Home / Charts / Goodman / Amana heat pump codes

Goodman / Amana AVZC18 Heat Pump Codes

Applies to: Goodman / Amana AVZC18 (Amana inverter heat pump, ComfortNet communicating). Seven-segment display on the outdoor control board (E codes), with matching messages on the ComfortNet thermostat.

Other Goodman, Amana and Daikin inverter outdoor units use a similar E-code list, but it varies by model. Check the unit's own installation and service reference.

CodeMeaningWhat to check
E11 / 11Run system test (RUN SYS TEST).Message only. The system test is incomplete or still running. Run EQUIP TEST and SYSTEM TEST from the ComfortNet thermostat's menu; the display clears when testing is complete.
E12 / 12Outdoor control failure 1 (OD CTRL FAIL1): general memory error.High electrical noise or a faulty control board. Replace the control board if necessary.
E13 / 13High pressure, critical (HI PRESSURE C): frequent high pressure faults.Blocked or restricted condenser coil or lines, stop valve not completely open, overcharge, outdoor fan not running, high pressure switch inoperable, faulty indoor EEV or EEV coil, faulty control board. How to fix →
14High pressure, minor (HI PRESSURE M).Shown at the thermostat only (ClimateTalk code 14); nothing on the outdoor board display. The control has decided the unit can keep running. Same causes as E13. How to fix →
E15 / 15Low pressure, critical (LOW PRESSURE C): frequent low pressure faults.Stop valve not completely open, restriction in refrigerant lines, low charge, refrigerant leak, low pressure sensor inoperable or not connected, indoor fan motor not working correctly, faulty indoor EEV or EEV coil, faulty control board. How to fix →
16Low pressure, minor (LOW PRESSURE M).Shown at the thermostat only (ClimateTalk code 16); nothing on the outdoor board display. The control has decided the unit can keep running. Same causes as E15. How to fix →
E17 / 17Compressor failure (COMPRESSOR FAIL): frequent compressor faults.Stop valve not completely open, compressor wire has lost a phase, compressor motor failure. Check the wiring between the control board and compressor. How to fix →
E20 / 20EEV open circuit (EEV OPEN CKT).Outdoor EEV coil not connected, or faulty outdoor EEV coil.
E21 / 21EEV control failure (EEV CTRL FAIL): frequent low discharge superheat faults.Thermistors inoperable or improperly connected, faulty indoor or outdoor EEV or EEV coil, overcharge, faulty pressure sensor, faulty control board.
E22 / 22High discharge temperature (HI DISCH TEMP).Discharge thermistor inoperable, improperly connected or out of position; low refrigerant charge; overcharge; faulty compressor. How to fix →
E23 / 23Discharge temperature sensor failure (DISCH TEMP FAIL): sensor out of range.Discharge thermistor inoperable or improperly connected. Check its resistance and connections.
E24 / 24High pressure switch open (HPS OPEN).High pressure switch inoperable. Check resistance on the switch to verify operation.
E25 / 25Outdoor air sensor fault (AIR SENSOR FLT): sensor open or shorted.Faulty outdoor thermistor or disconnected.
E26 / 26Pressure sensor (PRESSURE SENSOR): sensor not reacting properly.Low pressure sensor inoperable or not properly connected.
E28 / 28Outdoor coil temperature sensor failure (COIL TEMP FAIL2): sensor out of range.Outdoor coil thermistor inoperable or not properly connected.
E29 / 29Liquid temperature sensor failure (LIQ TEMP FAIL): sensor out of range.Liquid thermistor inoperable or not properly connected.
E30 / 30Outdoor control failure 3 (OD CTRL FAIL3): the control board may need to be replaced.Wiring to the control board disconnected, faulty control board, or electrical noise. Check wiring first.
E32 / 32High temperature on the outdoor control board (HI TEMP CTRL1).Ambient too high; cooling bracket screws missing or loose; no or poor thermal grease between the cooling plumbing and bracket on the control board; no or limited flow through the board cooling circuit (restriction or low refrigerant); stop valve not completely open.
33High temperature on the outdoor control board, minor (HI TEMP CTRL2).Shown at the thermostat only (ClimateTalk code 33); nothing on the outdoor board display. The control has decided the unit can keep running. Same causes as E32.
E34 / 34Current spike (CURRENT SPIKE): high current, potential short circuit.Current spike in supply, stop valve not completely open, compressor wire has lost a phase, faulty control board, faulty compressor. How to fix →
E35 / 35High current (HIGH CURRENT).Short circuit condition, stop valve not completely open, overcharge, faulty control board, faulty compressor. Check installation clearances. How to fix →
E36 / 36Startup error (STARTUP ERROR): abnormal condition during startup.Blocked or restricted condenser coil or lines, compressor wire has lost a phase, inconsistent compressor load, faulty control board.
E37 / 37Outdoor control failure 4 (OD CTRL FAIL4): the control board may need to be replaced.Faulty control board.
E38 / 38Compressor voltage (COMP VOLTAGE): voltage issue with the compressor.High or low supply voltage, compressor wire has lost a phase, faulty control board.
E39 / 39Outdoor control failure 5 (OD CTRL FAIL5): the control board may need to be replaced.Thermistors inoperable or improperly connected, or faulty control board. Check thermistor connections first.
E40 / 40Compressor mismatch (COMP MISMATCH): compressor requirement differs from compressor capability.Memory card not correct, or control board mismatch. Check memory card data and control board size against the unit model.
E41 / 41Low refrigerant (LOW REFRIGERANT).Refrigerant leak, low charge, or thermistors inoperable or not properly connected. How to fix →
E42 / 42Low line voltage (LOW LINE VOLT).Low supply voltage. Check breakers and fuses and that the supply matches the rating plate.
E43 / 43High line voltage (HIGH LINE VOLT).High supply voltage. Verify the supply matches the rating plate.
E44 / 44Operating temperature range (OP TEMP RANGE): outdoor temperature outside the recommended range. Unit may continue to operate normally.Ambient too high or too low. Cycle power and retry within the usable ambient range.
E45 / 45No cooling test (NO COOLING TEST): cooling mode test can't start because indoor heat is on.Heat from a secondary heating source. Turn the heater off at the thermostat before running the test.
E47 / 47No system verification test (NO SYS VER TEST): test can't start because indoor heat is on.Turn the heater off at the thermostat first.
E48 / 48No pump down (NO PUMP DOWN): pump down mode can't start because indoor heat is on.Turn the heater off at the thermostat first.
E49 / 49No charge mode (NO CHARGE MODE): charging mode can't start because indoor heat is on.Turn the heater off at the thermostat first.
E50 / 50Line voltage control (LINE VOLT CTRL): voltage issue on the control board.High or low supply voltage, or faulty control board.
E51 / 51Outdoor communication error (OD COMM ERROR).Communication wiring disconnected. Check communication wiring. How to fix →
52Compressor failure, minor (COMP FAIL MINOR).Shown at the thermostat only (ClimateTalk code 52); nothing on the outdoor board display. The control has decided the unit can keep running. Stop valve not completely open, compressor wire has lost a phase, or compressor motor failure. How to fix →
54EEV minor (EEV MINOR): frequent low discharge superheat faults.Shown at the thermostat only (ClimateTalk code 54); nothing on the outdoor board display. The control has decided the unit can keep running. Thermistors inoperable or improperly connected, faulty indoor EEV or EEV coil, faulty control board.
55High discharge temperature, minor (HI DIS TEMP MIN).Shown at the thermostat only (ClimateTalk code 55); nothing on the outdoor board display. The control has decided the unit can keep running. Same causes as E22. How to fix →
E56 / 56Suction temperature sensor failure (SUCT TEMP FAIL): sensor out of range.Suction thermistor inoperable or not properly connected.
57Cooling loop sweat (CL LOOP SWEAT): sweating sensed on the control board cooling loop.Shown at the thermostat only (ClimateTalk code 57); nothing on the outdoor board display. The control has decided the unit can keep running. Refrigerant leak, low charge, faulty indoor EEV or EEV coil, thermistors inoperable or improperly connected.
Eb0No indoor airflow (NO ID AIRFLOW): estimated airflow from the indoor unit is near 0 CFM.Failed indoor blower motor, indoor fan motor not properly connected, or too much static pressure. How to fix →
Eb9Low indoor airflow (LOW ID AIRFLOW): estimated airflow is lower than required.Failed indoor blower motor, indoor fan motor not properly connected, or too much static pressure. How to fix →
Ed0No network data (NO NET DATA): the control board doesn't have the data it needs.Wired as part of a communicating system and the integrated control module contains no shared data. Replace the control board if necessary.
Ed1Invalid data (INVALID DATA).The integrated control module contains invalid shared data, or network data is invalid for it. Replace the control board if necessary.
Ed2System mismatch (SYSTEM MISMATCH): airflow requirement is greater than the indoor unit can deliver.Outdoor unit needs more airflow than the indoor unit's capability, shared data incompatible or missing parameters, loose communication wiring, or an indoor unit without an EEV.

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a pressure switch to keep a unit running. Line-voltage work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Amana AVZC18 Heat Pump Installation & Service Reference, IOA-4016B, Troubleshooting, pp. 30-33. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.