Lennox XP17 Heat Pump Codes
Other Lennox heat pumps with the same A175 heat pump control show similar LED codes, but check the unit's own installation instructions. Communicating systems show the alert number on the icomfort Touch thermostat.
| Code | Meaning | What to check |
|---|---|---|
| 105 | Device communication failure (no LED code). | The icomfort Touch thermostat can't communicate with another device on the RSBus. Only occurs if the device communicated after power-up and was later lost. Possible causes: lost connection, bus short or open, or another device stopped responding. |
| 120 | Unresponsive device (no LED code). | A device on the RSBus did not get the expected response from another device. Normally indicates a device malfunction. |
| 124 | Active subnet controller missing (no LED code). | Device lost connection to the icomfort Touch thermostat (no heartbeat for three minutes). Normally a lost connection to the thermostat, or the thermostat is not working. |
| 125 | Hardware failure (no LED code). | Entire or partial system failure. Clears 300 seconds after the fault has recovered. |
| 126 | Internal control communication failure (no LED code). | Internal communication on the heat pump control. Clears 300 seconds after the fault has recovered. |
| 131 | Corrupted control parameters (no LED code). | Stored configuration data is corrupted. System will not run. |
| 132 | Failed flash CRC check (no LED code). | No operation; the control enters boot loader mode. Clears after reset. |
| 180 | Ambient sensor problem (DS11 and DS14 fast flashes together). | Sensor open, shorted or out of range. The control reverts to time/temperature defrost. The system will still heat or cool. |
| 400 | Compressor internal overload trip (DS15 yellow off, DS13 red on). | Y1 demand is present but the compressor is not running. Check: compressor protector open (high head pressure, compressor supply voltage); outdoor disconnect open; compressor breaker or fuses open; broken wire or connector; low or high pressure switch open (if present); contactor failed to close. Clears after current is sensed in the run and start windings for two seconds, service removed, or power reset. How to fix → |
| 401 | Long run time (yellow 1 flash then pause, red off). | Compressor running extremely long cycles. Check: low charge; indoor blower not running; frozen evaporator coil; faulty metering device (TXV bulb, stuck TXV or orifice); dirty condenser coil; liquid line restriction (filter drier); thermostat problem. Clears after 30 consecutive normal run cycles or power reset. How to fix → |
| 402 | System pressure trip (yellow 2 flashes then pause, red off). | Compressor protector open or missing supply power. Check: high head pressure (high pressure switch, overcharge, non-condensables); condenser coil airflow; condenser fan not running (capacitor, wiring, motor); return duct leakage. Clears after four consecutive normal run cycles or power reset. How to fix → |
| 403 | Short cycling (yellow 3 flashes then pause, red off). | Compressor running less than three minutes. Check for an intermittent thermostat demand signal, a defective time delay relay or heat pump control, and (if a high pressure switch is present) the causes for code 402. Clears after four consecutive normal run cycles or power reset. |
| 404 | Locked rotor (yellow 4 flashes then pause, red off). | Compressor locked out: run capacitor failed, low line voltage (check wiring), excessive liquid refrigerant in the compressor, or seized bearings. Clears after power reset or four normal compressor cycles. How to fix → |
| 405 | Open circuit (yellow 5 flashes then pause, red off). | Compressor has an open circuit. Check: outdoor disconnect open; breaker or fuses open; contactor failed to close (wiring, burned or pitted contacts, low pilot voltage at the coil); high pressure switch open and needs manual reset; open compressor supply wiring; long compressor protector reset in extreme ambient; damaged windings (check winding resistance). Clears after one normal run cycle or power reset. How to fix → |
| 406 | Open start circuit (yellow 6 flashes then pause, red off). | Current not sensed by the start transformer. Check the run capacitor, wiring to the compressor S terminal, and start winding resistance. Clears when amperage is sensed in RUN and START, or power reset. |
| 407 | Open run circuit (yellow 7 flashes then pause, red off). | Current not sensed by the run transformer. Check wiring to the compressor R terminal and winding resistance. Clears when amperage is sensed in RUN and START, or power reset. |
| 408 | Welded contactor (yellow 8 flashes then pause, red off). | Compressor always runs. The contactor failed to open, or the thermostat demand signal is not connected to the module. Clears after one normal run cycle or power reset. How to fix → |
| 409 | Secondary low voltage (yellow 9 flashes then pause, red off). | 24 V is below 18 VAC. Check for an overloaded control transformer and low line voltage. Clears after voltage is above 20 VAC for two seconds, or power reset. |
| 410 | Low pressure fault (DS11 green off, DS14 red slow flash). | Check for restricted airflow over the indoor or outdoor coil, improper charge (check with approach and subcooling), the metering device, and pressure switch and sensor connections. How to fix → |
| 411 | Low pressure switch lockout (green off, red on). | Same checks as 410. How to fix → |
| 412 | High pressure fault (green slow flash, red off). | Check for blockages on the coils and fans, indoor and outdoor fan motor current, system charge (approach and subcooling), and operating pressures against the charging charts. How to fix → |
| 413 | High pressure switch lockout (green on, red off). | Same checks as 412. How to fix → |
| 414 | Discharge line temperature fault (green slow flash, red on). | Discharge line above 279°F (137°C) during compressor operation. The control turns off the compressor contactor (and defrost output if active) until the discharge temperature drops below 225°F (107°C). How to fix → |
| 415 | Discharge line temperature lockout (green fast flash, red on). | See 414. How to fix → |
| 417 | Discharge sensor fault (green off, red fast flash) or coil sensor problem (alternating fast flash). | The table lists alert 417 for both. Discharge sensor: open, short or out of range after 90 seconds of running. Coil sensor: open or shorted, and the control will not perform defrost. Check the sensor resistance and connections. How to fix → |
| 418 | W output hardware fault (green 3 fast flashes then pause, red off). | Auxiliary heat output detected as active when it shouldn't be. Fault in the heat pump control; replace the control. |
| 419 | W output hardware fault lockout (green 3 fast flashes then pause, red on). | Five W output hardware fault events in a single cooling demand. The control locks out. |
| 421 | W external miswire fault (green off, red 3 fast flashes then pause). | Auxiliary heat output detected as active after the compressor has been de-energized. Check the W wiring. |
How to read the codes
- Find the LED pattern, then use the alert number listed with it. On an icomfort Touch (communicating) system, the thermostat shows the same alert number.
- A fast flash is 1/2 second and a slow flash 1 second. The pause is 2 seconds.
- Status, not faults: DS11 and DS14 flashing slowly together is normal operation. Alternating slow flash is the 5-minute anti-short-cycle delay (jumper the FIELD TEST pins to override). Both off is no 24 V at R and C, or a failed control. Both on solid means the control has an internal failure: cycle 24 V, and replace the control if it does not clear.
- Running status on DS11/DS14: green off with red 1 fast flash = first-stage heating; green on with red 2 fast flashes = defrost; green 1 fast flash with red off = first-stage cooling; green 2 fast flashes with red on = dehumidification.
- Codes clear automatically once the condition is gone, or manually by disconnecting R at the control or turning the indoor unit off and on. After power-up the existing code shows for 60 seconds, then clears.
- The DS15/DS13 compressor codes are a monitoring function only. They do not provide safety protection and cannot shut anything down.
- Alerts 400 and 409 start as moderate and become critical if the alarm lasts more than 10 minutes.
Source: Lennox XP17 Installation Instructions, 506586-01, Tables 14 and 15, pp. 40-44. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- How the heat pump defrost cycle works
- Checking heat pump charge in heat mode
- Look up any heat pump code
Other brands
- Lennox SL25XPV (Dave Lennox Signature variable-capacity heat pump, R-410A)
- Trane 5TWR4 (single-stage heat pump: 5TWR4018A1000A to 5TWR4060A1000A)
- Carrier 25HNB6 / 25HNB9 (Infinity two-stage heat pump, Puron)
- Carrier 25HNA6 / 25HNA9 (Infinity two-stage heat pump, Puron)
- Rheem / Ruud RP20 (EcoNet variable-speed heat pump, models (-)P20; e.g. RP2024AJVCA)
- Rheem / Ruud RA20 (EcoNet variable-speed air conditioner, models (-)A20)
- Goodman / Amana AVZC18 (Amana inverter heat pump, ComfortNet communicating)
- Goodman / Amana GSZC18 (Goodman two-stage heat pump, ComfortNet compatible)
- Goodman / Amana AVZC20 (Amana inverter heat pump, ComfortNet communicating)
- Goodman / Amana AVXC20 / GVXC20 (inverter air conditioner, ComfortNet communicating)