Carrier 25HPA Heat Pump Codes
This chart is from the single-stage 25HPA instructions (25HPA-4SI, edition 12/12). The two-stage 25HPA6 has its own instructions; check the model number before you use these codes.
| Code | Meaning | What to check |
|---|---|---|
| 16 | System communications failure. | Communication with the user interface lost. Check wiring to the UI and the indoor and outdoor units. |
| 31 | High pressure switch open. | High-pressure switch trip. Check refrigerant charge, outdoor fan operation and coils for airflow restrictions (outdoor coil in cooling, indoor airflow in heating). How to fix → |
| 32 | Low pressure switch open. | Low-pressure switch trip. Check refrigerant charge and indoor airflow (cooling), or outdoor fan operation and outdoor coil (heating). How to fix → |
| 45 | Control fault. | Outdoor unit control board has failed and needs to be replaced. |
| 46 | Brown out (24 V). | Control voltage below 15.5 V for at least 4 seconds. Compressor and fan aren't allowed until control voltage is at least 17.5 V. Verify control voltage (allowable range 18-30 V). |
| 53 | Outdoor air temperature sensor fault. | Sensor not reading or out of range. Ohm out the sensor and check wiring. |
| 55 | Outdoor coil sensor fault. | Sensor not reading or out of range. Ohm out the sensor and check wiring. With a failed coil sensor, defrost runs at each interval and ends after 5 minutes. How to fix → |
| 56 | Thermistors out of range. | Improper relationship between the coil sensor and outdoor air sensor. Ohm out both sensors and check wiring. At 60°F the outdoor air thermistor should read about 16,000 ohms. |
| 72 | Thermal cutout. | Compressor voltage sensed after start-up, then absent for 10 seconds while demand exists. Possible causes: compressor internal overload trip, or loss of high voltage to the compressor without loss of control voltage. How to fix → |
| 73 | Contactor shorted. | Compressor voltage sensed with no demand for compressor operation. Contactor may be stuck closed, or there is a wiring error. How to fix → |
| 74 | No 230 V at compressor. | Compressor voltage not sensed when the compressor should be starting. Disconnect may be open, contactor may be stuck open, or there is a wiring error. How to fix → |
| 82 | Thermal lockout. | Thermal cutout in three consecutive cycles. Unit is locked out for 4 hours or until 24 V power is recycled. How to fix → |
| 83 | Low-pressure lockout. | Low pressure switch trip in 5 consecutive cycles. Unit is locked out for 4 hours or until 24 V power is recycled. How to fix → |
| 84 | High-pressure lockout. | High pressure switch trip in 5 consecutive cycles. Unit is locked out for 4 hours or until 24 V power is recycled. How to fix → |
How to read the codes
- Short flashes are the first digit and long flashes the second. For example, 3 short then 2 long = code 32.
- A short flash is 0.25 seconds on and a long flash 1 second on, with 0.25 seconds between flashes, 1 second between the short and long groups, and 2.5 seconds off before the code repeats.
- On solid with no flash: standby, no call. 1 flash then pause: cooling or heating running normally. Only one fault code shows at a time: the most recent one with the highest priority.
- Codes 31 and 32: the contactor is de-energized and the outdoor fan keeps running for 15 minutes. After the 15-minute delay, if there's still a call and the switch has reset, the compressor restarts. Five trips in a row lock the unit out for 4 hours (83 or 84).
- Code 72: compressor voltage was sensed after start-up, then absent for 10 seconds with a call. The fan runs 15 minutes (if 230 V is present), then the control tries the compressor every 15 minutes. Three in a row lock the unit out for 4 hours (82).
Source: Carrier 25HPA Performance Series Heat Pump Installation Instructions, 25HPA-4SI (edition 12/12), Troubleshooting p. 13 and Table 7 Status Codes p. 14. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- How the heat pump defrost cycle works
- Checking heat pump charge in heat mode
- Look up any heat pump code
Other brands
- Lennox XP17 (Dave Lennox Signature two-stage heat pump, heat pump control A175)
- Lennox SL25XPV (Dave Lennox Signature variable-capacity heat pump, R-410A)
- Trane 5TWR4 (single-stage heat pump: 5TWR4018A1000A to 5TWR4060A1000A)
- Carrier 25HNB6 / 25HNB9 (Infinity two-stage heat pump, Puron)
- Carrier 25HNA6 / 25HNA9 (Infinity two-stage heat pump, Puron)
- Rheem / Ruud RP20 (EcoNet variable-speed heat pump, models (-)P20; e.g. RP2024AJVCA)
- Rheem / Ruud RA20 (EcoNet variable-speed air conditioner, models (-)A20)
- Goodman / Amana AVZC18 (Amana inverter heat pump, ComfortNet communicating)
- Goodman / Amana GSZC18 (Goodman two-stage heat pump, ComfortNet compatible)
- Goodman / Amana AVZC20 (Amana inverter heat pump, ComfortNet communicating)
- Goodman / Amana AVXC20 / GVXC20 (inverter air conditioner, ComfortNet communicating)
Did you find your code?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
HVAC Cheat Sheet · Free PT charts, code lookups and calculators for techs at hvaccheatsheet.com