Lennox XP17 Heat Pump Codes

Applies to: Lennox XP17 (Dave Lennox Signature two-stage heat pump, heat pump control A175). Four LEDs on the heat pump control (A175): DS11 green and DS14 red for system faults, DS15 yellow and DS13 red for compressor faults.

Other Lennox heat pumps with the same A175 heat pump control show similar LED codes, but check the unit's own installation instructions. Communicating systems show the alert number on the icomfort Touch thermostat.

CodeMeaningWhat to check
105Device communication failure (no LED code).The icomfort Touch thermostat can't communicate with another device on the RSBus. Only occurs if the device communicated after power-up and was later lost. Possible causes: lost connection, bus short or open, or another device stopped responding.
120Unresponsive device (no LED code).A device on the RSBus did not get the expected response from another device. Normally indicates a device malfunction.
124Active subnet controller missing (no LED code).Device lost connection to the icomfort Touch thermostat (no heartbeat for three minutes). Normally a lost connection to the thermostat, or the thermostat is not working.
125Hardware failure (no LED code).Entire or partial system failure. Clears 300 seconds after the fault has recovered.
126Internal control communication failure (no LED code).Internal communication on the heat pump control. Clears 300 seconds after the fault has recovered.
131Corrupted control parameters (no LED code).Stored configuration data is corrupted. System will not run.
132Failed flash CRC check (no LED code).No operation; the control enters boot loader mode. Clears after reset.
180Ambient sensor problem (DS11 and DS14 fast flashes together).Sensor open, shorted or out of range. The control reverts to time/temperature defrost. The system will still heat or cool.
400Compressor internal overload trip (DS15 yellow off, DS13 red on).Y1 demand is present but the compressor is not running. Check: compressor protector open (high head pressure, compressor supply voltage); outdoor disconnect open; compressor breaker or fuses open; broken wire or connector; low or high pressure switch open (if present); contactor failed to close. Clears after current is sensed in the run and start windings for two seconds, service removed, or power reset. How to fix →
401Long run time (yellow 1 flash then pause, red off).Compressor running extremely long cycles. Check: low charge; indoor blower not running; frozen evaporator coil; faulty metering device (TXV bulb, stuck TXV or orifice); dirty condenser coil; liquid line restriction (filter drier); thermostat problem. Clears after 30 consecutive normal run cycles or power reset. How to fix →
402System pressure trip (yellow 2 flashes then pause, red off).Compressor protector open or missing supply power. Check: high head pressure (high pressure switch, overcharge, non-condensables); condenser coil airflow; condenser fan not running (capacitor, wiring, motor); return duct leakage. Clears after four consecutive normal run cycles or power reset. How to fix →
403Short cycling (yellow 3 flashes then pause, red off).Compressor running less than three minutes. Check for an intermittent thermostat demand signal, a defective time delay relay or heat pump control, and (if a high pressure switch is present) the causes for code 402. Clears after four consecutive normal run cycles or power reset.
404Locked rotor (yellow 4 flashes then pause, red off).Compressor locked out: run capacitor failed, low line voltage (check wiring), excessive liquid refrigerant in the compressor, or seized bearings. Clears after power reset or four normal compressor cycles. How to fix →
405Open circuit (yellow 5 flashes then pause, red off).Compressor has an open circuit. Check: outdoor disconnect open; breaker or fuses open; contactor failed to close (wiring, burned or pitted contacts, low pilot voltage at the coil); high pressure switch open and needs manual reset; open compressor supply wiring; long compressor protector reset in extreme ambient; damaged windings (check winding resistance). Clears after one normal run cycle or power reset. How to fix →
406Open start circuit (yellow 6 flashes then pause, red off).Current not sensed by the start transformer. Check the run capacitor, wiring to the compressor S terminal, and start winding resistance. Clears when amperage is sensed in RUN and START, or power reset.
407Open run circuit (yellow 7 flashes then pause, red off).Current not sensed by the run transformer. Check wiring to the compressor R terminal and winding resistance. Clears when amperage is sensed in RUN and START, or power reset.
408Welded contactor (yellow 8 flashes then pause, red off).Compressor always runs. The contactor failed to open, or the thermostat demand signal is not connected to the module. Clears after one normal run cycle or power reset. How to fix →
409Secondary low voltage (yellow 9 flashes then pause, red off).24 V is below 18 VAC. Check for an overloaded control transformer and low line voltage. Clears after voltage is above 20 VAC for two seconds, or power reset.
410Low pressure fault (DS11 green off, DS14 red slow flash).Check for restricted airflow over the indoor or outdoor coil, improper charge (check with approach and subcooling), the metering device, and pressure switch and sensor connections. How to fix →
411Low pressure switch lockout (green off, red on).Same checks as 410. How to fix →
412High pressure fault (green slow flash, red off).Check for blockages on the coils and fans, indoor and outdoor fan motor current, system charge (approach and subcooling), and operating pressures against the charging charts. How to fix →
413High pressure switch lockout (green on, red off).Same checks as 412. How to fix →
414Discharge line temperature fault (green slow flash, red on).Discharge line above 279°F (137°C) during compressor operation. The control turns off the compressor contactor (and defrost output if active) until the discharge temperature drops below 225°F (107°C). How to fix →
415Discharge line temperature lockout (green fast flash, red on).See 414. How to fix →
417Discharge sensor fault (green off, red fast flash) or coil sensor problem (alternating fast flash).The table lists alert 417 for both. Discharge sensor: open, short or out of range after 90 seconds of running. Coil sensor: open or shorted, and the control will not perform defrost. Check the sensor resistance and connections. How to fix →
418W output hardware fault (green 3 fast flashes then pause, red off).Auxiliary heat output detected as active when it shouldn't be. Fault in the heat pump control; replace the control.
419W output hardware fault lockout (green 3 fast flashes then pause, red on).Five W output hardware fault events in a single cooling demand. The control locks out.
421W external miswire fault (green off, red 3 fast flashes then pause).Auxiliary heat output detected as active after the compressor has been de-energized. Check the W wiring.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a pressure switch to keep a unit running. Line-voltage work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Lennox XP17 Installation Instructions, 506586-01, Tables 14 and 15, pp. 40-44. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.