Hoshizaki KM-901M/1100M/1340M/1601M J Series Ice Machine Codes
| Code | Meaning | What to check |
|---|---|---|
| 1 beep | High evaporator temperature (over 127°F / 53°C). | A harvest problem: stuck hot gas valve or its relay, hot water entering the unit, stuck headmaster (remote units), or a shorted thermistor. How to fix → |
| 2 beeps | Harvest backup timer: harvest over 20 minutes for two cycles in a row. | Open thermistor, hot gas valve not opening, TXV or liquid line valve leaking by, low charge, inefficient compressor, or the water regulating valve leaking by. How to fix → |
| 3 beeps | Freeze timer: freeze cycle past the freeze timer setting for two cycles in a row. | Float switch stuck closed (up), inlet water valve or hot gas valve leaking by, pump motor not pumping, bad TXV, liquid line valve not opening, low charge, headmaster not bypassing, or an inefficient compressor. How to fix → |
| POWER LED blinks (red) | Freeze-up detection (board 2A9678-02 only): the thermistor reached 2°C (36°F) less than 30 seconds after the freeze cycle started, or in less than 90 seconds and 40 seconds faster than the previous cycle. | Work through Hoshizaki's freeze-up checklist. Hoshizaki asks you to contact its tech support (1-800-233-1940). Reset with ALARM RESET. How to fix → |
| POWER OK LED blinks (red) | Freeze-time correction (board 2A7664-02 only): maximum freeze time differential exceeded. | After 3 freeze-time correction cycles in 36 hours the yellow EXT HARVEST LED blinks too. Work through the freeze-up checklist. Reset with ALARM RESET. How to fix → |
| 6 beeps | Low voltage: control circuit at 92 VAC ±5% or less. | The red LED goes out while voltage protection is active. Resets on its own when the voltage is corrected. Check supply voltage under load and the control transformer. |
| 7 beeps | High voltage: control circuit at 147 VAC ±5% or more. | Resets on its own when the voltage is corrected. Check the supply and the transformer taps. |
How to read the codes
- Count the beeps. Fix the cause, then press ALARM RESET on the control board with the power on. Alarms 6 and 7 (voltage) reset on their own.
- Hoshizaki's alarm table lists the voltage alarms as types 6 and 7 next to 1, 2 and 3 Beep; they're shown here as 6 and 7 beeps.
- The green LEDs show where the machine is in its cycle. Newer boards (auxiliary code P-3 and later on KM-901/1100, P-0 and later on KM-1340/1601) label each LED: fill = WV; harvest = Comp, WV and FM/HGV (1 to 20 minutes); harvest pump time = Comp, PM, FM/HGV (0 to 50 seconds); freeze = Comp, PM (5 minutes to the freeze timer setting); anti-slush = Comp; pump-out = Comp, PM, FM/HGV, DV, WV (10 to 20 seconds).
- Older boards (P-2 and earlier on KM-901/1100, N-3 and earlier on KM-1340/1601) number the green LEDs 1 to 4, ordered 1, 4, 3, 2 from the board's outer edge: fill = 4; harvest = 1, 4, 2; harvest pump time = 1, 3, 2; freeze = 1; anti-slush = 1, 3; pump-out = 1, 4, 3, 2.
- Abbreviations: Comp compressor, DV drain valve, FM fan motor, FMR remote fan motor, FS float switch, HGV hot gas valve, HM headmaster (C.P.R.), LLV liquid line valve, PM pump motor, TXV expansion valve, WRV water regulating valve, WV inlet water valve.
Alarms point to a circuit, not a part. Test before replacing a board, thermistor or valve, and never bypass a safety to keep the machine running. Line-voltage work is for trained technicians, refrigerant work requires EPA 608 certification, and ice that touched a contaminated machine should be discarded.
Source: Hoshizaki Modular Crescent Cuber Service Manual, KM-901M_J, KM-1100M_J, KM-1340M_J, KM-1601MRJ, No. 73213 (revised 3-20-2026), LED Lights and Audible Alarm Safeties, pp. 71-72. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- Commercial ice machine troubleshooting (no ice, freeze-ups, harvest problems)
- Commercial refrigeration practice test
- Look up any ice machine code
Other brands
- Hoshizaki KM-350/420/520/660M J Series (modular crescent cubers: KM-350MAJ, KM-350MWJ, KM-420MAJ, KM-420MWJ, KM-420MRJZ, KM-520MAJ, KM-520MWJ, KM-520MRJ, KM-520MRJZ, KM-660MAJ, KM-660MWJ, KM-660MRJ, KM-660MRJZ)
- Hoshizaki KM MAK Series (modular crescent cubers: KM-322MAK, KM-330MAK, KM-522MAK, KM-530MAK, KM-622MAK, KM-730MAK, KM-930MAK2, KM-1130MAK2)
- Hoshizaki F MAK Series Flakers (modular flakers and cubelet: F-422MAK, F-622MAK-C, F-622MWK-C, F-622MRKZ-C, F-822MAK, F-822MWK, F-1022MAK, F-1022MWK, F-1022MRKZ, F-1022MLKZ; -C, -SC and -CB cubelet versions)
- Hoshizaki F-1530/2030 MK2 Flakers (modular flakers: F-1530MAK2, F-1530MWK2, F-1530MRKZ2, F-2030MWK2, F-2030MRKZ2, F-2030MRKZ3, F-2030MLKZ; -C and -SC cubelet versions)
- Scotsman Prodigy and Prodigy Plus Cubers (modular cubers C0322, C0522, C0722, C0330, C0530, C0630, C0830, C1030, C1448, C1848, C2148)
- Scotsman Prodigy Flaker and Nugget (flaked F0522, F0822, F1222, F1522; nugget N0422, N0622, N0922, N1322; includes Prodigy Plus D series)
- Manitowoc Indigo NXT (air, water and remote cubers and flakers: IDT0300, IDT0420, IDT0450, IDT0500, IDT0620, IDT0750, IDT0900, IDT1200, IDT1500, IDT1900, IYT0300, IYT0420, IYT0450, IYT0500, IYT0620, IYT0750, IYT0900, IYT1200, IYT1500, IYT1900, IRT0500, IRT0620, IRT0750, IRT0900, IRT1900, IDF0300, IDF0500, IDF0600, IDF0900, IYF0300, IYF0500, IYF0600, IYF0900, IRF0900)
Did you find your code?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
HVAC Cheat Sheet · Free PT charts, code lookups and calculators for techs at hvaccheatsheet.com