Home / Charts / Manitowoc ice machine codes

Manitowoc Indigo NXT Ice Machine Codes

Applies to: Manitowoc Indigo NXT (air, water and remote cubers and flakers: IDT0300, IDT0420, IDT0450, IDT0500, IDT0620, IDT0750, IDT0900, IDT1200, IDT1500, IDT1900, IYT0300, IYT0420, IYT0450, IYT0500, IYT0620, IYT0750, IYT0900, IYT1200, IYT1500, IYT1900, IRT0500, IRT0620, IRT0750, IRT0900, IRT1900, IDF0300, IDF0500, IDF0600, IDF0900, IYF0300, IYF0500, IYF0600, IYF0900, IRF0900). Alert log on the touchscreen: an alert icon shows the number of messages.

CodeMeaningWhat to check
E01Long Freeze: freeze time reached 35 minutes three cycles in a row; the ice machine is off.At 35 minutes the board forces a harvest; after three in a row it stops. Manitowoc says to rule out external and electrical causes first (they are often intermittent: low night ambient, water pressure drops, water shut off). Water: dirty water level probe, water pressure under 20 or over 80 psig, water over 90°F, clogged distribution tube, fill or dump valve, water pump, water loss from the sump. Electrical: low voltage, ice thickness probe out of adjustment, harvest not initiated, contactor, compressor, fan cycling control or fan motor. Refrigeration: charge, head pressure control, harvest valve, compressor, TXV starving or flooding (check bulb mounting), non-condensables, restrictions, dirty condenser, hot inlet air or recirculation. How to fix →
E02Long Harvest: harvest time reached 7 minutes three cycles in a row; the ice machine is off.After a 7-minute harvest the board runs a thaw cycle (about 1 to 1.75 hours) and goes back to freeze; after three in a row it stops. Water: dirty evaporator, dump valve, vent tube missing on the water outlet drain, water freezing behind the evaporator, loose plastic extrusions or gaskets, clogged distribution tube. Electrical: ice thickness probe out of adjustment, bin switch closed or defective, premature harvest from the water level probes. Refrigeration: charge, head pressure control valve, harvest valve, TXV flooding (check bulb mounting), fan cycling control; on water cooled units, a water regulating valve that won't close in harvest. How to fix →
E03Input power loss.Logged when power to the machine was interrupted, stamped at power-up. Check the supply if it repeats.
E04High condenser temperature (display: Hi cnd Temp or Wtr Cnd Fault).The liquid line temperature (T1) is too high: an air cooled or water cooled condenser fault on self-contained machines. How to fix →
E05High pressure control opened (HPC Fault).The high pressure cutout switch (HPCO) opened. How to fix →
E07Starving TXV, single evaporator, or low on charge.The average evaporator inlet (T3) and outlet (T4) temperatures differed by more than 12°F in the last minute of the freeze cycle. How to fix →
E08TXV fault, single or dual circuit evaporators.The average evaporator inlet (T3) and outlet (T4) temperatures differed by more than 12°F in the last minute of the freeze cycle. How to fix →
E09Flooding evaporator fault, single evaporator, single circuit (Flood Evap1).The board compares the average compressor discharge line temperature (T2) over the first 6 minutes of freeze with the pre-chill T1 average plus 50°F; the handbook gives the trip as a difference of less than 1.05°F. How to fix →
E10Flooding evaporator fault, dual TXV, dual circuit (Flood Evap2).Same test as E09, on dual TXV, dual circuit evaporators. How to fix →
E11Refrigeration fault.From refrigeration start-up or pre-chill to 2 minutes into freeze, the discharge temperature didn't rise at least 10°F and the evaporator temperature didn't drop at least 10°F. How to fix →
E12Curtain switch fault: open more than 24 hours.The machine is set to make ice but has shown bin full for over 24 hours. The curtain switch is open or the curtain is off.
E15Fan cycle control fault: low liquid line temperature.The liquid line dropped below 60°F for more than a minute during freeze. Check the fan cycling control.
E16Remote condensing unit fault (CVD QuietQube only).The liquid line dropped below 40°F or went over 140°F for more than a minute during freeze.
E19Ice thickness probe fault.The probe's monitored frequency is out of range: probe unplugged or a problem with its microphone. The machine can run in safe mode for up to 72 hours.
E20Water system fault.Any of: high water probe sensed without the low probe; evaporator outlet below -10°F at 6.5 to 7.5 minutes into freeze; low water probe still satisfied at the end of harvest; low or high probe satisfied at the end of freeze. The machine can run in safe mode for up to 72 hours. How to fix →
E221T1 temperature sensor issue (liquid line or receiver inlet).During pre-chill the thermistor's average reading was outside the valid range. Check that thermistor with the handbook's thermistor check procedure.
E222T2 temperature sensor issue (compressor discharge).During pre-chill the thermistor's average reading was outside the valid range. Check that thermistor with the handbook's thermistor check procedure.
E223T3 temperature sensor issue (evaporator inlet).During pre-chill the thermistor's average reading was outside the valid range. Check that thermistor with the handbook's thermistor check procedure.
E224T4 temperature sensor issue (evaporator outlet).During pre-chill the thermistor's average reading was outside the valid range. Check that thermistor with the handbook's thermistor check procedure.
E25Bin level probe low sensor fault.The bin level thermistor read outside its valid range for 10 minutes straight.
E26T6 or T7 temperature sensor issue.The thermistor's average reading was outside the valid range.
E27T6 or T7 temperature sensor issue.The thermistor's average reading was outside the valid range.
E28iAuCS not detected.The iAuCS automatic cleaning option was selected but the board isn't connected. Clears as soon as the hardware is detected.
E29USB communication fault.No USB drive in the port, or a defective drive.
E30USB download fault.A download error from the USB drive, or a defective drive.
E31Safe mode.A water level probe or ice thickness probe failed, so the board is running from model data and past cycles. It runs up to 72 hours, then goes to standby and turns off. It exits on its own if the probe signal returns.
E32RS485 communication fault.The device in the RS485 port isn't communicating between the control board and the gateway.
E33Touchscreen fault.The touchscreen isn't plugged into the control board or is faulty.
E34Display fault.The touchscreen isn't plugged into the control board or is faulty.
E36Check sum error.Alert log only; set on power loss.
E37Watch dog alert.Alert log only: the microprocessor timed out, possibly from electrical noise.
E38UI comm alert.Alert log only: user interface communication error from a loose communication cable or a power interruption.

How to read the codes

Alarms point to a circuit, not a part. Test before replacing a board, thermistor or valve, and never bypass a safety to keep the machine running. Line-voltage work is for trained technicians, refrigerant work requires EPA 608 certification, and ice that touched a contaminated machine should be discarded.

Source: Manitowoc Indigo NXT Air/Water/Remote Condenser Ice Machines Technician's Handbook, Part No. 000015430 Rev 04 (4/22), Troubleshooting and Alert Log pp. 79-87, E01/E02 checklists pp. 88-91, Thermistor Matrix pp. 159-160 (copy hosted by KaTom). The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.