Carrier 25HNB6 / 25HNB9 Heat Pump Codes

Applies to: Carrier 25HNB6 / 25HNB9 (Infinity two-stage heat pump, Puron). Amber STATUS light on the outdoor control board, two-digit status codes.

Other Carrier and Bryant two-stage outdoor units use similar two-digit status codes, but the list varies by model and board. Check the unit's own installation instructions.

CodeMeaningWhat to check
16System communications failure.Communication with the User Interface lost. Check wiring to the User Interface and the indoor and outdoor units.
25Invalid model plug.Control does not detect a model plug or detects an invalid one. The unit will not operate without the correct model plug.
31High pressure switch open.High-pressure switch trip. Check refrigerant charge, outdoor fan operation and coils for airflow restrictions. How to fix →
32Low pressure switch or discharge temperature switch open.Check refrigerant charge and indoor airflow. How to fix →
45Control fault.Outdoor unit control board has failed and needs to be replaced.
46Brown out (230 V).Line voltage below 187 V for at least 4 seconds. Compressor and fan are not allowed until voltage is 190 V or more. Verify line voltage.
47No 230 V at unit.No 230 V at the contactor when the indoor unit is powered and there is a cooling or heating demand. Verify the disconnect is closed and 230 V wiring is connected to the unit. How to fix →
53Outdoor air temperature sensor fault.Sensor not reading or out of range. Ohm out the sensor and check wiring.
55Outdoor coil sensor fault.Sensor not reading or out of range. Ohm out the sensor and check wiring. How to fix →
56Thermistors out of range.Improper relationship between the coil sensor and outdoor air sensor. Ohm out both sensors and check wiring.
71Low stage thermal cutout.Compressor operation detected, then lost, while low stage demand exists. Possible causes: internal compressor overload trip, or start relay and capacitor held in the circuit too long (if installed). How to fix →
72High stage thermal cutout.Compressor operation detected, then lost, while high stage demand exists. Possible causes: internal compressor overload trip, or start relay and capacitor held in the circuit too long (if installed). How to fix →
73Contactor shorted.Compressor voltage sensed with no demand for compressor operation. Contactor may be stuck closed, or there is a wiring error. How to fix →
74No 230 V at compressor.Compressor voltage not sensed when the compressor should be starting. Contactor may be stuck open, or there is a wiring error. How to fix →
81Low stage thermal lockout.Thermal cutout in three consecutive cycles. Low stage is locked out for 4 hours or until 24 V power is recycled. How to fix →
82High stage thermal lockout.Thermal cutout in three consecutive cycles. High stage is locked out for 4 hours or until 24 V power is recycled. How to fix →
83Low-pressure lockout.Low pressure switch trip during 3 consecutive cycles. Unit is locked out for 4 hours or until 24 V power is recycled. How to fix →
84High-pressure lockout.High pressure switch trip during 3 consecutive cycles. Unit is locked out for 4 hours or until 24 V power is recycled. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a pressure switch to keep a unit running. Line-voltage work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Carrier 25HNB6 / 25HNB9 Infinity 2-Stage Heat Pump Installation Instructions, 25HNB6-9-4SI, Table 6 Troubleshooting, p. 13. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.