Home / Charts / Carrier heat pump codes

Carrier 25HPA Heat Pump Codes

Applies to: Carrier 25HPA (Performance Series single-stage heat pump, Puron, sizes 018-060, 2012 instructions). Amber STATUS light on the outdoor control board, two-digit status codes (green COMM light shows Infinity communication).

This chart is from the single-stage 25HPA instructions (25HPA-4SI, edition 12/12). The two-stage 25HPA6 has its own instructions; check the model number before you use these codes.

CodeMeaningWhat to check
16System communications failure.Communication with the user interface lost. Check wiring to the UI and the indoor and outdoor units.
31High pressure switch open.High-pressure switch trip. Check refrigerant charge, outdoor fan operation and coils for airflow restrictions (outdoor coil in cooling, indoor airflow in heating). How to fix →
32Low pressure switch open.Low-pressure switch trip. Check refrigerant charge and indoor airflow (cooling), or outdoor fan operation and outdoor coil (heating). How to fix →
45Control fault.Outdoor unit control board has failed and needs to be replaced.
46Brown out (24 V).Control voltage below 15.5 V for at least 4 seconds. Compressor and fan aren't allowed until control voltage is at least 17.5 V. Verify control voltage (allowable range 18-30 V).
53Outdoor air temperature sensor fault.Sensor not reading or out of range. Ohm out the sensor and check wiring.
55Outdoor coil sensor fault.Sensor not reading or out of range. Ohm out the sensor and check wiring. With a failed coil sensor, defrost runs at each interval and ends after 5 minutes. How to fix →
56Thermistors out of range.Improper relationship between the coil sensor and outdoor air sensor. Ohm out both sensors and check wiring. At 60°F the outdoor air thermistor should read about 16,000 ohms.
72Thermal cutout.Compressor voltage sensed after start-up, then absent for 10 seconds while demand exists. Possible causes: compressor internal overload trip, or loss of high voltage to the compressor without loss of control voltage. How to fix →
73Contactor shorted.Compressor voltage sensed with no demand for compressor operation. Contactor may be stuck closed, or there is a wiring error. How to fix →
74No 230 V at compressor.Compressor voltage not sensed when the compressor should be starting. Disconnect may be open, contactor may be stuck open, or there is a wiring error. How to fix →
82Thermal lockout.Thermal cutout in three consecutive cycles. Unit is locked out for 4 hours or until 24 V power is recycled. How to fix →
83Low-pressure lockout.Low pressure switch trip in 5 consecutive cycles. Unit is locked out for 4 hours or until 24 V power is recycled. How to fix →
84High-pressure lockout.High pressure switch trip in 5 consecutive cycles. Unit is locked out for 4 hours or until 24 V power is recycled. How to fix →

How to read the codes

Codes point to a circuit, not a part. Test before replacing anything, and never jumper a pressure switch to keep a unit running. Line-voltage work is for trained technicians, and refrigerant work requires EPA 608 certification.

Source: Carrier 25HPA Performance Series Heat Pump Installation Instructions, 25HPA-4SI (edition 12/12), Troubleshooting p. 13 and Table 7 Status Codes p. 14. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.