gauges, replace the control; if not, replace the harness and/or transducer.
L42Compressor temperature thermistor failure (T955).Check thermistor continuity. The compressor thermistor is a 10k thermistor; see the 10k thermistor chart.
83Condenser coil temperature fault: abnormally low or high reading.Replace the sensor; check it is installed correctly on the control. How to fix →
84Outdoor ambient temperature fault (T952).If the unit is in a high-temperature area, wait for the ambient to drop and recheck. Replace the sensor; check it is installed correctly on the control.
93Configuration data restore failure (A950): the control is not functioning properly.Check the control for proper operation; replace the control.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a pressure switch to keep a unit running. Line-voltage work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Rheem Variable Speed R-410A Air Conditioning Outdoor Units Installation Instructions (RA20), 92-104921-12 Rev. 00, ICC Diagnostic Codes, pp. 54-57. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.