Hoshizaki F MAK Series Flakers Ice Machine Codes
| Code | Meaning | What to check |
|---|---|---|
| 1 beep | Low-water safety: the upper float switch stayed open more than 90 seconds after the inlet valve energized. | Resets on its own once the water supply is restored and the float switch closes. Check the water supply, inlet valve and float switch. How to fix → |
| 2 beeps | Control switch left in DRAIN for more than 15 minutes. | Resets on its own when the control switch is moved back to ICE. |
| 3 beeps | High-pressure switch: first or second trip within 1 hour. | Resets on its own once pressure drops and the switch closes. Look for the cause of high head pressure. How to fix → |
| 4 beeps | High-pressure switch: third trip within 1 hour. | Turn the power off and call for service. Hoshizaki recommends leaving the icemaker off until this alarm is resolved to avoid a possible catastrophic failure. How to fix → |
| 5 beeps | Freeze timer: inlet valve off more than 30 minutes since it last energized. | Manual reset (power off and on). Check for a float switch stuck up, inlet valve leaking by, bad TXV, liquid line valve not opening, low charge, headmaster not bypassing, or an inefficient compressor. How to fix → |
| 6 beeps | Low voltage: 92 VAC ±5% or less. | The green POWER LED turns off while voltage protection is active. Resets on its own when the voltage is corrected. |
| 7 beeps | High voltage: 147 VAC ±5% or more. | Resets on its own when the voltage is corrected. |
| 8 beeps (gear motor) | Gear motor fuse or protector open: the compressor control relay contacts failed to close (all models). | Turn the power off. Check the gear motor fuse or protector; replace the fuse or let the protector cool and reset. If it keeps tripping, call for service. |
| 8 beeps (evaporator thermistor) | Evaporator thermistor below -4°F (-20°C) at gear motor start-up (cubelet -C, -SC, -CB models only). | Turn the power off and call for service; Hoshizaki recommends leaving it off until resolved. Manual reset (power off and on). |
| 9 beeps | Bin control 2 (mechanical backup) open: control board K8 pins 3 and 4. | Manual reset (power off and on). Bin control 1 failed to shut the icemaker down, so the backup opened. S2 dip switch 7 must be ON on modular flakers and cubelet models, OFF on DCM and self-contained models. |
| 10 beeps | Evaporator thermistor reached -22°F (-30°C) for 3 cycles in a row (cubelet -C, -SC, -CB models only). | Turn the power off and call for service; Hoshizaki recommends leaving it off until resolved. Manual reset (power off and on). |
How to read the codes
- When a safety trips, the unit shuts down, the orange ALARM LED turns on and the board beeps the alarm number every 5 seconds. Count the beeps.
- Some alarms reset on their own once the cause is gone (1, 2, 3, 6, 7). The rest need a manual reset: turn the power off and on again.
- The green POWER LED shows proper control voltage. Sequence LEDs: fill = WTRIN (inlet valve); ice purge = GM (gear motor, 5 minutes); freeze = GM and COMP, with WTRIN on during refill until the upper float switch closes (alarm after 90 seconds); drain = DRAIN (2 seconds every hour on 1-in-1, up to 10 minutes on 1-in-12).
- To skip the 5-minute ice purge while diagnosing, press SERVICE on the control board after the gear motor starts (live terminals nearby).
- The larger F-1530 and F-2030 flakers use a shorter 1-9 beep list with different 8 and 9 meanings; they have their own chart.
- Abbreviations: CCR compressor control relay, Comp compressor, DV drain valve, EH evaporator heater, FM fan motor, FMR remote fan motor, FS float switch, GM gear motor, HM headmaster (C.P.R.), LLV liquid line valve, SLV suction line valve, TXV expansion valve, UFS upper float switch, WV inlet water valve.
Alarms point to a circuit, not a part. Test before replacing a board, thermistor or valve, and never bypass a safety to keep the machine running. Line-voltage work is for trained technicians, refrigerant work requires EPA 608 certification, and ice that touched a contaminated machine should be discarded.
Source: Hoshizaki Modular Flaker Service Manual, F-422MAK through F-1022M_K(Z), No. 73264 (revised 2-4-2026), LED Lights and Audible Alarm Safeties pp. 57-58, BC1 shutdown p. 20, dip switch settings p. 59. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.
Related
- Commercial ice machine troubleshooting (no ice, freeze-ups, harvest problems)
- Commercial refrigeration practice test
- Look up any ice machine code
Other brands
- Hoshizaki KM-901M/1100M/1340M/1601M J Series (modular crescent cubers: KM-901M_J, KM-1100M_J, KM-1340M_J, KM-1601MRJ)
- Hoshizaki KM-350/420/520/660M J Series (modular crescent cubers: KM-350MAJ, KM-350MWJ, KM-420MAJ, KM-420MWJ, KM-420MRJZ, KM-520MAJ, KM-520MWJ, KM-520MRJ, KM-520MRJZ, KM-660MAJ, KM-660MWJ, KM-660MRJ, KM-660MRJZ)
- Hoshizaki KM MAK Series (modular crescent cubers: KM-322MAK, KM-330MAK, KM-522MAK, KM-530MAK, KM-622MAK, KM-730MAK, KM-930MAK2, KM-1130MAK2)
- Hoshizaki F-1530/2030 MK2 Flakers (modular flakers: F-1530MAK2, F-1530MWK2, F-1530MRKZ2, F-2030MWK2, F-2030MRKZ2, F-2030MRKZ3, F-2030MLKZ; -C and -SC cubelet versions)
- Scotsman Prodigy and Prodigy Plus Cubers (modular cubers C0322, C0522, C0722, C0330, C0530, C0630, C0830, C1030, C1448, C1848, C2148)
- Scotsman Prodigy Flaker and Nugget (flaked F0522, F0822, F1222, F1522; nugget N0422, N0622, N0922, N1322; includes Prodigy Plus D series)
- Manitowoc Indigo NXT (air, water and remote cubers and flakers: IDT0300, IDT0420, IDT0450, IDT0500, IDT0620, IDT0750, IDT0900, IDT1200, IDT1500, IDT1900, IYT0300, IYT0420, IYT0450, IYT0500, IYT0620, IYT0750, IYT0900, IYT1200, IYT1500, IYT1900, IRT0500, IRT0620, IRT0750, IRT0900, IRT1900, IDF0300, IDF0500, IDF0600, IDF0900, IYF0300, IYF0500, IYF0600, IYF0900, IRF0900)
Did you find your code?
One field tip a week
A short, practical HVAC tip in your inbox every week: diagnostics, charging, airflow and code changes. Free, unsubscribe anytime.
We'll only use your email for the newsletter. Privacy policy.
HVAC Cheat Sheet · Free PT charts, code lookups and calculators for techs at hvaccheatsheet.com