Home / Charts / Carrier heat pump codes

Carrier 25HNA6 / 25HNA9 Heat Pump Codes

Applies to: Carrier 25HNA6 / 25HNA9 (Infinity two-stage heat pump, Puron). Amber STATUS light on the outdoor control board, two-digit status codes.

Several codes apply to only one of the two models (25HNA6 or 25HNA9); those rows say which. The newer 25HNB6 / 25HNB9 has a shorter list and its own chart.

CodeMeaningWhat to check
16System communications failure.Communication with the User Interface lost. Check wiring to the User Interface and the indoor and outdoor units.
25Invalid model plug.Control does not detect a model plug or detects an invalid one. The unit will not operate without the correct model plug.
31High pressure switch open.High-pressure switch trip. Check refrigerant charge, outdoor fan operation and coils for airflow restrictions. How to fix →
32Low pressure switch open.Low-pressure switch trip. Check refrigerant charge and indoor airflow. How to fix →
45Control fault.Outdoor unit control board has failed and needs to be replaced.
46Brown out (230 V).Line voltage below 187 V for at least 4 seconds. Compressor and fan are not allowed until voltage is 190 V or more. Verify line voltage.
47No 230 V at unit.No 230 V at the contactor when the indoor unit is powered and there is a cooling or heating demand. Verify the disconnect is closed and 230 V wiring is connected to the unit. How to fix →
53Outdoor air temperature sensor fault.Sensor not reading or out of range. Ohm out the sensor and check wiring.
55Outdoor coil sensor fault.Sensor not reading or out of range. Ohm out the sensor and check wiring. How to fix →
56Thermistors out of range.Improper relationship between the coil sensor and outdoor air sensor. Ohm out both sensors and check wiring.
71Low stage thermal cutout.Compressor operation detected, then lost, while low stage demand exists. Possible causes: internal compressor overload trip, or start relay and capacitor held in the circuit too long (if installed). How to fix →
72High stage thermal cutout.Compressor operation detected, then lost, while high stage demand exists. Possible causes: internal compressor overload trip, or start relay and capacitor held in the circuit too long (if installed). How to fix →
73Contactor shorted.Compressor voltage sensed with no demand for compressor operation. Contactor may be stuck closed, or there is a wiring error. How to fix →
74No 230 V at compressor (25HNA9 only).Compressor voltage not sensed when the compressor should be starting. Contactor may be stuck open, or there is a wiring error. How to fix →
75Low stage did not start (25HNA6 only).Specified start voltage at the VR terminal was not achieved in low stage. Start relay was de-energized after 1 second. How to fix →
76Low stage did not start 3 times (25HNA6 only).For 3 consecutive low stage starts, the specified start voltage at the VR terminal was not achieved and the start relay was de-energized. Low stage is locked out for 30 minutes. How to fix →
77High stage did not start (25HNA6 only).Specified start voltage at the VS terminal was not achieved in high stage. Start relay was de-energized after 1 second. How to fix →
78High stage did not start 3 times (25HNA6 only).For 3 consecutive high stage starts, the specified start voltage at the VS terminal was not achieved and the start relay was de-energized. High stage is locked out for 30 minutes. How to fix →
81Low stage thermal lockout.Thermal cutout in three consecutive low/high stage cycles. Low stage is locked out for 4 hours or until 24 V power is recycled. How to fix →
82High stage thermal lockout.Thermal cutout in three consecutive high/low stage cycles. High stage is locked out for 4 hours or until 24 V power is recycled. How to fix →
83Low-pressure lockout.Low pressure switch trip during 3 consecutive cycles. Unit is locked out for 4 hours or until 24 V power is recycled. How to fix →
84High-pressure lockout.High pressure switch trip during 3 consecutive cycles. Unit is locked out for 4 hours or until 24 V power is recycled. How to fix →
85Low contactor open (25HNA6 only).Compressor voltage not sensed when the compressor should be starting. Low stage contactor may be stuck open, or there is a wiring error. How to fix →
87High contactor open (25HNA6 only).Compressor voltage not sensed when the compressor should be starting. High stage contactor may be stuck open, or there is a wiring error. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a pressure switch to keep a unit running. Line-voltage work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Carrier 25HNA Infinity Series Heat Pump Installation Instructions, 25HNA-5SI, Table 6 Troubleshooting, p. 14. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.