Home / Charts / Lennox heat pump codes

Lennox SL25XPV Heat Pump Codes

Applies to: Lennox SL25XPV (Dave Lennox Signature variable-capacity heat pump, R-410A). Seven-segment display on the outdoor control; red and green LEDs on the inverter flash a matching inverter code.

Other Lennox variable-capacity communicating outdoor units use similar E-codes, but the list varies by model. Check the unit's own service literature.

CodeMeaningWhat to check
E105Lost communication with the thermostat or indoor unit (Service Soon).Check for miswired or loose connections between the thermostat, indoor unit and outdoor unit, and for a high-voltage noise source near the system. Most cases are electrical noise; keep high voltage away from the RSBus. Clears when communication is restored.
E120Delay in the outdoor unit responding (Service Soon).Usually clears on its own. Check all wiring connections. Clears when the unresponsive device responds.
E124S30 thermostat lost communication with the outdoor unit for more than 3 minutes (Service Urgent).Stops all HVAC operation until the signal returns. Check wiring connections and resistance, and cycle system power.
E125Hardware problem with the outdoor control (Service Urgent).Replace the outdoor control if the problem prevents operation and persists. Clears 300 seconds after the fault recovers.
E131Outdoor control parameters corrupted (Service Urgent).Reconfigure the system. Replace the control if heating or cooling is not available.
E132Internal software error (Service Urgent).Replace the outdoor control.
E180Outdoor ambient temperature sensor malfunction (Service Soon).The control will not perform low-ambient cooling. Compare sensor resistance to the temperature/resistance charts in the installation instructions and replace the sensor pack if needed. Clears on configuration or when normal values are sensed.
E181Suction pressure transducer fault (Service Soon).Signal should be 0.5-4.5 VDC between blue and black. Clears when the proper signal returns. On a conventional 24 VAC heat pump thermostat the unit runs in staged mode.
E182Suction temperature sensor malfunction (Service Soon).Check the sensor per the installation and service procedure. Nominal 10K ohms at 77°F.
E183Liquid pressure transducer fault (Service Soon).Signal should be 0.5-4.5 VDC between blue and black. On a conventional 24 VAC heat pump thermostat the unit runs in stage mode.
E345"O" relay on the outdoor control has failed (Service Urgent).The pilot relay contacts didn't close, the relay coil didn't energize, or the circuit that confirms it isn't sensing properly.
E409Secondary voltage 18 VAC or less (Service Soon).After 10 minutes, operation stops. Check indoor line voltage and transformer output. Clears when voltage is above 20 VAC for 2 seconds, or after a power reset.
E410Low suction pressure (Service Soon).Cut-out 25 psig, cut-in 40 psig. Check charge, TXV, indoor blower motor, dirty filters, clogged refrigerant filter, and that the evaporator coil is clean. Clears when pressure rises above 40 psig. How to fix →
E411Low pressure lockout: 5 trips within one hour (Service Urgent).Same checks as E410. Clears after a power reset. How to fix →
E412High pressure switch opened (Service Soon).Opens at 590 psig, closes at 418 psig. Check charge, clogged TXV, indoor blower motor, clogged filter drier, and that the outdoor unit is clean. In heating, indoor CFM may be set too low (or zone CFM on a zoned system). How to fix →
E413High pressure lockout: 5 trips within one hour (Service Urgent).Same checks as E412, plus the condenser fan motor and a stuck reversing valve. Clears after a power reset. How to fix →
E416Outdoor coil sensor malfunction (Service Soon / Urgent).The SL25XPV has a fixed 10K ohm resistor on the harness connector between pins 5 and 6. Check connections there and for 10K ohms. Occurs on an open or shorted circuit.
E422Compressor top cap switch over its thermal limit (Service Soon).The top of the compressor is hot. Charge may be low or refrigerant flow low. Check the TXV, filter drier, condenser fan motor and indoor blower motor, and that the indoor coil is clean. How to fix →
E423Inverter circuit problem. Inverter code 40; inverter LED red 4 flashes, green off.Locks out after 10 strikes in an hour. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on.
E424Liquid line temperature sensor malfunction (Service Soon).Check connections at pins 3 and 4 of the four-pin liquid/suction temperature plug (bottom left of the control) and the resistance: nominal 10K ohms at 77°F. Occurs on an open or short.
E425Minimum compressor speed raised for oil return in low ambient (dealer information only).Adjustments begin at 45°F, reaching 100% minimum at 17°F. Clears automatically when the outdoor temperature stays above the limit for more than 5 minutes.
E426Excessive inverter alarms (Service Urgent).Ten faults within one hour lock out the control. Review the alarm history. Check the condenser fan motor, TXV, indoor blower motor, over- or undercharge, and clogged refrigerant filter. Inverter alarms 12-14 and 53 don't count toward this lockout. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on.
E427DC peak fault (55 A or higher). Inverter code 21; red 2 flashes, green 1.Compressor and fan stop and an anti-short cycle starts; 10 times in an hour locks out. Indicates high pressure, condenser fan failure, locked compressor rotor or overcharge. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on. How to fix →
E428High main input current. Inverter code 22; red 2, green 2.Five times in an hour locks out. Indicates high pressure, condenser fan failure or overcharge. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on. How to fix →
E429DC link voltage didn't rise. Inverter code 23; red 2, green 3.On a compressor call, DC link voltage didn't reach 180 VDC (2- and 3-ton) or 250 VDC (4- and 5-ton) within 30 seconds, or the inverter capacitors aren't charging. Ten times in 60 minutes locks out. Check main power to the outdoor unit and for loose connections.
E430Compressor start failure. Inverter code 26; red 2, green 6.Ten times in an hour locks out. Indicates a poor connection at the compressor harness, improper winding resistance, locked rotor or flooded compressor. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on.
E431PFC over-current (100 A). Inverter code 27; red 2, green 7.Ten times in 60 minutes locks out. Causes: power interruption, brownout, poor connection or loose inverter input wire; or, during system testing, the reversing valve de-energized coming out of defrost without the 30-second compressor delay. Check main power and connections. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on.
E432DC link high voltage (over 480 VDC). Inverter code 28; red 2, green 8.Ten times in an hour locks out. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on.
E433Compressor over-current (peak phase current over 28 A). Inverter code 29; red 2, green 9.The inverter shows code 14 first and slows down; if current stays high the compressor and fan stop. Five times in an hour locks out. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on.
E434Outdoor control lost communication with the inverter for more than 3 minutes. Inverter code 53; red 5, green 3.Compressor stops; locks out after 60 minutes without communication. Causes: outdoor disconnect off while indoor power is on, loose power connections, main power interrupted, or a generator powering the indoor unit but not the outdoor. Reset by cycling indoor power off and on. Check the disconnect, connections and 230 V supply.
E435Inverter internal error. Inverter code 60; red 6, green off.The control cycles inverter power by opening the contactor for two minutes; after three cycles it locks out. Check that the EEPROM is properly seated. Replace the inverter if it persists.
E436Inverter heat sink over temperature. Inverter code 62; red 6, green 2.The inverter shows code 13 first and slows down; five times in an hour locks out. Check for an outdoor fan not running or a heat sink blocked with debris. Lennox also notes loose screws between the inverter board and heat sink: wait five minutes for the capacitor to discharge, then tighten them. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on.
E437Heat sink temperature sensor fault. Inverter code 65; red 6, green 5.Sensor reads below 4°F (the causes column prints 0.4°F) or above 264°F after 10 minutes of operation. Five times in an hour locks out. Replace the inverter if it persists. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on.
E438PFC over-current. Inverter code 73; red 7, green 3.Caused by high load, high pressure or outdoor fan failure. After 3 minutes the inverter resets and the compressor restarts; 10 times in 60 minutes locks out. Check for high pressure trips or other alerts. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on. How to fix →
E439Compressor slowdown, high input current. Inverter code 12; red 1, green 2.Information only: the inverter briefly drops about 4 Hz (5-6%) and resumes normal operation.
E440Heat sink temperature approaching limit. Inverter code 13; red 1, green 3.Information only: the compressor slows when the heat sink passes 167°F and resumes at 150°F. Normal for 3-4 minutes in high outdoor temperatures (above 110°F). If it's frequent at lower temperatures, check the finned heat sink on the back of the inverter for debris or anything blocking airflow.
E441Compressor slowdown, high compressor current. Inverter code 14; red 1, green 4.Information only. Typical at startup, and can occur at high operating pressures. Usually needs no service.
E442Top cap switch opened five times within one hour; unit locked out (Service Urgent).See E422. To clear: turn off power to the indoor unit (the 24 VAC source for the outdoor control), which powers off the control and opens the contactor to the inverter, then turn it back on. How to fix →
E443Incorrect unit size code selected (Service Urgent).Check the unit size code configuration. If the inverter was replaced, check the inverter model matches the unit size. Clears after a reset once the match is correct. Remove the thermostat while applying power and reprogramming.
E600Compressor cycled off by utility load shedding (dealer information only).Activated by 24 VAC on the L and C terminals of the outdoor control.
E601Low temperature protection (dealer information only).The outdoor unit won't start at or below -4°F. If already running when the temperature drops below -4°F, it continues until the thermostat is satisfied or it reaches -15°F.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a pressure switch to keep a unit running. Line-voltage work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Lennox SL25XPV Unit Information, Corp. 100026 (June 1, 2022), Table 6 and Figure 22, pp. 39-44. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.