Trane 5TWR4 Heat Pump Codes

Applies to: Trane 5TWR4 (single-stage heat pump: 5TWR4018A1000A to 5TWR4060A1000A). Status and fault LEDs on the demand defrost control (DFC) in the outdoor unit control box.

Other Trane and American Standard heat pumps with demand defrost controls use flash codes too, but older boards use a different list. Check the Service Facts in the unit's control box.

CodeMeaningWhat to check
1 flashAmbient temperature sensor out of range (open or shorted).The control goes into an adaptive timed limp mode: it forces a defrost after every 60 minutes of heating runtime and ends it on coil temperature. Clears when the sensor fault is fixed. Check the sensor against the resistance table in the manual. How to fix →
2 flashCoil temperature sensor out of range (open or shorted).Timed limp mode: defrost after every 60 minutes of heating runtime. The table says a 15-minute forced defrost; the notes below it say the defrost ends after 5 minutes. Clears when the sensor fault is fixed. If both sensors fail, the control forces a 5-minute defrost every 60 minutes. How to fix →
3 flashLow pressure switch open.Goes away if and when the LPCO closes. How to fix →
4 flashHard lockout.After the 9th LPCO trip. Can only be cleared by cycling low-voltage power. During hard lockout the X2 relay opens so the Y signal doesn't pass through. How to fix →
5 flashSoft lockout.Goes away when the soft lockout period ends. See the LPCO lockout periods above. How to fix →
6 flashDefrost cycles too close together.A heating short cycle fault (defrost within 15 minutes of heating, or two defrosts with less than 15 minutes of heating between them) puts the control in adaptive limp mode for up to 10 heating cycles, then it returns to demand defrost. Trane lists condenser fan motor failure and low charge among the causes. How to fix →
7 flashLow ambient soft lockout.Outdoor temperature at or below -12°F. Once ambient drops that low, the control waits 5 minutes, then soft-locks; during the lockout Y passes through to X2 (for auxiliary heat). The fault table says it turns back on at 3°F; the notes and the quick-specs table say -3°F. LPCO should reset around 5°F.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a pressure switch to keep a unit running. Line-voltage work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Trane Heat Pumps 5TWR4 Installation, Operation, and Maintenance, ODR-SVX004D-EN (April 2026), Tables 14-17 and notes, pp. 25-26. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.