Hoshizaki F MAK Series Flakers Ice Machine Codes

Applies to: Hoshizaki F MAK Series Flakers (modular flakers and cubelet: F-422MAK, F-622MAK-C, F-622MWK-C, F-622MRKZ-C, F-822MAK, F-822MWK, F-1022MAK, F-1022MWK, F-1022MRKZ, F-1022MLKZ; -C, -SC and -CB cubelet versions). Beeps every 5 seconds and the orange ALARM LED on control board 2A9874-03.

CodeMeaningWhat to check
1 beepLow-water safety: the upper float switch stayed open more than 90 seconds after the inlet valve energized.Resets on its own once the water supply is restored and the float switch closes. Check the water supply, inlet valve and float switch. How to fix →
2 beepsControl switch left in DRAIN for more than 15 minutes.Resets on its own when the control switch is moved back to ICE.
3 beepsHigh-pressure switch: first or second trip within 1 hour.Resets on its own once pressure drops and the switch closes. Look for the cause of high head pressure. How to fix →
4 beepsHigh-pressure switch: third trip within 1 hour.Turn the power off and call for service. Hoshizaki recommends leaving the icemaker off until this alarm is resolved to avoid a possible catastrophic failure. How to fix →
5 beepsFreeze timer: inlet valve off more than 30 minutes since it last energized.Manual reset (power off and on). Check for a float switch stuck up, inlet valve leaking by, bad TXV, liquid line valve not opening, low charge, headmaster not bypassing, or an inefficient compressor. How to fix →
6 beepsLow voltage: 92 VAC ±5% or less.The green POWER LED turns off while voltage protection is active. Resets on its own when the voltage is corrected.
7 beepsHigh voltage: 147 VAC ±5% or more.Resets on its own when the voltage is corrected.
8 beeps (gear motor)Gear motor fuse or protector open: the compressor control relay contacts failed to close (all models).Turn the power off. Check the gear motor fuse or protector; replace the fuse or let the protector cool and reset. If it keeps tripping, call for service.
8 beeps (evaporator thermistor)Evaporator thermistor below -4°F (-20°C) at gear motor start-up (cubelet -C, -SC, -CB models only).Turn the power off and call for service; Hoshizaki recommends leaving it off until resolved. Manual reset (power off and on).
9 beepsBin control 2 (mechanical backup) open: control board K8 pins 3 and 4.Manual reset (power off and on). Bin control 1 failed to shut the icemaker down, so the backup opened. S2 dip switch 7 must be ON on modular flakers and cubelet models, OFF on DCM and self-contained models.
10 beepsEvaporator thermistor reached -22°F (-30°C) for 3 cycles in a row (cubelet -C, -SC, -CB models only).Turn the power off and call for service; Hoshizaki recommends leaving it off until resolved. Manual reset (power off and on).

How to read the codes

Alarms point to a circuit, not a part. Test before replacing a board, thermistor or valve, and never bypass a safety to keep the machine running. Line-voltage work is for trained technicians, refrigerant work requires EPA 608 certification, and ice that touched a contaminated machine should be discarded.

Source: Hoshizaki Modular Flaker Service Manual, F-422MAK through F-1022M_K(Z), No. 73264 (revised 2-4-2026), LED Lights and Audible Alarm Safeties pp. 57-58, BC1 shutdown p. 20, dip switch settings p. 59. The "meaning" column follows the manufacturer's wording; "what to check" is our field summary. Always go by the label on the unit you're working on.